Page 21
SC22-3/-3E Safety Controller Instruction Manual
3 Components and Specifications The Safety Controller can be ordered alone, without terminals, as a replacement part. To order the Safety Controller ready for use, order it as part of a kit (see SC22-3 Safety Controller Starter Kit Models on page 21). Kits include the Safety Controller, a set of plug-on terminal blocks (screw or cage-clamp type, depending on model), a USB A/B cable (for direct connection between a PC and the Safety Controller, included with some kits), external nonvolatile memory card (XM card, with write-on label on reverse side), XM card programming tool (included with some models), a user CD (includes software interface, online manual, ethernet references and configuration tutorials), and quick start guide.
3.1 SC22-3 Safety Controller Starter Kit Models Kit Model
Terminal Type
SC22-3-S
Screw
SC22-3-C
Clamp
SC22-3-SU1
Screw
SC22-3-CU1
Clamp
SC22-3E-S
Screw
SC22-3E-C
Clamp
SC22-3ESU1
Screw
SC22-3ECU1
Clamp
Safety Outputs
Status Outputs
Safety Output Rating
10 Status
0.75 amps each output
USB A/B Cable
XM Card
─
XM Card Programmi ng Tool
Communica tion Protocol
─ ─
1.8 m
Yes
6 PNP Terminals (3 pairs)
10 Status plus 32 Virtual Status
Yes
─
─ EtherNet/IP &
0.5 amps each output 1.8 m
Yes
Modbus/TCP
3.2 Replacement Parts/Accessories Model
Description
SC22-3
Replacement Controller (no terminals)
SC22-3E
Replacement Controller (no terminals), Ethernet compatible
SC-XM1
External memory card (XM card)
SC-XM1-5
Bulk pack of 5 XM cards
SC-XMP
USB programming tool for XM card
SC-TS1
Screw terminal replacement set
SC-TC1
Cage clamp terminal replacement set
SC-USB1
USB A/B cable, 1.8 m
134534
CD including PCI program and instruction manual
3.3 Ethernet Cordsets Cat5e Shielded Cordsets
Cat5e Crossover Shielded Cordsets
Length
STP07
STPX07
2.1 m (7 ft)
www.bannerengineering.com - Tel: 763.544.3164
21
Page 22
SC22-3/-3E Safety Controller Instruction Manual
Cat5e Shielded Cordsets
Cat5e Crossover Shielded Cordsets
Length
STP25
STPX25
7.62 m (25 ft)
STP50
STPX50
15.2 m (50 ft)
STP75
STPX75
22.9 m (75 ft)
3.4 Interface Modules NOTE: External device monitoring (EDM) is required to be wired separately to the N.C. contacts to comply with ISO 13849-1 categories and ANSI/OSHA control reliability; see External Device Monitoring (EDM) on page 37. SC-IM9 series interface modules are used only with the Safety Controller; dry contacts are used with higher ac/dc voltage and current. The modules have 10A output, DIN-mount housing, removable (plug-in) terminal blocks for OSSD outputs (screw terminal block supplied). They measure 72 mm (2.8 in) high, 170 mm (6.7 in) deep, and 45 mm (1.8 in), 90 mm (3.5 in), or 140 mm (5.5 in) wide, depending on model. See datasheet p/n 131845 for more information. Model
Description
SC-IM9A
For use with 1 Safety Controller Safety Output
SC-IM9B
For use with 2 Safety Controller Safety Outputs
SC-IM9C
For use with 3 Safety Controller Safety Outputs
Supply Voltage
Inputs (Safety Controller Outputs)
Safety Outputs
2 (SO1)
3 N.O.
4 (SO1 and SO2)
Total of 6 (3 N.O. per output)
6 (SO1, SO2, and SO3)
Total of 9 (3 N.O. per output)
24V dc (Controllersupplied)
Output Rating
EDM Contacts
10 amps
1 N.C. pair per output
IM-T-9 series interface modules have 6A output, 22.5 mm DIN-mount housing, removable (plug-in) terminal blocks, low current rating of 1V ac/dc at 5 mA, high current rating of 250 V ac/dc at 6A. See datasheet p/n 62822 for more information. Model
Supply Voltage
IM-T-9A
24V dc
IM-T-11A
Inputs
Safety Outputs
Output Rating
EDM Contacts
6 amps
2 N.C.
3 N.O.
2 (dual-channel hookup)
2 N.O.
Aux. Outputs, 1 N.C.
3.4.1 Mechanically Linked Contactors Mechanically Linked Contactors provide an additional 10 or 18 amp carrying capability to any safety system. If used, two contactors per Safety Output pair are required. The N.C. contacts are to be used in an external device monitoring (EDM) circuit. NOTE: EDM is required to be wired separately to the N.C. contacts to comply with ISO 13849-1 categories and ANSI/OSHA control reliability; see External Device Monitoring (EDM) on page 37 . Model
Supply Voltage
Inputs
Outputs
24 V dc
2 (dual-channel hookup)
3 N.O. and 1 N.C.
11-BG00-31-D024
10 amps
BF1801L-024
22
Output Rating www.bannerengineering.com - Tel: 763.544.3164
18 amps
Page 23
SC22-3/-3E Safety Controller Instruction Manual
3.5 Specifications Power 24V dc, ± 20% Model SC22-3: 0.4 A (Controller only), 5.9 A (all outputs ON at full rated load) Model SC22-3E: 0.4 A (Controller only), 4.9 A (all outputs ON at full rated load) The Controller should be connected only to a SELV (safety extra-low voltage, for circuits without earth ground) or a PELV (protected extra-low voltage, for circuits with earth ground) power supply. Safety and Non-Safety Inputs (22 terminals) Input ON threshold: > 15V dc (guaranteed on), 30V dc max. Input OFF threshold: < 5V dc (guaranteed off with any 1 fault), –3V dc min. Input ON current: 8 mA typical at 24Vdc, > 2 mA (guaranteed with 1 fault) 50 mA peak contact cleaning current at 24V dc Sourcing current: 30 mA minimum continuous (3V dc max. drop) Input lead resistance: 300 Ω max. (150 Ω per lead) Input requirements for a 4-wire safety mat: • Max. capacity between plates: 0.5 µF • Max. capacity between bottom plate and ground: 0.5 µF • Max. resistance between the 2 input terminals of one plate: 20 Ω Safety Outputs (6 terminals, 3 redundant outputs) Rated output current: Model SC22-3: 0.75 A max. at 24V dc (1.0V dc max. drop) Model SC22-3E: 0.5 A max. at 24V dc (1.0V dc max. drop) Output OFF threshold: 0.6V dc typical (1.2V dc max. guaranteed with 1 fault) Output leakage current: 50 µA max. with open 0V Load: 0.1 µF max., 1 H max., 10 Ω max. per lead Status Outputs (10 terminals) Rated output current: 0.5A at 24V dc (individual), 1.0 A at 24V dc (total of all outputs) O1 to O8 (General Purpose) - Output OFF voltage: < 0.5V dc (no load), 22 KΩ pull down to 0V O9 and O10 (General Purpose or Monitored Mute Lamp) - Output OFF voltage: Internal 94 KΩ pull up to 24V dc supply Output ON/OFF threshold: 15V dc +/−4V dc at 24V dc supply Response and Recovery Times Response Time (ON to OFF): 10 ms max. (with standard 6 ms debounce; this can increase if debounce time increases. Refer to the configuration summary for actual response time.) Recovery Time (OFF to ON): 400 ms max. (with manual reset option) Recovery Time (OFF to ON): 400 ms max. plus input debounce time (auto reset) Onboard LCD Information Display - Password Requirements Password is not required: Run mode (I/O status) Fault (I/O fault detection and remedial steps) Review configuration parameters (I/O properties and terminals) Password is required: Configuration mode (create/modify/confirm/download configurations)
Environmental Rating NEMA 1 (IEC IP20), for use inside NEMA 3 (IEC IP54) or better enclosure Operating Conditions Temperature range:0 °C to +55 °C (+32 °F to +131 °F) Mechanical Stress Shock: 15g for 11 milliseconds, half sine, 18 shocks total (per IEC 61131-2) Bump: 10g for 16 milliseconds, 6000 cycles total (per IEC 61496-1) Vibration: 3.5 mm occasional / 1.75 mm continuous at 5Hz to 9Hz, 1.0g occasional and 0.5g continuous at 9Hz to 150Hz: (per IEC 61131-2) and 0.35 mm single amplitude / 0.70 mm peak-to-peak at 10 to 55Hz (per IEC 61496-1), all at 10 sweep cycles per axis EMC Meets or exceeds all EMC requirements in IEC 61131-2, IEC 61496-1 (Type 4), and IEC 61326-3-1. Removable Terminals Screw terminals Wire sizes: 16, 18, 20, 22 or 24 AWG (0.20 – 1.31 mm²) Wire strip length: 5.00 mm (0.197 in) Tightening torque: 0.23 Nm (2 in. lbs.) nominal; 0.34 Nm (3.0 in. lbs.) maximum Clamp terminals Important: Clamp terminals are designed for 1 wire only. If more than 1 wire is connected to a terminal, a wire could loosen or become completely disconnected from the terminal, causing a short. Wire size: 16, 18, 20, 22, or 24 AWG (0.20 – 1.31 mm²) Wire strip length: 9.00 mm (0.35 in) Network Interface (Model SC22-3E only) Ethernet 10/100 Base-T/TX, RJ45 modular connector Selectable auto negotiate or manual rate and duplex Auto MDI/MDIX (auto cross) Protocols: EtherNet/IP (with PCCC), Modbus/TCP Data: 32 configurable virtual Status Outputs; fault diagnostic codes and messages; access to fault log Product Performance Standards IEC 62061 Safety of Machinery – Functional Safety of Safety-Related Electrical, Electronic and Programmable Electronic Control Systems: SIL CL 3 IEC 61508 Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems: SIL 3 ISO 13849-1 (1999): Category 4 ISO 13849-1 (2006): Category 4 Performance Level (PL) e, complies with Machinery Directive 2006/42/EC IEC 61131-2 Programmable Controllers, Part 2: Equipment Requirements and Tests UL 508 Industrial Control Equipment UL 1998 Software in Programmable Components ANSI NFPA 79 Electrical Standards for Industrial Machinery IEC 60204-1 Electrical Equipment of Machines: General Requirements ISO 13851 (EN574) Safety of Machinery – Two-Hand Control Devices – Functional Aspects and Design Principles ISO 13850 (EN418) Emergency Stop Devices Also see front section of this manual for a list of other applicable U.S. and international standards. Agency Approvals
NOTE: For O9 and O10 (when configured as a monitored mute lamp output), if a short circuit or other fault condition causes the output to drop below this threshold while the output is ON, a lockout will occur. If an open circuit or other fault condition causes the output to rise above this threshold while the output is OFF, a lockout will occur.
www.bannerengineering.com - Tel: 763.544.3164
23
Page 24
SC22-3/-3E Safety Controller Instruction Manual
3.5.1 Dimensions
Allow minimum 65 mm (2.6") clearance for USB cable or Ethernet cable and 43 mm (1.7") for XM Card insertion
64 mm (2.5")
35 mm (1.4") 112 mm (4.4") 130 mm (5.1")
131 mm (5.2")
Figure 9. SC22-3 and SC22-3E dimensions
24 www.bannerengineering.com - Tel: 763.544.3164