The text of a manual · part 4 of 20
Do-more T1H Series PLC Hardware User Manual: Chapter 1. Getting Started, pages 21 to 28
Pages 21 to 28 of 168, from Do-more T1H Series PLC Hardware User Manual
The original document is the PDF (40 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect T1K-08B, Konnect-It T1K-08B and Koyo T1K-08B
Page 21
Chapter 1: Getting Started
The popup shown here will allow you to choose whether or not to install a shortcut for the software on your PC’s desktop. Click Yes or No to continue with the installation.
The software will now install the needed files and folders with the Setup Status window detailing the status of the installation. Once the installation has been successfully completed, the window below will open. Your software is now installed and ready to use. The installation wizard can now be closed by clicking the Finish button at the bottom of the window.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
1–9
Page 22
Chapter 1: Getting Started
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Step 2: Launch Do-more Designer Software
1–10
After installing Do-more Designer, launch the software by double clicking the desktop DM icon. You can also launch the software from the PC’s Start menu or All Programs menu. If the software link is not embedded in the Start menu, use the path: Start > All Programs > Do-more > Designer x.x > Do-more Designer x.x to launch the software. NOTE: Software version 1.2 or greater is required.
The Do-more Designer Software will start up and display the Start Page shown below. This page consists of a Launchpad with quick links to existing projects, software applications and communications links. There is also a section containing shortcuts to important help file topics and the Do-more Designer simulator application.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 23
Chapter 1: Getting Started To begin a new project offline select New from the toolbar on the Start Page. The New Project window seen here will open. Name the new project and select the type of controller it is intended for. Use the Browse button to choose a different location to store the project or accept the default location. Click OK after your selections have been made to continue. The Main programming window and Instruction Palette shown below will open. The Instruction Palette lists all of the instructions available for use in your program. A brief explanation of each instruction is provided once the instruction is highlighted and a more detailed explanation is available in the help file. The Main programming window is divided into menus and toolbars for quick access to configurations, instructions and other needed items used during project development.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 1–11
Page 24
Chapter 1: Getting Started
Step 3: Install Hardware
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 1–12
The “Installation and Wiring” chapter of this manual contains detailed information for the installation of components in your Do-more T1H Series PLC system. The 3 following summary explains the basic steps for installing modules in a base. 1 • First, insert module into base: 1. Pull base arm back to allow space for module to enter base. 2. Align module slides with base track. 3. Press module firmly into base.
• Next, mount the components on the DIN Rail:
2
NOTE: Do not force the modules on the DIN rail. Due to slight size variations in different manufacturers’ DIN rail, it may be necessary to first unlatch the locking tab, rotate the module into place, then latch the locking tab.
1. Make sure the locking tab is in the latched position (pushed in). 2. Hook upper tab over upper flange of DIN rail. 3. Tilt the unit toward DIN rail until it snaps securely to DIN rail.
2
3
1
• Finally, slide the module assembly into position on the DIN Rail: Slide the module assembly on the DIN rail until the clip arm attaches securely to the adjacent module. T1H-DM1E TERM
RUN I/O ERR
RUN
STOP
USB TX RX
USB PGM PORT
NOTE: One power supply is required in the leftmost component position followed by the CPU. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements. Each power supply powers the modules to its right, but is interrupted by the next power supply. WARNING: Minimize the risk of electrical shock, personal injury, or equipment damage. Always disconnect the system power before installing or removing any system component.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 25
Chapter 1: Getting Started Once all of the modules have been installed, connect the USB cable. Use a standard USB cable with Type A and Type B connectors. (Ethernet and Serial connections are also available, but are not shown for this example.)
T1H-DM1E TERM
RUN I/O ERR
RUN
STOP
USB TX RX
USB PGM PORT
1 2 3 4 Step 4: Apply Power to the PLC 5 Power is supplied to the Do-more T1H Series PLC through the backplane of the base from the power supply. The following diagram and table show the terminal connections located on Terminator power supplies and their specifications. 6 110/220 VAC Terminal Strip 1 7 8 9 10 11 110/220 VAC Terminal Strip 12/24 VDC Terminal Strip 12 110/220 VAC Terminal Strip 12/24 VDC Terminal Strip 13 14 Power Supply T1K-01AC T1K-01DC Wire Size A Recommended Torque B NOTE: You can connect either a 115VAC or 220VAC supply to the AC terminals. C Once all of the power wiring has been completed and verified, connect the appropriate voltage source to the power supply and power up the system. The Do-more T1H Series PLC will D Solid: 24–12 AWG Stranded: 24–12 AWG 4.43–5.31 lb·in (0.5–0.6 N·m)
Type B
Type A
Solid: 24–12 AWG Stranded: 24–12 AWG 4.43–5.31 lb·in (0.5–0.6 N·m)
perform a self evaluation once power is applied. Refer to the “Installation and Wiring” chapter of this manual for more power supply and input wiring information.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
1–13
Page 26
Chapter 1: Getting Started
Step 5: Establish Communication
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 1–14
Now that the Do-more T1H Series PLC is powered up, you need to establish a communications link between the PC and the PLC. The Do-more Designer software provides a Link Wizard to assist you with configuring this new communications link. To open the Link Wizard, select the New Link... button in the Links section of the Main Page’s Launchpad as shown below.
The Link Wizard will first ask you to choose which communications port you will be using. In this example, we will be using a USB connection. Select USB, click Next and the wizard will automatically search for available CPU’s on that port.
Choose the CPU that you are programming and select Next. The Do-more Designer software will create a link to that controller. The Link Wizard will now display the saved settings for this link as seen on following page. Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 27
Chapter 1: Getting Started A unique name is required for each link that is created. Name the new link and, if desired, give it a description then select Finish. You can also manually configure each link by selecting the Link Editor... button from the lower left corner of the Link Wizard. The Configure Link dialog will open, as seen below, allowing you to select PLC types, port parameters, and protocols.
Once you have completed configuring your communications link, either manually with the Link Editor or automatically with the Link Wizard, it will be available to select in the Links section of the Launchpad. There you can edit, enable/disable, delete or view statistics for that link.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
1–15
Page 28
Chapter 1: Getting Started
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 1–16
Now select the New Online button and the Online dialog box, seen below, will open. From this dialog, you are given available communications links to choose from with options to add, edit disable/enable, or delete links. Choose the appropriate link, select OK and the software will connect to the Do-more T1H Series PLC. If the mode selector switch on the CPU module is not in the Term position when connecting, the warning shown below will appear.
You are allowed to continue if you wish or place the mode selector switch on the CPU module in the Term position to avoid any unintended communication errors. If you were connecting to the CPU module with a project created offline, you may encounter the message window shown here.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M