Page 25
SC22-3/-3E Safety Controller Instruction Manual
4 System Installation 4.1 Appropriate Application The correct application of the Safety Controller depends on the type of machine and the safeguards that are to be interfaced with the Controller. If there is any concern about whether or not your machinery is compatible with this Controller, contact Banner Engineering. WARNING: Not a Stand-Alone Safeguarding Device This Banner device is considered complementary equipment that is used to augment safeguarding that limits or eliminates an individual's exposure to a hazard without action by the individual or others. Failure to properly safeguard hazards according to a risk assessment, local regulations, and relevant standards may lead to serious injury or death. WARNING: User Is Responsible for Safe Application of this device The application examples described in this document depict generalized guarding situations. Every guarding application has a unique set of requirements. Make sure that all safety requirements are met and that all installation instructions are followed. Direct any questions regarding safeguarding to a Banner applications engineer at the number or addresses listed this document. WARNING: Shock Hazard and Hazardous Energy Always disconnect power from the safety system (for example, device, module, interfacing, etc.) and the machine being controlled before making any connections or replacing any component. Electrical installation and wiring must be made by Qualified Personnel2 and must comply with the relevant electrical standards and wiring codes, such as the NEC (National Electrical Code), ANSI NFPA79, or IEC 60204-1, and all applicable local standards and codes. Lockout/tagout procedures may be required. Refer to OSHA 29CFR1910.147, ANSI Z244-1, ISO 14118, or the appropriate standard for controlling hazardous energy. WARNING: Read this Section Carefully Before Installing the System The Banner Safety Controller is a control device that is intended to be used in conjunction with a machine safeguarding device. Its ability to perform this function depends upon the appropriateness of the application and upon the Safety Controller's proper mechanical and electrical installation and interfacing to the machine to be guarded. If all mounting, installation, interfacing, and checkout procedures are not followed properly, the Banner Safety Controller cannot provide the protection for which it was designed. The user is responsible for satisfying all local, state, and national laws, rules, codes, or regulations relating to the installation and use of this control system in any particular application. Make sure that all safety requirements have been met and that all technical installation and maintenance instructions contained in this document are followed.
4.2 Installing the Safety Controller The Safety Controller mounts to a standard 35 mm DIN-rail track. It must be installed inside an enclosure rated NEMA 3 (IEC IP54) or better. It can be mounted in any orientation. The user must comply with all instructions contained within product manuals and relevant regulations. Do not exceed the operating specifications for reliable operation. The enclosure must provide adequate heat dissipation so that the air closely surrounding the Controller does not exceed its maximum operating temperature (see Operating Conditions on page 23 ). Methods to reduce heat build-up include venting, forced air flow (for example, exhaust fans), adequate enclosure exterior surface area, and spacing between the Safety Controller and other sources of heat.
2 A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.
www.bannerengineering.com - Tel: 763.544.3164
25
Page 26
SC22-3/-3E Safety Controller Instruction Manual
Important: Mount the Safety Controller in a location that is free from large shocks and high-amplitude vibration. CAUTION: Electrostatic Discharge (ESD) can cause damage to electronic equipment. To prevent this, follow the proper ESD handling practices such as wearing an approved wrist strap or other grounding products, or touching a grounded object before handling the modules. See ANSI/ESD S20.20 for further information about managing ESD.
4.3 Safety Input Devices Safety input devices allow for the cessation of motion, or an otherwise hazardous situation, by controlling the safety outputs of the Safety Controller. A Safety Output in the Off state results in a stop of motion and removal of power from the machine actuators (assuming this does not create additional hazards). In general, when all of the input devices that have been configured to control a particular Safety Output are in the Run sate, the Safety Output turns or remains On. A few special safety input device functions can, under predefined circumstances, temporarily suspend the safety input stop signal to keep the safety output On, for example, muting and bypassing. The Safety Controller input configurations, depending on the type, have means to detect failures and faults that would otherwise result in a loss of the control of the safety function. Once such a failure or fault is detected, the Safety Controller locks out until the problem it is fixed. Other input configurations do not have this detection capability. To eliminate or minimize the possibility of failures and faults that could result in a loss of the safety function(s), install the Safety Controller together with its associated safety and safeguarding devices. Methods to eliminate or minimize the possibility of these failures include, but are not limited to: • Physically separating the interconnecting control wires from each other and from secondary sources of power • Routing interconnecting control wires in separate conduit, runs, or channels • Locating all elements (modules, switches, and devices under control) within one control panel, adjacent to each other, and directly connected with short wires • Properly installing multi-conductor cabling and multiple wires through strain-relief fittings. Over-tightening of a strain-relief can cause short circuits at that point • Using positive-opening or direct-opening components, as described by IEC 60947-5-1, that are installed and mounted in a positive mode • Periodically checking the functional integrity/safety function • Training the operators, maintenance personnel, and others involved with operating the machine and the safeguarding to recognize and immediately correct all failures
NOTE: Follow the device manufacturer's installation, operation, and maintenance instructions and all relevant regulations. If there are any questions about the device(s) that are connected to the Safety Controller, contact Banner Engineering for assistance.
26 www.bannerengineering.com - Tel: 763.544.3164
Page 27
SC22-3/-3E Safety Controller Instruction Manual
WARNING: Sharing of Safety Inputs
Inputs Inputs S1.............S11 S12...........S22
2 x 24V dc (A1) 2 x 0V dc (A2)
O1.........O10 Status Outputs
System Reset (SR)
Multiple Safety Controllers must not share safety input devices; this includes solid-state outputs from light curtains, Safety Controllers, or other safety devices. A safety output from one Controller can be connected to a Safety Input of a second Controller. However, the second Controller should be the only device to which the output from the first Controller is connected. If a third device is also connected to the same safety output (now used as the safety input of the second Controller), during a power transition of the second Controller, the input may be a source of current, momentarily causing a false On (Run) signal at the input of the third device. Failure to connect multiple Controllers correctly could create an unsafe condition that may lead to serious bodily injury or death.
SO1 SO2 SO3
Safety Outputs 0V dc (A2)
Figure 10. Input and output terminal locations
WARNING: Failures and Faults The Safety Controller Safety control can be interfaced with input devices at differing levels of integrity. The user must conduct a Risk Assessment to determine the appropriate method of integration. The user must also eliminate or minimize the possibility of failures and faults that may result in the loss of the safety function(s).
4.3.1 Signals: Run and Stop States Dual-channel safety input devices have two separate signal lines. Dual-channel signals for some devices are both positive (+24 V dc) when the device is in the Run state. Other devices may have a complementary circuit structure where one channel is at 24 V dc and the other is at 0 V dc when the device is in the Run state. This manual adopts the Run state/Stop state convention instead of referring to a safety input device as being On (24 V dc) or Off (0 V dc).
4.3.2 Safety Input Device Properties The Controller can be configured to accommodate many types of safety input devices. However, the number of the device properties must be established (using either the OBI or PCI interface) so that the Controller can properly monitor their signals. The configurable properties include: • • • • • • • • • • •
Device name - generated automatically by the Controller and can be changed by the user Circuit type - the circuit and signal convention options that can be selected to define the input device Reset logic - Automatic (Trip mode) or Manual (Latch mode) Terminal number - the assignment of input terminals for a device I/O mapping - the logic control relationship between inputs and outputs or between inputs Signal change-of-state - Simultaneous or Concurrent type and signal convention (high or low) Signal debounce time - the signal state transition time Start-up test - an optional precautionary safety input device test required after each power-up Function time limit - the adjustable time limit within which a function is allowed to operate Mutable - determines whether or not the device can be muted Bypassable - determines whether or not the device can be bypassed
Circuit Types: Contact and Solid State Circuits The table below depicts many of the input devices and circuit types the Controller can monitor. It highlights which of these properties can be configured, and for which devices. More description of some of these topics is included in the following paragraphs. www.bannerengineering.com - Tel: 763.544.3164
27
Page 28
SC22-3/-3E Safety Controller Instruction Manual Not all circuit types meet the Category 4 classification per ISO 13849-1; refer to section Safety Circuit Integrity and ISO 13849-1 Safety Circuit Principles on page 86 for a discussion of safety circuit integrity levels.
E-Stop Safety Optical Two-Hand Rope Gate Sensor Control Pull Circuit Types Reset Logic
7
13
10
Auto/ Auto/ Auto/ Manual Manual Manual
7
10
Auto
Auto/ Manual
Protect. Safety Enabling Mute Bypass Stop Mat Device Sensors Switch 10
1
Auto/ Auto/ Manual Manual
EDM
AVM
10
7
10
2
2
Auto
Auto
Auto, - I/O Mapping
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/I
I/I
I/O
I/O
Signal COS*
S/C
S/C
S/C
S
S/C
S/C, S/C
S
S/C
S, Debounce Times
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Start Up Test, Yes
Yes, - - - - - - - - Function Time Limit, - - - - - Yes
Yes
Yes, Yes
Muteable, Yes
Yes
Yes, Yes
Yes, - - - - Bypassable, Yes
Yes
Yes, Yes
Yes, - - - - * Refer to change-of-state table. S = Simultaneous C = Concurrent
Figure 11. Device Monitoring
Reset Logic: Manual or Automatic Reset Safety input devices can be configured to require a manual reset before the safety output(s) they control are permitted to turn back On. This is sometimes referred to as “latch” mode because the safety output “latches” to the Off state until a reset is performed. If a safety input device is configured for automatic reset or “trip” mode, the safety output(s) it controls will turn back On when the input device changes to the Run state (provided that all other controlling inputs are also in the Run state). Reset rules and types are discussed in the section Input Device Resets on page 31.
Connecting the Input Devices The Safety Controller needs to know what device signal lines are connected to which wiring terminals so that it can apply the proper signal monitoring methods, Run and Stop conventions, and timing and fault rules. The terminals are assigned automatically during the configuration process and can be changed manually using either the Onboard Interface or the PC Interface.
Signal Change-of-State Types Two change-of-state (COS) types can be used when monitoring dual-channel safety input device signals: Simultaneous or Concurrent.
28 www.bannerengineering.com - Tel: 763.544.3164
Page 29
SC22-3/-3E Safety Controller Instruction Manual
Input Signal COS Timing Rules
Input Circuit
Stop State - SO turns Off when3:
Run State - SO turns On when4:
Dual-Channel A and B Complementary 2 Terminals
3 Terminals
2 Terminals, PNP ON
24V
OFF
At least 1 channel (A or B) input is in the Stop state.
Dual-Channel A and B 2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
2-Ch, 2 Terminal PNP ON
24V
ON
Simultaneous: A and B are both in the Stop state and then both in the Run state within 3 seconds before outputs turn On. Concurrent: A and B are concurrently in the Stop state, then both in the Run state with no simultaneity to turn outputs On.
2X Complementary A and B 4 Terminals
5 Terminals
24V
At least 1 channel (A or B) within a pair of contacts is in the Stop state.
PNP ON
OFF
ON
Simultaneous: A and B are concurrently in the Stop state, then contacts within a channel in the Run state within 400 ms (150 ms for two-hand control), both channels are in the Run state within 3 seconds (0.5 seconds for two-hand control). Concurrent: A and B are concurrently in the Stop state, then contacts within a channel in the Run state within 3 seconds. Both channels are in the Run state with no simultaneity.
OFF
4-Wire Safety Mat
One of the following conditions is met: Input channels are shorted • together (normal operation) • At least 1 of the wires is disconnected • One of the normally low channels is detected high • One of the normally high channels is detected low
2-Ch, 2 Terminals
Each channel detects its own pulses.
Signal Debounce Times Closed-to-Open Debounce Time (from 6 ms to 100 ms in 1 ms intervals, except 6 ms to 1500 ms for mute sensors). The closed-to-open debounce time is the time limit required for the input signal to transition from the high (24 V dc) state to the steady low (0 V dc) state. This time limit may need to be increased in cases where high-magnitude device vibration, impact shock, or switch noise conditions result in a need for longer signal transition times. If the debounce time is set too short under these harsh conditions, the system may detect a signal disparity fault and lock out. The default setting is 6 ms. CAUTION: Debounce and Response Any changes in the closed-to-open debounce time will affect the Safety Output response (turn Off) time. This value is computed and displayed for each Safety Output when a configuration is created. The values are also listed in the OBI and the PCI Configuration Summary documents. (Default setting is 6 ms.) Open-to-Closed Debounce Time (from 10 ms to 500 ms in 1 ms intervals, except 10 ms to 1500 ms for mute sensors). The open-to-closed debounce time is the time limit required for the input signal to transition from the low (0 V dc) state to the steady high (24 V dc) state. This time limit may need to be increased in cases where high magnitude device vibration, impact shock, or switch noise conditions result in a need for longer signal transition times. If the debounce time is set too short under these harsh conditions, the system may detect a signal disparity fault and lock out. The default setting is 50 ms. 3 Safety Outputs turn Off when one of the controlling inputs is in the Stop state. 4 Safety Outputs turn On only when all of the controlling inputs are in the Run state and after a manual reset is performed (if any safety inputs are configured for Manual reset and were in their Stop state).
www.bannerengineering.com - Tel: 763.544.3164
29
Page 30
SC22-3/-3E Safety Controller Instruction Manual When a safety mat is used, the response time calculation for the safety mat depends on the Stop (6 to 100 ms) debounce time. CAUTION: Response Times • The response time for a complementary device is based on the closed contact(s) opening, not on the open contact(s) closing. Both will lead to a stop signal, but only one determines the response time. • The configurable debounce of an On/Off input and an enabling device input are not part of the calculated and confirmed response times. • Any changes in the open-to-closed debounce time will affect the Safety Output reaction (turn On) time
4.4 Non-Safety Input Devices The non-safety input devices include manual reset devices, On/Off switches, and mute enable devices. Configurable Properties
Manual Reset
ON/OFF
Mute Enable
Cancel Off-Delay
Circuit Types
3
3
3
3
Input and Output Mapping
I/O
I/O
I/I
I/O
Fixed at 50 ms
Closed-to-open: 6 to 100 ms Open-to-closed: 10 to 500 ms
Fixed at 50 ms
Fixed at 50 ms
Yes, - Yes
Debounce Times
Monitored / Non-monitored
Manual Reset Devices: The manual reset is used to create a reset signal after a safety input device that has been configured to require a manual reset has been opened and closed. After the manual reset operation is performed, any of the Safety Outputs controlled by that safety input device can turn ON. WARNING: Non-Monitored Resets If a non-monitored reset (either latch or system reset) is configured and if all other conditions for a reset are in place, a short from the Reset terminal to +24 V will turn On the safety output(s) immediately. ON/Off Switch: provides an On or Off command to the machine. When all of the controlling safety inputs are in the Run state, this function permits the safety output to turn On and Off. This is a single-channel signal; the Run state is 24 V dc and the Stop state is 0 V dc. An On/Off input can be added without mapping to a safety output, which allows this input to control only a status output. Mute Enable Switch: signals the Controller when the mute sensors are permitted to perform a mute function. When the mute enable function is configured, the mute sensors are not enabled to perform a mute function until the mute enable signal is in the Run state. This is a single-channel signal; the enable (Run) state is 24 V dc and the disable (Stop) state is 0 V dc. Cancel Off-Delay Devices: provide the option to cancel a configured Off-delay time. It functions in one of the following ways: • Keeps the safety output On • Turns the safety output Off immediately after the Controller receives a Cancel Off-Delay signal A status output function (OK to Cancel Output's Off-Delay Status) indicates when a Cancel Delay Input can be activated in order to keep the Off-delayed safety output On.
30 www.bannerengineering.com - Tel: 763.544.3164
Page 31
SC22-3/-3E Safety Controller Instruction Manual
Table 1: Cancel Off-Delay Timing
Safety Input(s) (Manual or Auto)
Run Stop Cancel Delay Performed
Cancel Delay Input (Monitored Option Shown)
Reset Run Off Delay Ended
Safety Output (Cancel Off Delay) Status Output (OK to Cancel OFF-Delay)
ON OFF
Off Delay Normal End
Off Delay
2
1
Off Delay Started
Run Stop Cancel Delay Performed
Cancel Delay Input (Monitored Option Shown)
Reset Run Off Delay Ended
0.5 sec.
Active Inactive
1 2
Note 1 - If “turn output off” function is selected Note 2 - If “keep output on” function is selected
Figure 12. Safety Input remains in Stop mode
Manual Safety Input(s)
Safety Input(s) (Manual or Auto)
ON
Safety Output (Cancel Off Delay)
OFF
Status Output (OK to Cancel OFF-Delay)
Inactive
Off Delay Normal End
Off Delay
On (Auto) Off (Manual)
Off Delay Started 0.5 sec.
Active
Figure 13. Turn Output Off function
Run Stop Latch Reset Performed
Latch Reset Input (Monitored Reset Shown)
Reset
Cancel Delay Input (Monitored Option Shown)
Reset
Auto Safety Input(s)
Run
Run Stop Cancel Delay Performed
Cancel Delay Performed
Cancel Delay Input (Monitored Option Shown)
Run Off Delay Ended
Safety Output
Status Output (OK to Cancel OFF-Delay)
Run Off Delay Ended
Off Delay Normal End
Off Delay
ON OFF
Reset
Safety Output
Active
Status Output (OK to Cancel OFF-Delay)
Inactive
Figure 14. "Keep Output ON" function, manual (latch) Safety Input
Off Delay
ON OFF
Off Delay Started
Off Delay Normal End
Off Delay Started
Active Inactive
Figure 15. "Keep Output ON" function, auto (trip) Safety Input
4.5 Input Device Resets There are three reset types available: •
•
•
Manual Reset: used to manually reset a safety output that turned OFF in response to a Stop signal from the safety input device configured for manual (latch mode) reset. The reset signal type can be configured to be either monitored (default setting) or non-monitored. System Reset: used to recover from a fault condition or to restart the Controller after the configuration has been altered. This reset device (a button or a switch) connects to a dedicated input terminal on the Safety Controller, labeled SR. The reset signal type can be configured to be either monitored (default setting) or non-monitored. Automatic Reset: used to allow a safety output to return to an ON state without action by an individual once the input device changes to the Run state (provided that all other controlling inputs are also in the Run state). Also known as trip mode, the automatic reset is typically used in applications in which the individual is continually being sensed by the safety input device.
The reset switch must be mounted at a location that complies with the warning below. A key-actuated reset switch provides some operator or supervisory control, as the key can be removed from the switch and taken into the guarded area. However, this does not prevent from any unauthorized or inadvertent resets due to spare keys being in the possession of others, or additional personnel entering the guarded area unnoticed (a pass-through hazard). See section Perimeter Guarding and Pass-Through Hazards on page 33 for more information.
www.bannerengineering.com - Tel: 763.544.3164
31
Page 32
SC22-3/-3E Safety Controller Instruction Manual
WARNING: Reset Switch Location All reset switches must be accessible only from outside, and in full view of, the hazardous area. Reset switches must also be out of reach from within the safeguarded space, and must be protected against unauthorized or inadvertent operation (for example, through the use of rings or guards). If any areas are not visible from the reset switch(es), additional means of safeguarding must be provided. Failure to do so may result in serious bodily injury or death. Important: Resetting a safeguard must not initiate hazardous motion. Safe work procedures require a start-up procedure to be followed and the individual performing the reset to verify that the entire hazardous area is clear of all personnel before each reset of the safeguard is performed. If any area cannot be observed from the reset switch location, additional supplemental safeguarding must be used: at a minimum, visual and audible warnings of the machine start-up.
4.5.1 Reset Signal Requirements Both manual (latch) reset and system reset signals can be configured for monitored or non-monitored operation, as follows: Monitored reset: Requires the reset signal to transition from low (0 V dc) to high (24 V dc) and then back to low. The high state duration must be 0.3 to 2 seconds. This is called a trailing edge event. Non-monitored reset: Requires only that the reset signal transitions from low (0 V dc) to high (24 V dc) and stays high for at least 0.3 seconds. After the reset, the reset signal can be either high or low. This is called a leading-edge event.
4.5.2 Automatic and Manual Reset Inputs Mapped to the Same Safety Output Safety input devices can be configured for either manual (latch mode) or automatic (trip mode) reset, and both types can be mapped to the same safety output. In order for a safety output to turn on, all associated safety input devices must be in their Run state. If one or more of these safety input devices is configured for manual reset and one or more of them change from the Stop state to the Run state, then the output needs a valid manual reset signal before it turns on. If two safety inputs, each configured for manual reset, are mapped to the same safety output, then only one valid reset operation is required to reset the safety output. A manual reset operation is valid when all safety inputs mapped to the safety output are in the Run state and the manual reset is performed. If a manual reset is performed before a safety input is in the Run state, the manual reset signal is ignored, except in the case of a two-hand control and an ON/OFF input. See sections Manual Reset on page 70 and Automatic and Manual Reset Inputs Mapped to the Same Safety Output on page 32 for more information about resets. Safety Device 1 (Auto) Safety Device 2 (Manual) Manual Monitored Reset Input Safety Output
Figure 16. Timing logic: auto and manual monitored reset safety inputs mapped to the same Safety Output (no delay)
Safety Device 1 Manual Monitored Reset Safety Device 2 Manual Monitored Reset Manual Reset Safety Output Figure 17. Timing logic: Safety Outputs with a common reset, mapped to the same Safety Output
32 www.bannerengineering.com - Tel: 763.544.3164
Page 33
SC22-3/-3E Safety Controller Instruction Manual
4.5.3 Perimeter Guarding and Pass-Through Hazards A pass-through hazard is associated with applications, such as perimeter guarding, where personnel may pass through a safeguard (which issues a stop command to remove the hazard), and then continue into the guarded area, where their presence is no longer detected. The related danger becomes the unexpected start or restart of the machine while personnel are within the guarded area.
Reducing or Eliminating Pass-Through Hazards Eliminate or reduce pass-through hazards whenever possible. While it is recommended to eliminate the pass-through hazard altogether, this may not be possible due to machine layout, machine capabilities, or other application considerations. •
•
One solution is to ensure that personnel are continually sensed while within the hazardous area. This can be accomplished by using supplemental safeguarding, such as described by the ANSI B11 series of safety requirements or other appropriate standards. An alternate method is to ensure that when the safeguarding device is tripped, it will latch (manual reset), and will require a deliberate manual action to reset. This method of safeguarding relies upon the location of the reset switch as well as safe work practices and procedures to prevent an unexpected start or restart of the guarded machine. WARNING: Perimeter Guarding Applications If the application may result in a pass-through hazard (for example, perimeter guarding), either the safeguarding device or the guarded machine's MSCs/MPCEs must cause a Latched response following a Stop command (for example, interruption of the sensing field of a light curtain, or opening of an interlocked gate/guard). The reset of this Latched condition may only be achieved by actuating a reset switch that is separate from the normal means of machine cycle initiation. The switch must be positioned as described in this document. Lockout/Tagout procedures per ANSI Z244.1 may be required, or additional safeguarding, as described by ANSI B11 safety requirements or other appropriate standards, must be used if a passthrough hazard cannot be eliminated or reduced to an acceptable level of risk. Failure to observe this warning may result in serious bodily injury or death.
4.6 Safety Input Function 4.6.1 Internal Logic The Controller’s internal logic is designed so that a Safety Output can turn ON only if all the controlling safety input device signals and the Controller’s self-check signals are in the Run state and report that there is no fault condition. The table at right illustrates the logic for two safety input devices that are mapped to control Safety Output 1. If either safety input device is in the Stop state, the Safety Output will be OFF. When both safety inputs and the Controller are in the Run state, Safety Output 1 will be ON.
Safety Input 1
Safety Input 2
Safety Output 1
Stop
Stop
OFF
Stop
Run
OFF
Run
Stop
OFF
Run
Run
ON
4.6.2 Two-Hand Control (THC) The two-hand control function requires that two hand actuators (for example, hand/palm buttons) each be activated within 0.5 seconds of each other in order to produce a Run signal to start a machine cycle. THC devices are always the last input (in time) to turn the safety output ON. If one or more of the other controlling input devices are configured for manual reset and are used to stop the machine, a manual reset must be performed before the THC device can cycle the machine again. See section Two-Hand Control on page 96 for more information.
www.bannerengineering.com - Tel: 763.544.3164
33