Do-more T1H Series PLC Hardware User Manual: Chapter 3. Specifications - CPU Modules
Pages 49 to 60 of 168, from Do-more T1H Series PLC Hardware User Manual
The original document is the PDF (40 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect T1K-08B, Konnect-It T1K-08B and Koyo T1K-08B
Page 49
Specifications - CPU Modules In This Chapter:
Chapter
3
CPU Specifications . ................................................................................................. 3–2 CPU General Specifications. ...................................................................................... 3–2 Communications Ports Specifications. ...................................................................... 3–4 Port 1 Specifications (USB)........................................................................................ 3–4 Port 2 Specifications (Serial)...................................................................................... 3–4 Port 3 Specifications (Ethernet)................................................................................. 3–5 Ethernet I/O. .............................................................................................................. 3–6 Status Indicators......................................................................................................... 3–8 Mode Switch Functions.............................................................................................. 3–8 Dip Switch Specifications........................................................................................... 3–9 Battery Replacement................................................................................................ 3–12
Page 50
Chapter 3: Specifications - CPU Modules
CPU Specifications
1 CPU General Specifications Feature T1H-DM1 2 Total Memory (bytes) Ladder Memory words) 3 (instruction V-Memory (words) V Memory (words) 4 Non-volatile D-memory (DWORDs) 5 Non-volatile D Memory (DWORDs) R-memory (REAL DWORDs) R Memory 6 Non-volatile (REAL DWORDs) execution 7 Boolean Stage Programming 8 Number of Stages Handheld Programmer 9 Programming Software for Windows communications ports 10 Built-In Program Memory 11 Total I/O points available Number of Local I/O Modules 12 Max Local I/O points available 13 Ethernet I/O Discrete points Ethernet I/O Analog I/O Channels 14 Max Number of Ethernet slaves per PLC A I/O points on Ethernet I/O Discrete I/O Module Point Density B Number of instructions available Control relays relays (system defined) C Special Special registers (system defined) D Timers Counters
T1H-DM1E
262,144 bytes
65,536 instruction words
T1H-DM1
Configurable up to 65536 (4096 default) Configurable up to 65536 (4096 default)
STAT
Configurable up to 65536 (4096 default) Configurable up to 65536 (4096 default) Configurable up to 65536 (4096 default) Configurable up to 65536 (4096 default) 50µs Yes
T1H-DM1
128 per Program code-block; number of code-blocks configurable to memory limit No
FREE Do-more Designer
USB, RS-232
USB, RS-232, Ethernet (10/100 Base-T) Flash ROM
X, Y, each configurable up to 65536 (2048 default); WX, WY (analog in/out) each configurable up to 65536 (256 default)
T1H-DM1E
STAT
16 256 131,072 32,768 16 32,768
T1H-DM1E
8/16
>160
>170
Configurable up to 65536 (2048 default) 1024 512
Configurable up to 65536 (256 default) Configurable up to 65536 (256 default)
System Date/Time structures
3–2
8
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 51
Chapter 3: Specifications - CPU Modules
Feature
CPU General Specifications (continued) T1H-DM1
User Date/Time structures ASCII String/Byte buffer structures
T1H-DM1E
Configurable up to 65536 (32 default) Configurable up to memory limit (192 default)
Modbus Client memory
Yes, configurable up to memory limit, default 1024 input bits, 1024 coil bits, 2048 input registers, 2048 holding registers
DL Classic Client memory Immediate I/O Interrupt input (hardware / timed) Subroutines Drum Timers Table Instructions Loops Math
Up to memory limit, default 512 X, 512 Y, 512 C, 2048 V No No Program and Task code-blocks, up to memory limit Yes, up to memory limit Yes FOR/NEXT, WHILE/WEND, REPEAT/UNTIL loops >60 operators and functions: Integer, Floating Point, Trigonometric, Statistical, Logical, Bitwise, Timing
ASCII
Yes, IN/OUT, Serial, Ethernet TCP and UDP; 11 output script commands
PID Loop Control, Built In Time of Day Clock/Calendar Run Time Edits Supports True Force Internal Diagnostics Password security System error log User error log Battery backup
Yes, configurable to memory limit (over 2,000) Yes Yes Yes Yes Multi-user, credentialed, session-based security Yes Yes Yes (Battery included)
Do-more Designer V1.2 or newer must be used with these Do-more T1H CPU modules.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–3
Page 52
Chapter 3: Specifications - CPU Modules
Communications Ports Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–4
Port 1 Specifications (USB) USB Port: This port has a USB Type B female connector and requires a USB Type A-B cable. • Do-more programming protocol only
USB Type B Slave Input Specifications Description
Standard USB 2.0 Slave input for programming and online monitoring only, with built-in surge protection. Not compatible with older full speed USB devices.
Cables
USB Type A to USB Type B: USB-CBL-AB3 (3ft) USB-CBL-AB6 (6ft) USB-CBL-AB10 (10ft) USB-CBL-AB15 (15ft)
(ADC part #)
1 2 3 4
USB Port 1 5V DD+ 0V
Bus Voltage Sense Data Data + Ground
Port 2 Specifications (Serial) RS-232 Port: Serial RS-232 multipurpose communications port: • Full-duplex • 1024B buffer • RJ-12 connector
RJ-12 style connector used for: • Do-more programming protocol • RTU Master connections • RTU Slave connections • Incoming and Outgoing communications • Protocol Incoming and Outgoing communications
RS-232 Specifications
Description
Non-isolated, full duplex RS-232 DTE port used for programming, online monitoring or can connect the CPU as an ASCII or Modbus RTU master or slave to a peripheral device. Includes ESD and built-in surge protection.
Communications
1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 Baud 220mA maximum at 5V, ±5%. Reverse polarity and overload protected.
+5V Cable Power Source Maximum Output Load (TXD/RTS) Minimum Output Voltage Swing Output Short Circuit Protection Cable Options
3kV, 1,000pf ±5V ±15mA D2-DSCBL USB-RS232 with D2-DSCBL FA-CABKIT FA-ISOCON for converting RS-232 to isolated RS-422/485 EA-MG-PGM-CBL
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 53
Chapter 3: Specifications - CPU Modules 1 2 3 4 5 6
RS-232 Port 2
0V 5V RXD TXD RTS CTS
Power (-) connection (GND) Power (+) connection (220mA max) Receive Data (RS-232) Transmit Data (RS-232) Request to Send (RS-232) Clear to Send (RS-232)
Port 3 Specifications (Ethernet) Port: Programming and Modbus TCP Client/Server port with 10/100 Base-T Ethernet RJ45 connector. RJ-45 style connector used for: • Do-more programming protocol • TCP Client connections (Modbus requests sent from the CPU) • TCP Server connections (Modbus requests received by the CPU) • I/O Master
Ethernet Specifications Description
Standard transformer isolated Ethernet port with built-in surge protection for programming, online monitoring, Modbus/TCP client/server connections (fixed IP or DHCP) and Ethernet I/O capabilities.
Transfer Rate
10/100 Mbps
Cables
Use a Patch (Point to Point) cable when a switch or hub is used. Use a Crossover cable when a switch or hub is not used.
NOTE: The Ethernet port can support all the functions listed above at the same time. However, it is important to consider the implications to network traffic and network topology. Since there is just one Ethernet port available, it will not be possible to use multiple functions and have an isolated network for Ethernet I/O, as is recommended. Utilize the adjustable poll rates of Ethernet I/O and Modbus TCP Clients (if auto-polling) to limit the impact on your network. 8 1
NOTE: The above diagram illustrates the standard wire positions in the RJ45 connector. It is recommended that all 10/100 Base-T cables be Category 5, UTP cables.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–5
Page 54
Chapter 3: Specifications - CPU Modules
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Ethernet I/O
3–6
The T1H-DM1E CPU’s built-in Ethernet port can be configured as an Ethernet I/O master. The Ethernet I/O feature allows expansion beyond the local chassis to slave I/O using the onboard high-speed Ethernet link. The onboard Ethernet port can support up to 16 slave devices. The slave I/O modules supported are: • H2-EBC100 • T1H-EBC100 (Terminator I/O) • GS-EDRV100 (GS Drives)
The Ethernet I/O network uses Category 5 UTP cables for cable runs up to 100 meters (328 ft.) with extended distances achieved through Ethernet switches. Ethernet I/O Example Stride Ethernet Switch
Do-more T1H-DM1E CPU T1H-DM1E TERM
RUN I/O ERR
RUN
STOP
USB TX RX
USB PGM PORT
DirectLOGIC DL205 I/O with H2-EBC100 Module
C-more Operator Interface GS-EDRV100
Terminator I/O with T1H-EBC100 Module
GS Drive
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 55
Chapter 3: Specifications - CPU Modules Ethernet I/O functionality is enabled through the System Configuration dialog of Do-more Designer. Under the PLC drop down menu, select System Configuration. Then, from the System Configuration window select the CPU Configuration option under the Configuration Entries column. Finally, left-click the Enable Ethernet I/O Master checkbox in the Ethernet I/O Master section of the T1H-DM1E CPU Configuration window as seen below.
For more information on the setup, use and options available with Ethernet I/O, refer to the Ethernet I/O Master section of Do-more Designer Help File topic DMD0247.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–7
Page 56
5)
Chapter 3: Specifications - CPU Modules
Status Indicators Do-more T1H CPU modules have multi-color LEDs that are used to visually provide operational status to the user. 1 T1H-DM1E LED Indicators ver 2 Indicator Status Description RUN 3 ROM STAT 4 STAT* 5 USB 6 TX RX 7 ACTIVITY 100 MBIT 8 In addition to the individual definition of each LED, there are times when the controllers will 9 use combinations of the LED ON/OFF state and colors to convey status information. The following combinations use some or all of the LEDs: 10 • LED is blinking RED for (15 seconds) - Do-more Designer can blink the STAT LED for 15 seconds to verify that a communication link is targeting the correct controller. 11 • six (6) of the LEDs are ON and the color of each LED is GREEN - indicates the operating system has started running. • six (6) of the LEDs are cycling through RED and GREEN, in a circular ‘chase’ pattern 12 indicates the operating system is initializing. • left-most three (3) LEDs are cycling through RED and GREEN, in a ‘bouncing ball’ pattern 13 - indicates the controller is running only the boot loader and is NOT going to load and run the operating system. The most likely cause is having DIP switch #1 in the ON position. 14 • six (6) of the LEDs are ON and the color of each LED is RED - indicates the hardware watchdog timer has expired because the controller’s operating system has stopped running. A Mode Switch Functions T1H-DM1E B Mode Switch Functions Mode Switch Position CPU Action C RUN (Run Program) TERM (Terminal) D STAT Green
ACTIVITY
RS232 SERIAL PORT
100 MBIT
10/100 BASE-T ETHERNET PORT
CPU is in RUN Mode
Yellow
Forces are Active
Yellow Red* Yellow
CPU is updating Non-volatile Memory CPU Fatal Error Low Battery
Green
Status OK (good)
Green
USB Receive Activity
Yellow
USB Transmit Activity
Green
RS-232 Transmit Activity
Green
RS-232 Receive Activity
Green
Ethernet Port Activity
Yellow
Ethernet Port communicating at 100 MBIT Rate
* See Do-more software manual to further investigate what type of error has occurred.
CPU is forced into RUN Mode if no errors are encountered. RUN, PROGRAM and the DEBUG modes are available. In this mode, the mode of operation can be changed through the Do-more Designer Software.
STOP (Stop Program)
3–8
CPU is forced into STOP Mode.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 57
Chapter 3: Specifications - CPU Modules As mentioned in the previous table, the CPU mode can also be changed through the programming software if the mode switch is placed in the TERM position. In this position, the CPU can be changed remotely between the Run and Program modes. For more information on changing CPU modes through the software, see the “Step 9: Write Project to the Do-more PLC” section of Chapter1 “Getting Started”. When power is applied to the system, the controller will go through it’s power-up sequence then either stay in Program mode if the mode switch is in the STOP position, or attempt to go to Run mode if the mode switch is in the RUN position. If the mode switch is in the TERM position, the controller will return to the last operational mode before power was lost. For example, if the controller was in Run mode when power was lost, when power is restored and the mode switch is in the TERM position, the controller will attempt to return to Run mode.
1 2 3 4 5 DIP Switch Specifications Do-more controller’s circuit board has a block of DIP switches that are used to perform 6 various debug and reset operations. The DIP switch settings are only read when the system is first powered up. Changing the settings of the DIP switches requires that the system 7 containing the controller be powered down and the CPU removed. The DIP switches can then be changed as required. The DIP switch block is located on the right side of the CPU 8 under a small cover. Once the switches have been set, the CPU can then be reinstalled in the system and powered back up. The default position for all of the 9 DIP switches is OFF. The table below describes the position and 10 function associated with each DIP switch. 11 12 DIP Switch Settings Do-more T1H controllers 13 Switch Switch make use of combinations of Function DIP switch settings and the Number Position 14 Mode switch on the front of the 0 1 controller to perform two reset functions. These reset functions A can only be performed when the 2 controller is in the boot loader. B 3 4 C 5 6 D 7 7 6 5 4 3 2 1 0
ON ON
Load the last copy of the operating system. Do not load an Operating System, stay in the Booter.
ON
Disable the hardware watchdog timer - the hardware watchdog is always enabled, but this switch allows the user to override the ability of the Force Watchdog Error (WATCHDOG) and Debug Mode to generate a Watchdog condition.
ON ON ON ON ON
All 8
ON
ON
Disable ability to update the firmware and/or gate array. Reserved
Reset the TCP/IP Network Settings to factory default values Must be used with DIP #1 Clears everything from the controller (see details in the following pages)
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
3–9
Page 58
Chapter 3: Specifications - CPU Modules
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–10
The following sequence describes the steps necessary to perform one of the reset operations. This combination of DIP switch settings and mode switch manipulation is purposely complex to prevent these reset operations from being accidentally executed. Clear only the Network Settings This reset function will clear ONLY the Network settings, which consists of the Module ID, Module Name, Module Description, IP Address, Subnet Mask and Gateway Address. • Begin by powering down the controller. • the controller from the base and record the location of the DIP switches (so they can be set back to their original position after the manual reset is finished). • set ONLY DIP #1 and #7 ON to perform the Clear Only the Network Settings operation, make sure all other DIP switches are OFF. • Reinstall the controller in the base. • Set the controller mode switch to TERM (the center location) and power up the controller. • this point the LEFT bank of 3 LEDs should be blinking the ‘stay in the boot loader sequence’, that is, they should be blinking in sequence, from top to bottom then back to the top, alternating between red and green. • Move the controller mode switch to RUN (to the left). • Move the controller mode switch to TERM (to the center). • Move the controller mode switch to RUN (to the left). • Move the controller mode switch to TERM (to the center). • Move the controller mode switch to STOP (to the right). • the controller mode switch to TERM (to the center) - the LEFT bank of 3 LEDs should now be ON. NOTE: If you want to terminate the reset at this point you can do so by moving switch to RUN instead of STOP or powering down the controller.
• the controller mode switch to STOP (to the right) - the RIGHT bank of 3 LEDs should now be ON. NOTE: If you want to terminate the manual reset at this point you can only do so by powering down the controller.
• the controller mode switch to TERM (to the center) - the LEFT bank LEDs begin flashing the power up sequence, and the ROM led should briefly be ON indicating that the data in the ROM is being rewritten. The LEDs will then begin flashing the ‘staying in boot loader’ sequence indicating the reset is complete. • Power down the controller. • Remove the controller from the base and return the DIP switches to their original positions. • Set the controller mode switch to TERM (in the center location).
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 59
Chapter 3: Specifications - CPU Modules Clear All This reset function will clear everything from the controller, this includes the Network Settings as described previously, and the System Configuration, Memory Configuration, all control logic, all Documentation, and all of the User Accounts and Passwords. • Begin by powering down the controller.
1 2 • the controller from the base and record the location of the DIP switches (so they can be set 3 back to their original position after the manual reset is finished). • Next set all eight of the DIP switches ON to perform the Clear All operation. 4 • Reinstall the controller in the base. • Set the controller mode switch to TERM (the center location) and power up the controller. 5 • this point the LEFT bank of 3 LEDs should be blinking the ‘stay in the boot loader sequence’, that is, they should be blinking in sequence, from top to bottom then back to the top, alternating 6 between red and green. • Move the controller mode switch to RUN (to the left). 7 • Move the controller mode switch to TERM (to the center). • Move the controller mode switch to RUN (to the left). 8 • Move the controller mode switch to TERM (to the center). • Move the controller mode switch to STOP (to the right). 9 • the controller mode switch to TERM (to the center) - the LEFT bank of 3 LEDs should now be ON. 10 NOTE: If you want to terminate the reset at this point you can do so by moving switch to RUN instead of STOP or powering down the controller. 11 • the controller mode switch to STOP (to the right) - the RIGHT bank of 3 LEDs should now be ON. 12 NOTE: If you want to terminate the manual reset at this point you can only do so by powering down the 13 controller. • the controller mode switch to TERM (to the center) - the LEFT bank LEDs begin flashing the 14 power up sequence, and the ROM led should briefly be ON indicating that the data in the ROM is being rewritten. The LEDs will then begin flashing the ‘staying in boot loader’ sequence indicating A the reset is complete. • Power down the controller. B • Remove the controller from the base and return the DIP switches to their original positions. • Set the controller mode switch to TERM (in the center location). C D Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
3–11
Page 60
Chapter 3: Specifications - CPU Modules
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Battery Replacement
3–12
All Do-more controllers have an onboard battery that maintains the contents of the retentive memory any time the power to the controller is lost. The battery has an expected lifespan of three years; after which the battery will need to be replaced. The battery is a standard CR2032, coin cell battery. AutomationDirect part number: D0-MC-BAT. When the controller detects that the battery voltage is too low, and needs to be replaced, the ERR LED will be YELLOW. When Do-more Designer is online with the controller, the system-defined location $BatteryLow will be ON as well. NOTE: Make sure to have a current copy of the Do-more Designer project saved to Disk before performing this operation.
• Power down the system containing the controller. • Remove the controller from the system. • open the front cover and remove the battery from it’s holder that is located in the lower left corner. The battery is removed by pushing on the back of the battery to begin sliding it out of the holder, then pulling it the rest of the way out by the front edge of the battery. Make note of how the battery is aligned in the holder. T1H-DM1 and T1H-DM1E Battery Replacement Part # D0-MC-BAT
NOTE: The controller has an onboard capacitor that will maintain the retentive memory contents while the battery is being replaced. This capacitor has a two-hour runtime (minimum), which should be more than enough to replace the battery.
• the new battery into the holder, making sure the alignment is correct, and close the cover. • Reinstall the controller in the system. • Power up the system containing the controller. • that the ERR LED is not YELLOW and the system-defined location $BatteryLow will be OFF. Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M