The text of a manual · part 3 of 18

SC22-3/-3E Safety Controller Instruction Manual: 2 Overview

Pages 9 to 20 of 122, from SC22-3/-3E Safety Controller Instruction Manual

The original document is the PDF (6.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Banner SC22-3E

Page 9

SC22-3/-3E Safety Controller Instruction Manual

2 Overview NOTE: This section of this document provides a high-level discussion of the Banner SC22 Safety Controllers to acquaint the user with the Controller's capabilities and features. For in-depth information about installation, wiring, and use of the product, refer to later sections. The Banner SC22 Safety Controllers (the Safety Controller, or the Controller) are easy-to-use, configurable, 24V dc safety modules designed to monitor multiple safety and non-safety input devices and control up to three independent machine primary control elements (MPCEs). They provide safety stop and start functions for machines with hazardous motion. The Safety Controller can replace multiple safety relay modules in applications that include such safety input devices as E-stop buttons, gate interlocking switches, safety light curtains, and other safeguarding devices. It also can be used in place of safety PLCs and other safety logic devices when they are excessive for the application. Configurations are created using an Onboard LCD and push-button interface, or using a PC connected to the Safety Controller via a USB port.

2.1 Ethernet-Compatible Model The model SC22-3E provides the same features of the SC22-3, and in addition provides the ability to interface to Ethernet (for example to a PLC or HMI human interface touch panel), using Modbus/TCP or EtherNet/IP™ protocols. Modbus/TCP is an open standard protocol developed by the Modbus IDA. It is similar to Modbus RTU, except that it uses standard Internet communication protocols, just like Web communications or email. The master is referred to as the “client,” and the slave is the “server.” (The SC22-3E is a “server.”) Modbus/TCP follows the same structure as Modbus RTU: clients initiate all communication, servers can only respond. EtherNet/IP (EtherNet Industrial Protocol) is an open standard protocol developed by Allen-Bradley, but managed by the ODVA. EtherNet/IP is an adaptation of the DeviceNet serial fieldbus protocol, using Internet communications protocols. EtherNet/IP is DeviceNet over Ethernet. Compatible devices supported are: • EtherNet/IP connection (using the CIP protocol) to the Allen-Bradley ControlLogix family of PLCs. Both implicit and explicit messaging is supported • EtherNet/IP connection (using the PCCC protocol) to the Allen-Bradley SLC and PLC5 families of PLCs • Modbus/TCP connection to any compatible PLCs, HMIs, or devices www.bannerengineering.com - Tel: 763.544.3164

9

Page 10

SC22-3/-3E Safety Controller Instruction Manual

2.2 Applications

The Safety Controller can be used wherever safety modules are used. The Safety Controller is well suited to address many types of applications, including, but not limited to: • Two-hand control with mute function • Robot weld/processing cells with dualzone muting • Material-handling operations that require multiple inputs and bypass functions • Manually loaded rotary loading stations • Multiple two-hand-control station applications • Lean manufacturing stations • Dynamic monitoring of single- or dualsolenoid valves or press safety valves Figure 1. A palletizing application with multiple safeguarding controlled by the Safety Controller

2.3 Design and Testing The Safety Controller is designed for up to Category 4 PL e (ISO 13849-1) and Safety Integrity Level 3 (IEC 61508 and IEC 62061) safeguarding applications. It has been extensively tested to ensure that it meets the UL, IEC, and ISO product performance requirements. The Safety Controller incorporates: • Redundant microcontrollers • Redundant input signal detection circuitry • Redundant safety output control circuitry The safety circuit performance of a specific safety or safeguarding application is determined by the devices used and their interconnection to the Safety Controller. See section Input Device and Safety Category Reference on page 86 for specific information about integrating devices with the controller.

2.4 Components The Safety Controller Starter Kit includes: • 1 Safety Controller (model SC22-3 or SC22-3E) • 1 set of removable terminals (choose screw or clamp type) • 1 SC-XM1 external memory (XM) card • 1 USB A/B cable (Ethernet models) • 1 SC-XMP XM card programming tool (some models) • 1 CD containing PCI software, instruction manual, and configuration tutorials (p/n 134534) • 1 Quick Start Guide Ethernet connection cables (for model SC22-3E) are user-supplied.

10 www.bannerengineering.com - Tel: 763.544.3164

Page 11

SC22-3/-3E Safety Controller Instruction Manual

2.4.1 PC Requirements Operating system Microsoft Windows® XP, Windows 2000, Vista®, Windows 7 Hard drive space 100 MB (plus up to 280 MB for Microsoft .NET 2.0, if not already installed)

Third-party software Microsoft .NET 2.0, included and installed with PCI, if not already on computer Adobe® Reader® for Windows version 7.0 or newer USB port USB 1.1 or 2.0 type A port

2.4.2 USB Connections The Safety Controller is connected to the PC via the USB A/B cable. The cable is also used to connect the PC to the SC-XMP programming tool in order to download a configuration to the XM card.

Figure 2. USB connections: PC to SC-XMP programming tool connection

Figure 3. USB connections: PC to Safety Controller USB port connection

2.4.3 Ethernet Connections Ethernet connections are made using an ethernet cable connected from the SC22-3E Ethernet port to a network switch or the user’s control device. The SC22-3E supports either the standard or crossoverstyle cables. A shielded cable may be needed in highnoise environments. 1. USB Port 2. XM Card Port 3. Ethernet Port

Figure 4. Safety Controller Connections

2.4.4 SC-XMP Programming Tool The programming tool is used to transfer a configuration from a PC (running the PCI software) to an XM card, or from an XM card to the PC, without requiring a Safety Controller. It connects to the PC via the USB A/B cable.

www.bannerengineering.com - Tel: 763.544.3164

11

Page 12

SC22-3/-3E Safety Controller Instruction Manual

2.4.5 SC-XM1 External Memory (XM) Card The model SC-XM1 external memory (XM) card is a removable memory module that can store or be used to transfer a single configuration. The XM card has a write-on label on its reverse side where a configuration name or a machine identification can be noted. The XM card can be used to: • Keep a backup copy of the Safety Controller’s configuration (to minimize downtime in the case of a hardware failure that may require a Controller replacement) • Transfer configurations from one Safety Controller to another Safety Controller • Send (download) identical configurations into multiple Safety Controllers • Transfer configurations between the Safety Controller and a personal computer Store a configuration on the XM card in one of two ways: • Send a copy to the XM card using the PC Interface (PCI) and the SC-XMP programming tool • Send a copy from the Controller to the XM card, using the Onboard Interface (OBI) NOTE: 1. A configuration can be stored permanently in an XM card, if the “lock” function is performed. However, once the card is locked, it cannot be unlocked (it becomes "read-only"). 2. Configurations on an XM card do NOT contain any network settings. The PCI software must be used to change network settings.

2.5 Configuring the Safety Controller The Safety Controller can be configured using either of the two interfaces: the push buttons and the LCD screen on the controller itself (the Onboard Interface, or OBI), or the PCI software included on the enclosed CD (p/n 134534). The configuration process comprises three main steps: 1. Define the safeguarding application (risk assessment). • Determine the required devices • Determine the required level of safety 2. Build the configuration. • Select safety input device types and circuit connections • Map each input to one or more safety outputs, or to other input devices • Set optional safety output ON- or OFF-time delays • Select non-safety input device types and circuit connections, if needed • Assign status output signals, if needed • Create configuration name, file name, date, and author name 3. Confirm the configuration. • Controller verifies that the desired configuration is valid • User confirms that the configuration is as expected

2.5.1 Onboard Interface (OBI) The Safety Controller can be configured using its built-in push buttons and LCD screen, the Onboard Interface (OBI). The LCD display provides I/O device and system status information for any event that causes one or more of the Safety Outputs to turn OFF. The display is used in conjunction with the six push buttons to: • Create or modify password-protected configurations • Retrieve fault log information • Review device wiring detail and I/O logic relationships • Display I/O device fault details and likely remedial steps • Display configuration checksum NOTE: 1. Onboard Interface functions are covered in more detail in Section 5 and the OBI tutorial, located separately on the disk. 2. The OBI cannot be used to change network settings; the PCI must be used for that function.

12 www.bannerengineering.com - Tel: 763.544.3164

Page 13

SC22-3/-3E Safety Controller Instruction Manual

1. Moves cursor to the left or selects settings. 2. Moves cursor to the pre-established point in the program to reestablish a menu reference point. 3. Enters/stores the item highlighted in the display as the intended selection or toggles a setting. 4. Moves cursor to the right or selects settings. 5. Moves cursor down or moves through a list to display individual list items. Also used to select settings. 6. Moves cursor up or moves through a list to display individual list items. Also used to select settings. 7. Ethernet connector indicators (Yellow and Green; Ethernet models only) 8. Status indicators 9. LCD display

Figure 5. Onboard Interface, including push buttons, LCD display and status indicators (model SC22-3E shown)

Status Indicator

Condition

All Indicators OFF, Indicates Controller Status Initiation Mode

ON Green

Power ON

OFF

Power OFF

ON Red

Configuration mode

Flashing Red

Lockout mode

OFF

Run mode

Flashing Green

Transmitting or receiving data (a link is established with the PC)

OFF

Not transmitting or receiving data

ON Green

Safety Output ON

ON Red

Safety Output OFF

Flashing Red

Safety Output fault detected

Flashing Green

Safety Output waiting for reset

Yellow OFF

No link

Yellow ON

Link OK

Green OFF

No activity

Green ON or flashing

Activity detected

Power

Status (Controller Mode)

USB or Tx/Rx (depending on model)

Safety Output SO1, SO2, SO3

Ethernet Connector (model SC22-3E only)

Accessing Fault Codes Fault codes are displayed on the last line of the OBI fault diagnostics menu (see example on the right). Refer to Fault Diagnostics - OBI on page 84 for more information.

www.bannerengineering.com - Tel: 763.544.3164

13

Page 14

SC22-3/-3E Safety Controller Instruction Manual

2.5.2 Personal Computer Interface (PCI) The Safety Controller can also be configured using a Windows®-based computer and the Safety Controller PC Interface (PCI) program. This user-friendly interface makes use of icons and circuit symbols to simplify the selection of device properties during configuration. The configuration wiring and ladder logic diagrams develop automatically as the configuration progresses. Creating a configuration is simple. Once a configuration is created, it: • Can be stored to a computer file for archiving and future use • Can be emailed to a remote location as an attachment • Can be sent directly to another Safety Controller or to the plug-in external memory card The PCI can be used to create a configuration, save it and send it as described above, and also monitor the function of a Controller using the live display, as well as monitor the fault log for troubleshooting purposes. To access the Ethernet functionality of the model SC22-3E, click on the Network Settings icon and check the Enable Network Interface box. The Virtual Status Outputs will appear on the I/O Properties menu, as will additional tabs above the document section of the screen, as shown in the following figure.

1. 2. 3. 4. 5.

Toolbar Network settings I/O properties Document (in this case, Wiring Diagram) Virtual Status Outputs (These outputs become visible after the Enable Network Interface box is checked under the Network Settings tab.) 6. New tab selections also become visible.

Figure 6. PC User Interface (PCI) main screens

• •

PC Interface functions are covered in more detail in section PC Interface (PCI) Overview on page 50 and in the PCI tutorial PC Interface network functions are covered in more detail in sections Virtual Status Outputs on page 49 and Ethernet Reference on page 116

PCI Software Compatibility To identify the version of your PCI software (PC Interface), click the Help tab located on the top tool bar and then click Compatibility Information. The information contained in the pop-up window identifies what PCI software version is running and lists when a feature was added or changed. Newer PCI versions are backwards compatible with earlier SC22 firmware versions, although features must be supported by the SC22 firmware version or the feature will be unavailable. If an unsupported feature is attempted to be downloaded, an error message will be displayed. The SC22 firmware version can be identified via the Onboard Interface (OBI) "Model #" menu item; see section Display Controller Information, Onboard Interface (OBI) on page 68. This screen identifies the Safety Controller model, the firmware versions of microprocessors A and B, and the hardware version. Contact a Banner Applications Engineer with any questions.

14 www.bannerengineering.com - Tel: 763.544.3164

Page 15

SC22-3/-3E Safety Controller Instruction Manual

2.6 Input and Output Connections 2.6.1 Safety and Non-Safety Input Devices The Safety Controller has 22 input terminals that can be used to monitor either safety or non-safety devices; these devices may incorporate either solid-state or contact-based outputs. Each of these 22 input terminals can either monitor an input signal or provide 24V dc. The function of each input circuit depends on the type of the device connected; this function is established during the controller configuration. For general and specific information about input devices, their requirements, hookup options, appropriate warnings and cautions, additional installation information, and calculating Safety Distance (Minimum Distance), refer to the sections System Installation on page 25 and Input Device and Safety Category Reference on page 86, which contain hookup information and other useful information about integrating the following devices: • Safety Circuit Integrity • Protective (Safety) Stop • Optical Sensors • Safety Gate (Interlock Guard) • Two-Hand Control • Safety Mat (Edges) • Emergency Stop Push Buttons • Rope (Cable) Pull • Enabling Devices (Pendants) • Bypass • Muting Contact Banner Engineering for additional information about connecting other devices not described in this manual.

Safety Device Hookup Considerations The Safety Controller inputs can be configured to interface with many types of safety devices, including safeguarding devices, such as safety light curtains, complementary protective equipment, such as emergency stop push buttons, and other devices that impact the safe use of a machine, such as equipment protection. The way these devices interconnect impacts their ability to exclude or detect faults that could result in the loss of the safety function. There are many standards, regulations and specifications that require certain capabilities of a safety circuit. WARNING: User Responsibility The user is responsible for ensuring that all local, state, and national laws, rules, codes, and regulations relating to the use of this device in any particular application are satisfied. Make sure that all legal requirements have been met and that all installation, operation, and maintenance instructions contained in the device documentation are followed.

2.6.2 Safety Outputs The Safety Outputs are designed to control final switching devices (FSDs) and machine primary control elements (MPCEs) that are the last in the control chain to control the dangerous motion. These control elements include relays, contactors, solenoid valves, motor controls and other devices that incorporate force-guided (mechanically-linked) monitoring contacts, or control-reliable signals needed for external device monitoring. The Safety Controller has three independently controlled and redundant solid-state Safety Outputs. The Controller’s selfchecking algorithm ensures that the outputs turn ON and OFF at the appropriate times, in response to the assigned input signals and the system’s self-checking test signals. The Safety Outputs, SO1, SO2 and SO3, can be controlled by input devices with both automatic and manual reset operation.

www.bannerengineering.com - Tel: 763.544.3164

15

Page 16

SC22-3/-3E Safety Controller Instruction Manual

1. 2. 3. 4. 5.

Safety Controller OFF-Delay Solenoid locking switch Robot Contactors

Figure 7. Safety Outputs

See section Safety Outputs on page 38 for more information about configuring Safety Outputs.

Functional Stops according to IEC 60204-1 and ANSI NFPA79 The Controller is capable of performing two functional stop types: • •

Category 0: an uncontrolled stop with the immediate removal of power from the guarded machine Category 1: a controlled stop with a delay before power is removed from the guarded machine

Delayed stops can be used in applications where machines need power for a braking mechanism to stop the hazardous motion.

ON-Delays and OFF-Delays Each safety output can be configured to function with a time delay. There are two types of time delays: ON-delay and OFFdelay, where the outputs turn ON or OFF only after the time limit has elapsed. The ON and OFF time delay limit options are from 100 milliseconds to 5 minutes, in 100 millisecond increments. Safety output ON-delays are sometimes used when a machine operation must be delayed before a safe machine startup is permitted. An example application would be a robot weld cell. WARNING: Turning a Delayed Output On/Off If an input that is mapped to both an immediate safety output and a delayed safety output opens and then closes before the delay time of the delayed output has expired, the immediate safety output will turn Off and remain Off while the delay time is running. At the end of the delay time, the delayed output will also turn Off. Both outputs will then remain Off for about 500 ms, before they will turn back On. This will happen either automatically, if configured for auto reset, or after a valid manual reset signal, if configured for manual reset.

2.6.3 Status Outputs The Safety Controller has ten configurable status outputs used to send non-safety status signals to programmable logic controllers (PLCs) or to human machine interfaces (HMIs), or they may be used to power indicator lights. These outputs can be configured to report on the status of input devices, safety outputs, or the controller itself. See section Status Output Signal Conventions on page 46 for more information.

Signal Convention The status output signal convention can be configured to be 24V dc or 0V dc to indicate: • When an input is in the Run state • When a safety output is in the ON state (see Note 1 below) • When a safety output is in a logical ON state (ON or in an ON-delay; see Note 1 below) • When the system is in a Lockout condition • When an I/O fault is present (see Note 2 below) • When a system reset is needed • When a safety output needs a reset (see Note 3 below) • When a safety input is muted • Which safety input, of a defined group of safety inputs, turned OFF first • When a safety input is bypassed 16 www.bannerengineering.com - Tel: 763.544.3164

Page 17

SC22-3/-3E Safety Controller Instruction Manual • •

When a safety input has a Fault condition When a safety output's OFF-delay can be cancelled NOTE: 1. Only safety outputs that have inputs mapped to them can be mapped to a status output. 2. An I/O fault is a failure of one or more safety inputs, safety outputs, or status outputs. 3. Only safety outputs mapped to inputs configured with manual reset logic can have a status output configured to indicate a reset is needed. WARNING: Status Outputs The Status Outputs are not safety outputs and can fail in either the On or Off state. They must never be used to control any safety-critical applications. If a Status Output is used to control a safety-critical application, a failure to danger is possible and may lead to serious injury or death.

Monitored Mute Lamp Outputs Status Outputs O9 and O10 can be configured to create a monitored mute lamp function for a mute operation. When the mute lamp is ON, the Controller monitors for a short circuit in the load. When the lamp is OFF, it monitors for an open circuit in the load. If an open circuit occurs before the start of a mute cycle, the next mute cycle will be prevented. If an open circuit occurs during a mute cycle, that mute cycle will finish, but the next mute cycle will be prevented. If a short occurs before or during a mute, that mute cycle will start and finish, but the next mute cycle will be prevented. If not used to monitor a mute lamp, these outputs may be used in the same ways as outputs O1–O8. Important: Only terminals O9 and O10 have the extra monitoring circuitry needed for a monitored mute lamp. If monitoring of the mute lamp is not required (depending on applicable standards), any of the Status Outputs (O1–O10) may be used to indicate a mute condition. Because of this feature, these Status Outputs will always appear ON with no load (see Specifications on page 23).

2.6.4 Virtual Status Outputs Using the PCI, the model SC22-3E (only) can configure up to 32 Virtual Status Outputs. These outputs can communicate the same information as the status outputs, but over the network. WARNING: Virtual Status Outputs Virtual Status Outputs are not safety outputs and can fail in either the On or the Off state. They must never be used to control any safety-critical applications. If a Virtual Status Output is used to control a safety-critical application, a failure to danger is possible and may lead to serious injury or death.

2.6.5 I/O Mapping: the I/O Control Relationship The term “map” implies a control logic relationship between an input and an output, or between an input and another input, where the state of the first input determines the state of the output or of the second input. Inputs Mapped to Outputs. The following devices can be mapped directly to the Safety Outputs: • • • • • • •

Emergency stop buttons Safety gate switches Optical sensors Two-hand control devices Safety mats Protective stop switches Rope pulls

• • • • • •

Enabling devices External device monitoring ON/OFF devices Manual reset devices Solenoid or press safety valves Cancel OFF-delay devices

Figure 8. Input and Output mapping www.bannerengineering.com - Tel: 763.544.3164

17

Page 18

SC22-3/-3E Safety Controller Instruction Manual Inputs Mapped to Inputs. Muting sensors and bypass switches work in conjunction with certain safety input devices to temporarily suspend the Stop signal of a safety input device. These sensors and switches are mapped directly to the safety inputs; they are then indirectly mapped to the safety output(s) controlled by the muted safety inputs (see section Mute Function on page 34).

2.7 System Settings The controller’s system settings define parameters for both the configuration file and the controller. These settings include: • Configuration name • Author’s name • Power-up mode • Mute on power-up enable • Monitored system reset Configuration Name The configuration name identifies the configuration that is used in a Safety Controller application. The configuration name is displayed on the controller and helps to ensure the correct controller configuration is used. Author’s Name The author’s name is helpful if questions about configuration settings arise. Power-Up Mode (Operational Characteristics When Power Is Applied) The controller provides three power-up modes to determine how the controller will behave after the power is supplied. These modes are: Normal, Automatic, and Manual. • Normal Power-Up Mode (default). In a normal power-up mode, after power is applied: ◦ Only those safety outputs that have automatic reset inputs will turn ON ◦ Safety outputs that have one or more manual reset inputs will turn ON only after a manual (latch) reset operation is performed ◦ Exception: Two-hand control inputs, bypass inputs, and enabling device inputs must be seen to be in the Stop state at power-up, regardless of the power-up mode selection. If these are seen to be in the Run state at power-up, the outputs will remain OFF. • Automatic Power-Up Mode. In an automatic power-up mode, after power is applied: ◦ All safety outputs will turn ON immediately if the inputs that are mapped to these outputs are all in the Run state. ◦ Exception: Two-hand control inputs, bypass inputs, and enabling device inputs must be seen to be in the Stop state at power-up, regardless of the power-up mode selection. If these are seen to be in the Run state at power-up, the outputs will remain OFF.

WARNING: Automatic Power-Up When the Controller is configured for automatic system reset power-up mode, the Controller acts as if all input devices are configured for auto (trip) reset. Each safety output will immediately turn on at power-up if the assigned input devices are all in the Run state, even if one or more of the input devices is configured for manual (latch) reset. If the application requires that a manual (latch) reset operation be performed before the Safety Output turns On, then either manual or normal powerup mode configuration must be used. Failure to do so could cause a machine to operate in an unexpected way at power-up or after temporary power interruptions. •

18

Manual Power-up Mode. In a Manual Power-up Mode, after power is applied: ◦ Safety outputs will turn ON only after all inputs mapped to this output are in the Run state and a System Reset has been performed. (A manual latch reset is not required.) ◦ Exception: Two-hand control inputs, bypass inputs, and enabling device inputs must be seen to be in the Stop state at power-up, regardless of the power-up mode selection. If these are seen to be in the Run state at power up, the outputs will remain OFF.

www.bannerengineering.com - Tel: 763.544.3164

Page 19

SC22-3/-3E Safety Controller Instruction Manual

WARNING: Controller Operation on Power-Up It is the responsibility of the user of the Controller to assess what safeguarding devices and methods are appropriate for any given machine or application. The Qualified Person1 who configures, installs, and/or maintains it must be aware of the power-up behavior of the Controller and instruct the machine operator on the operation of the Controller and its associated devices. Mute On Power-Up Enable If configured, the Mute on Power-Up function will initiate a mute cycle after power is applied to the Safety Controller if the muted safety inputs are active (Run state or closed), and either M1-M2 or M3-M4 (but not all four) are signaling a muted condition (for example, active or closed). • For more information on the Mute On Power-Up function, see section Mute Function on page 34. Monitored System Reset Monitored System Reset is enabled by default and requires an OFF-ON-OFF signal at the reset input, where the ONduration must be between 0.3 and 2 seconds (trailing edge reset), in order to reset the system. If unchecked (Monitored System Reset disabled), the reset input requires only a signal from OFF to ON (leading edge reset), in order to reset the system.

2.8 Internal Logic The Controller’s internal logic is designed so that a Safety Output can turn ON only if all the controlling input device signals are in the Run state and the Controller’s self-check signals are in the No-Fault state. Safety Input 1

Safety Input 2

Safety Controller

Safety Output 1

Stop

Stop

Run (No Fault)

OFF

Stop

Run

Run (No Fault)

OFF

Run

Stop

Run (No Fault)

OFF

Run

Run

Run (No Fault)

ON

The table above illustrates the logic for two safety input devices mapped to control Safety Output 1. If any of the safety input devices are in the Stop state, then Safety Output 1 is OFF. When both safety inputs are in the Run state, then Safety Output 1 will turn ON.

2.8.1 Additional Logic Functions Other logic functions are slight variations of the general AND logic rule set. • Two-Hand Control: The machine initiation signal incorporating a 0.5 second actuator simultaneity limit and antitie-down logic, designed to prevent single-actuator machine cycle operation • Safety Device Muting: The automatic suspension of one or more safety input Stop signals during a portion of a machine operation when no hazard is present or when access to the hazard is otherwise safeguarded • Safety Device Bypass: The manually activated, temporary suspension of one or more safety input Stop signals when the hazard is otherwise safeguarded • Enabling Device Control: The actively controlled manual suspension of a Stop signal during a portion of a machine operation when a hazard could occur • Cancel OFF-Delay: The option to cancel a configured OFF-delay time by either keeping the Safety Output ON, or turning it OFF immediately The rules that apply to these special cases are explained in section Input Device and Safety Category Reference on page 86.

2.9 Password Overview To provide security, in some cases, the Safety Controller requires the use of a password. For information about changing a controller’s password, refer to System Options on page 63. If the password becomes lost, contact the Banner Engineering for assistance. 1 A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.

www.bannerengineering.com - Tel: 763.544.3164

19

Page 20

SC22-3/-3E Safety Controller Instruction Manual Creating a Configuration • Via computer using the Safety Controller PC Interface (PCI) program (no password needed) • Via the Controller Onboard Interface (OBI) (password needed) Confirming a Configuration • Via the PCI, using the PC connected to a powered Controller (password needed) • Via the OBI, on a powered Controller (password needed) Sending a Confirmed Configuration to the Controller • Via a direct connection between the PC and the Controller, using the SC-USB1 cable and the PC Interface program (password needed) • Via the PC, the XM card programming tool, and the XM card (password needed)

2.10 Confirming a Configuration Although a controller will accept an unconfirmed configuration, it will only activate it (adopt the configuration and function according to its parameters) after the configuration is confirmed, using the OBI or PC Interface. Important: If any modification is made to a confirmed configuration, or if a configuration is edited during the confirmation process, the PCI and the controller will recognize this modified configuration as being new and will require it to be confirmed before it can be activated and used. Once confirmed, a configuration can be stored and reused without reconfirmation. The configuration code will be validated automatically each time it is downloaded to a controller and whenever the controller powers up. Configurations, confirmed or not, can be sent via email. Sending (downloading) a new confirmed configuration to a controller requires entry of the controller password.

20 www.bannerengineering.com - Tel: 763.544.3164