Page 61
Specifications Terminal Bases and Power Supplies In This Chapter:
Chapter
14
T1K-08B(-1) I/O Terminal Base............................................................................. 4–2 T1K-16B(-1) I/O Terminal Base............................................................................. 4–2 T1K-01AC, T1K-01DC Power Supply..................................................................... 4–4 Calculating the Power Budget.............................................................................. 4–6
Page 62
Chapter 4: Specifications - Terminal Bases and Power Supplies
T1K-08B(-1) I/O Terminal Base
1 Specifications Specification T1K-08B 2 3 4 5 *Twist stranded conductors before inserting into gate. 6 7 T1K-16B(-1) I/O Terminal Base Specifications 8 Specification T1K-16B 9 10 11 12 *Twist conductors before inserting into gate. 13 Environmental Specifications 14 A B C D Screw type
Spring clamp type
Recommended Torque
1.77–3.54 lb·in (0.2–0.4 N·m)
N/A
Recommended Screwdriver Blade Size
0.02 in. X 0.125 in. (0.5 mm X 3.0 mm)
Weight
Solid conductor: 25–12 AWG Stranded conductor: 26–12 AWG* 135g
Push in on clamp using screwdriver blade size: 0.016 X 0.79 in. to 0.032 X 0.16 in. (0.4 mm X 2mm to 0.8 mm X 4mm) Solid conductor: 25–14 AWG Stranded conductor: 26–14 AWG* 125g
Terminal Type
Screw type
Spring clamp type
Recommended Torque
1.77–3.54 lb·in (0.2–0.4 N·m)
N/A
Recommended Screwdriver Blade Size
0.02 in. X 0.125 in. (0.5 mm X 3.0 mm)
Wire Gauge Size
Wire Gauge Size Weight
Ambient Operating Temperature Storage Temperature Ambient Humidity Atmosphere
Vibration Resistance Shock Resistance Voltage Withstand Insulation Resistance Noise Immunity
Agency Approvals
4–2
T1K-08B-1
Terminal Type
Solid conductor: 25–12 AWG Stranded conductor: 26–12 AWG* 220g
T1K-16B-1
Push in on clamp using screwdriver blade size: 0.016 X 0.79 in. to 0.032 X 0.16 in. (0.4 mm X 2mm to 0.8 mm X 4mm) Solid conductor: 25–14 AWG Stranded conductor: 26–14 AWG* 210g
32!F to 131!F (0!C to 55!C) -4!F to 158!F (-20!C to 70!C) 5% to 95% (Non-condensing) No corrosive gases. The level of environmental pollution = 2 (UL 840). MIL STD 810C. Method 514.2 MIL STD 810C. Method 516.2 1500VAC, 1 minute 500VDC, 10Mq NEMA ICS3-304 Impulse Noise 1es, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm) UL E185989, CE, FCC class A
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 63
Chapter 4: Specifications - Terminal Bases and Power Supplies
T1K-08B, T1K-08B-1
T1K-16B, T1K-16B-1
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 4–3
Page 64
Chapter 4: Specifications - Terminal Bases and Power Supplies
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
T1K-01AC, T1K-01DC Power Supply
4–4
Specifications Specification Input Voltage Range Input Frequency Maximum Power Maximum Inrush Current Insulation Resistance Voltage Withstand (Dielectric) Auxiliary 24VDC Supply Voltage Output 1: 5VDC Current Base Power Supplied Ripple Voltage Output 2: 24VDC Current Base Power Supplied Ripple Replacement Terminal Block Phoenix Contact Fuse
T1K-01AC
T1K-01DC
110/220 VAC (85–264 VAC) 12/24 VDC (10.8–26.4 VDC) 50/60 Hz (47–63 Hz) 50VA 20W 20A 10A >10Mq @ 500VDC 1 min. @ 1500VAC between primary, secondary and field ground 300mA maximum 5.25 VDC (5.00–5.50 VDC) 5.25 VDC (5.00– 5.50 VDC) a) 2.0 A maximum 2.0 A maximum b) 1.5 A maximum (see note) 5% maximum 5% maximum 24VDC (20.0–28.0 VDC) a) 300mA maximum b) 500mA maximum (see note) 10% maximum MVSTBW 2.5/4-ST-5.08 BK
MVSTBW 2.5/6-ST-5.08 BK
1 (Primary) not replaceable
NOTE: 500mA @ 24VDC is achieved by lowering the 5VDC to 1.5 A from 2.0 A.
Environmental Specifications Ambient Operating Temperature Storage Temperature Ambient Humidity Atmosphere Vibration Resistance Shock Resistance Voltage Withstand Insulation Resistance Noise Immunity
32!F to 131!F (0!C to 55!C) -4!F to 158!F (-20!C to 70!C) 5% to 95% (Non-condensing) No corrosive gases. The level of environmental pollution = 2 (UL 840). MIL STD 810C. Method 514.2 MIL STD 810C. Method 514.2 1500VAC, 1 minute 500VDC, 10Mq NEMA ICS3-304 Impulse Noise 1es, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm)
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 65
Chapter 4: Specifications - Terminal Bases and Power Supplies
100-240V 50-60Hz 50VA
AC(L) 12.0-24.0V 20W
AC(N)
+ _
+24V _OUT LG
LG
G
G
T1K-01DC
T1K-01AC
1 PULL TO UNLOCK
1 PULL TO UNLOCK
T1K-01DC
T1K-01AC
Power Supply #1
T1K-10CBL Base Expansion Cable Power Supply #2
Note: Use the T1K–01AC 24VDC auxiliary supply or an external user supply for modules that require an external 24VDC.
Important Power Budget Note: For each power supply in a system make sure the current required by the CPU and I/O modules does not exceed the current supplied at both 5VDC and 24VDC (if using the 24VDC auxiliary supply).
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 4–5
Page 66
Chapter 4: Specifications - Terminal Bases and Power Supplies
Calculating the Power Budget
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 4–6
Managing the Power Resource When determining the types and quantity of I/O modules to be used in the Do-more T1H Series PLC system, it is important to remember there is a limited amount of power available from the power supply. A chart is provided to help you easily see the amount of power available with AC and DC power supplies. At the end of this section you will also find an example of power budgeting and a worksheet showing sample calculations. If the chosen I/O exceeds the maximum power available from the power supply the problem is corrected by simply adding another power supply . WARNING: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.
Power Supply Specifications
The following chart shows the amount of current supplied by the Terminator I/O power supply. Use this to calculate the power budget for your system. The Auxiliary 24V Power Source mentioned in the table can be used to power field devices or modules that require an external 24VDC. AC Power Supply
Auxiliary 5VDC Current 24VDC Power Supplied in mA Source Current (Internal) Supplied in mA
T1K-01AC
2000
300
T1K-01AC (see Note)
1500
500
DC Power Supply T1K-01DC
Auxiliary 5VDC Current 24VDC Power Supplied in mA Source Current (Internal) Supplied in mA 2000
-
Note A max. of 500mA @ 24VDC can be achieved by lowering the 5VDC to 1500mA. T1H-DM1E TERM
RUN I/O ERR
RUN
STOP
USB TX RX
Power Supply #1
USB PGM PORT
Power Supply #2
NOTE: Important about Power Supplies - One power supply is required in the leftmost component position (Power Supply #1), as shown above. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements. Each power supply powers the modules to its right, but is interrupted by the next power supply. It is not mandatory to have a power supply in the leftmost position on an expansion rack. The system shown above: Power Supply #1 powers the CPU module and the two I/O modules to its right. Power Supply #2 powers the remaining five I/O modules. This is only an example and the power budget requirements vary depending on the I/O modules used.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 67
Chapter 4: Specifications - Terminal Bases and Power Supplies
Module Power Requirements This chart shows the amount of maximum current required for each of the Do-more T1H PLC modules. Use this information to calculate the power budget for your system. If an external 24VDC power source is required, you can use the built-in 24VDC auxiliary supply as long as you do not exceed the power budget. If any device is connected to the Controller’s serial port that uses the 5VDC supply pin, be sure to include the device’s power consumption in your 5VDC power budget calculation. Terminator Module Power Consumption Module CPU Modules
5VDC (mA)
24VDC (mA)
250 275
0 0
35 70 -
0 0 -
35 70
0 0
T1H-DM1 T1H-DM1E
DC Input Modules T1K-08ND3 T1K-16ND3 -
AC Input Modules T1K-08NA-1 T1K-16NA-1
DC Output Modules T1K-08TD1 T1K-08TD2-1 T1H-08TDS T1K-16TD1 T1K-16TD2-1
100 100 200 200 200
24VDC (mA)
T1F-08AD-1 T1F-16AD-1 T1F-08AD-2 T1F-16AD-2 T1F-16RTD T1F-16TMST T1F-14THM
50 (see note 1) 50 (see note 1) 50 (see note 1) 50 (see note 1) 0 0 70 (see note 1)
75 75 75 75 150 150 60
Analog Output Modules T1F-08DA-1
75
150 (see note 1)
T1F-16DA-1 200 (see note 1) 0 T1F-08DA-2 0 400 (see note 1) T1F-16DA-2 0
75
150 (see note 1)
75
150 (see note 1)
75
150 (see note 1)
AC Output Modules T1K-08TA T1K-16TA T1K-08TAS
Module 5VDC (mA) Analog Input Modules
Combination Analog Modules 250 450 300
0 0 0
T1K-08TR
350
0
T1K-16TR
700
0
T1K-08TRS
400
0
Relay Output Modules
T1F-8AD4DA-1
75
60 (see note 1 and 2)
T1F-8AD4DA-2
75
70 (see note 1)
Specialty Module and other devices T1H- CTRIO
400
0
Note 1: Use T1K-01AC 24VDC auxiliary supply or external user supply. Note 2: 60mA plus 20mA per output loop. NOTE: Important Power Budget - For each power supply in a system, make sure the current required by the CPU module and I/O modules does not exceed the current supplied at both 5VDC and 24VDC.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
4–7
Page 68
Chapter 4: Specifications - Terminal Bases and Power Supplies
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 4–8
Power Budget Calculation Example The following example shows how to calculate the power budget for a Do-more T1H Series PLC system. PLC 5VDC (mA) Required
24VDC (mA) Required
2000 275 70 450
300 0 0 0
Maximum power required
795
0
Remaining power available
2000-795 = 1205 5VDC (mA) Required
300-0 = 300 24VDC (mA) Required
Maximum power required
735
Remaining power available
1500-735 = 765
500 500-500 = 0 (see note 1)
Power Supply #1
Part Number
Power Supplied T1K-01AC CPU T1H-DM1E Module T1K-16NA-1 Module T1K-16TA
Power Supply #2 Power Supplied T1K-01AC Module Module Module Module Module
Part Number T1K-08AD-2 T1K-08AD-2 T1K-16TD1 T1K-08TR T1K-08ND3
1500 75 75 200 350 35
500 50 50 400 0 0
Note 1: An external user power supply must be used if the 24VDC current requirement exceeds the T1K-01AC 24VDC auxiliary supply.
1. in the information for the CPU, I/O modules, and any other devices that will use system power, including devices that use the 24VDC output. Devices which fall into the “Other” category are devices such as an operator interface which also has power requirements but do attach as a module to the system. 2. the current columns starting with the CPU and put the total in the row labeled “Maximum power required”. 3. the row labeled “Maximum power required” from the “Power Supplied”. Place the difference in the row labeled “Remaining Power Available”. 4. “Maximum Power Required” is greater than “Power Supplied” in either of the two columns, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your configuration.
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M