Page 34
SC22-3/-3E Safety Controller Instruction Manual
Two-Hand Control Device Safety Device 2 (Manual Reset) Reset Signal Safety Output Figure 18. Timing logic: Two-Hand Control device and manual reset safety input device
Two-Hand Control Activation on Power-Up Protection. The Controller’s two-hand control logic will not permit the assigned safety output to turn ON when power is initially supplied while the THC actuators are in their Run state. The THC actuators must change to their Stop state and return to the Run state before the Safety Output can turn ON. A two-hand control device does not have a manual reset option.
4.6.3 Enabling Devices The enabling device actively controls the suspension of a Stop signal during a portion of a machine operation where a hazard can occur. The enabling device permits a hazardous portion of the machine to run, but must not start it. A separate machine command signal from another device is needed to start the hazardous motion. This enabling device must have ultimate hazard turn OFF or Stop authority when being used. An enabling device can be mapped to one or more safety outputs. When the enable signal goes from the Stop state to the Run state, the Controller will go into Enable mode. In this mode, the associated safety outputs will turn ON if any of the assigned EDM inputs are closed (these may open after the outputs turn ON) and all of the controlling E-stop or rope pull devices are in their Run state. With the exception of the E-stop and rope pull devices, all other safety input signals (Run or Stop) will be ignored while the Controller is in the Enable mode. Safety output enabling control resides in the enabling device function when in Enable mode. Repetitive enable cycles are allowed. In order to exit Enable mode, the enabling device must be in the OFF state, and a system reset must be performed. Enabling Device Time Limit. The enabling device time limit can be adjusted between 1 second and 30 minutes and cannot be disabled. When the time limit expires, the associated safety outputs will turn OFF. In order to start a new Enable mode cycle with the time limit reset set to its original time limit value, the enabling device must switch from ON to OFF, and the back to ON. All ON- and OFF-delay time limits associated with the safety outputs that are controlled by the enabling device function will be followed during the Enable mode.
Enable Device Don’t Care*
Safety Device
ONDelay
Safety Output (ON-Delayed)
ONDelay
System Reset Enable Mode ON
Enable Mode
Enable Mode OFF
*Unless it’s an E-Stop or a Rope-Pull Figure 19. Timing logic: Enabling device and enable mode
See section Enabling Device on page 106 for more information.
4.6.4 Mute Function Safety device muting is the automatically controlled suspension of one or more safety input stop signals during a portion of a machine operation when no immediate hazard is present or when access to the hazard is safeguarded. Muting sensors can be mapped to one or more of the following “mutable” safety input devices: • • • 34
Safety gate (interlocking) switches Optical sensors Two-hand controls www.bannerengineering.com - Tel: 763.544.3164
Page 35
SC22-3/-3E Safety Controller Instruction Manual • •
Safety mats Protective stops
E-stop buttons, rope pulls, enabling devices, external device monitoring, and bypass switches are non-mutable devices or functions. At least two mute sensors are required for each muting operation (the mute occurs typically 100 ms after the second mute sensor input has been satisfied). One or two pairs of mute sensors can be mapped to one or more safety input devices so that their assigned safety outputs can remain ON to complete the operation; see section Mute Sensor Pair on page 110 for more information. Mute Enable. The optional mute enable function can be configured to ensure that a mute function is permitted only at the appropriate time. If a mute enable input device has been mapped to a mutable safety input device, this safety input device can be muted only if the mute enable switch is in the Enable (24V dc) state at the time the mute cycle is started. After the mute cycle starts, the mute enable input can be turned OFF. A mute enable input device can be mapped to one or more mutable safety inputs. NOTE: Mute enable is not a safeguarding function, but rather a machine logic function.
Mute Enable
ON or OFF
Safety Input Mute Sensor Pair Safety Output Figure 20. Timing logic: one mute sensor pair with mute enable
Mute Time Limit (Backdoor Timer). A time limit can be established to limit how long a mute cycle is permitted to be active. The time limit can be adjusted from 1 second to 30 minutes. A different time limit can be set for each mutable safety input device. Other input devices that are also muted are affected only by their own mute time limit setting. The mute time limit can be disabled. When disabled, the time limit for the mute function for that input device is infinite. Directional Muting. As soon as two mute sensor pairs are configured and mapped to a mutable safety input, an advanced setting option appears in the PCI to provide the option of directional muting. Check the box "Enable Directional Muting," then select the muting sensor pair to be blocked first. The Controller requires sensor pair 1 to be blocked first, then the safeguard, then sensor pair 2 (all within the configured time limits) in order for the mute to take place. Mute Sensor Debounce Time. The input debounce time, accessible under the "Advanced settings" in the Mute Sensor Pair properties window, can be used to extend a mute cycle after a mute sensor signal is removed. By configuring the "closed-to-open" debounce time, the mute cycle can be extended up to 1.5 seconds (1500 ms) to allow the Safety Input Device to turn ON. The start of the mute cycle can also be delayed, by configuring the "open-to-closed" debounce time. Mute on Power-Up Function. If configured, the Mute on Power-Up function will initiate a mute cycle after power is applied to the Safety Controller if the muted safety inputs are active (Run state or closed), and either M1-M2 or M3-M4 (but not all four) are signaling a muted condition (active or closed). WARNING: Mute on Power-Up The Mute on Power-Up function should be used only in applications where: • •
Muting the System (M1 and M2 closed) when power is applied is required, and Using it does not, in any situation, expose personnel to any hazard.
Mute on Power-Up Disabled. When the mute on power-up option is disabled, the Controller will not go into a mute cycle, even if the conditions for a valid mute cycle are fulfilled at power-up. Mute on Power-Up Enabled. When the Mute on Power-Up option is enabled, the Controller will go into a mute cycle if the conditions for a valid mute cycle are fulfilled at power-up. Specific valid mute signal conditions must be present for a mute cycle to be initiated and maintained. If Auto Power-Up is configured, the Controller allows approximately 2 seconds for the input devices to become active (closed) to accommodate systems that may not be immediately active at power-up. If Manual Power-Up is configured and all other conditions are satisfied, the first valid system reset after the muted safety inputs are active (Run state or closed) will result in a mute cycle. The Mute On Power-up function should only be used if safety can be assured when the mute cycle is expected, and the use of this function is the result of a risk assessment and is required by that particular machine operation. www.bannerengineering.com - Tel: 763.544.3164
35
Page 36
SC22-3/-3E Safety Controller Instruction Manual
WARNING: Mute and Bypass Mute and Bypass operations must be done in a way that minimizes personnel risk. Implement the following when creating mute and bypass applications: • •
Guard against unintended stop signal suspension by using one or more diverse-redundant mute sensor pairs or a dual channel key-secured bypass switch. Set reasonable time limits (no longer than needed) for the mute and bypass functions.
Failure to follow these rules could lead to an unsafe condition that may result in serious injury or death. See section Mute Sensor Pair on page 110 for more information.
4.6.5 Bypass Function The safety device bypass is a manually activated and temporary suspension of one or more safety input stop signals when no immediate hazard is present. Bypass switches can be mapped to one or more of the following safety input devices: • Safety gate (interlocking) switches • Optical sensors • Two-hand control devices • Safety mats • Protective stop When the bypass switch signal changes to the Bypass (Run) state, it will turn On or keep On all of the safety outputs that are controlled by the bypassed safety input devices only if all other non-bypassed safety devices that are mapped to these Safety Outputs are in the Run state. If an input that is configured for a manual reset is turned off during a bypass, a manual reset must occur before the end of the bypass or the Safety Outputs will turn off. Bypass Time Limit. A bypass function time limit can be established to limit how long the safety input device bypass is active. The time limit can be adjusted from 1 second to 12 hours and cannot be disabled. Only one time limit can be set, and this limit will apply to all safety devices that are bypassed. At the end of the time limit, the safety output control authority is transferred back to the bypassed safety input devices. Two-Hand Control Bypassing. The Safety Controller locks out and issues a Stop signal if a Two-Hand Control input is actuated while the input is being bypassed. This ensures that the operator does not mistake that the Two-Hand Control is functional and is aware that the bypassed Two-Hand Control is no longer providing the safeguarding function. Mute-Dependent Override. When this option is enabled, and a mute sensor is mapped to the safety input device, and the safety input device is in the Stop state, at least one of the Mute sensors must be in the Mute (Run) state to start a new bypass cycle. If the conditions are right for the bypass, the mute status output indicator (if configured) starts flashing at 1 Hz. If this option is disabled, the safety input is not required to be in the Stop state and the mute sensors do not need to be blocked in order to start a new bypass cycle. Light Screen Mute Sensor 1 (2) Mute Sensor 2 (1) Bypass Switch Safety Output
Don’t Care BypassTime Expired
Figure 21. Timing logic: Light screen with mute sensors and bypass switch
4.6.6 Adjustable Valve Monitoring (AVM) Function The Adjustable Valve (Device) Monitoring (AVM) function is similar in function to One-Channel External Device Monitoring (1-channel EDM, see External Device Monitoring (EDM) on page 37). The AVM function monitors the state of the device(s) that are controlled by the safety output to which the function is mapped. When the safety output turns Off, the AVM input must be high/On (+24 V dc applied) before the AVM timer expires or a lockout will occur. The AVM input must also be high/On when the safety output attempts to turn On or a lockout will occur.
36 www.bannerengineering.com - Tel: 763.544.3164
Page 37
SC22-3/-3E Safety Controller Instruction Manual
Safety Output
AVM
ON OFF Closed Open
Don’t Care
Don’t Care 100 ms to 5 sec.
NOTE: 100 ms to 5 s time period is adjustable in 50 ms intervals (default is 100 ms). Figure 22. Timing logic - AVM Function
The Adjustable Valve (Device) Monitoring function is useful for dynamically monitoring devices under the control of the safety output that may become slow, stick, or fail in an energized state or position, and whose operation needs to be verified after a Stop signal occurs. Example applications include single- or dual-solenoid valves controlling clutch/brake mechanisms, and position sensors that monitor the home position of a linear actuator. Synchronization or checking a maximum differential timing between two or more devices, such as dual valves, may be achieved by mapping multiple AVM functions to one safety output and configuring the AVM timer to the same values. Any number of AVM inputs can be mapped to one safety output. An input signal can be generated by a hard/relay contact or a solid-state PNP output. CAUTION: Adjustable Valve Monitoring (AVM) Operation When an input is configured with automatic reset logic and is quickly cycled (from Run to Stop to Run), the Safety Output(s) will not turn ON until the AVM input is satisfied. This could result in an OnDelay up to the configured AVM monitoring time. The user is responsible to make sure that the AVM monitoring time is properly configured for the application and to instruct all individuals associated with the machine about the possibility of the On-Delay effect, which may not be readily apparent to the machine operator or other personnel.
4.7 EDM, OSSD (Safety Output), and FSD Hookup 4.7.1 External Device Monitoring (EDM) The Controller’s safety outputs can control external relays, contactors, or other devices that have a set of normally closed (N.C.), force-guided (mechanically linked) contacts that can be used for monitoring the state of the machine power contacts. The monitoring contacts are normally closed (N.C.) when the device is turned Off. This capability allows the Controller to detect if the devices under load are responding to the safety output, or if the N.O. contacts are possibly welded closed or stuck On. The EDM function provides a method to monitor these types of faults and to ensure the functional integrity of a dualchannel system, including the MPCEs and the FSDs. An EDM input can be mapped to only one safety output. The EDM inputs can be configured as one-channel, two-channel, or no monitoring. One-channel EDM inputs are used when the OSSD outputs directly control the de-energizing of the MPCEs or external devices. • One-Channel Monitoring - a series connection of closed monitor contacts that are forced-guided (mechanically linked) from each device controlled by the Controller. The monitor contacts must be closed before the Controller outputs can be reset (either manual or automatic). After a reset is executed and the safety outputs turn On, the status of the monitor contacts are no longer monitored and may change state. However, the monitor contacts must be closed within 250 milliseconds of the safety outputs changing from On to Off. • Two-Channel Monitoring - an independent connection of closed monitor contacts that are forced-guided (mechanically linked) from each device controlled by the Controller. Both EDM inputs must be closed before the Controller can be reset and the OSSDs can turn On. While the OSSDs are On, the inputs may change state (either both open, or both closed). A lockout occurs if the inputs remain in opposite states for more than 250 milliseconds. • No Monitoring - If no monitoring is desired, do not select either the one-channel or two-channel monitoring option. If the Controller does not use the EDM function in Category 3 or Category 4 applications, the user must make sure that any single failure or accumulation of failures of the external devices does not result in a hazardous condition and that a successive machine cycle is prevented.
www.bannerengineering.com - Tel: 763.544.3164
37
Page 38
SC22-3/-3E Safety Controller Instruction Manual
CAUTION: EDM Configuration If the application does not require the EDM function, it is the user’s responsibility to ensure that this does not create a hazardous situation. CAUTION: External Device Monitoring Hookup It is strongly recommended that at least one normally closed, forced-guided monitoring contact of each MPCE or external device is wired to monitor the state of the MPCEs (as shown in the hookup figures). If this is done, proper operation of the MPCEs will be verified. MPCE monitoring contacts must be used to maintain control reliability.
Safety Input Device
Safety Input Device
+24V dc
EDM EDM
EDM Safety Controller
MPCE 1
Safety Controller
MPCE 1
SO 1 MPCE 2
SO 1 MPCE 2 MPCE1
MPCE1
MPCE2
MPCE2
Single-channel EDM used to monitor both MPCE feedback signals. If one or both channels do not close, the system goes into a Lockout condition.
Figure 23. One-channel EDM hookup
Safety Output
EDM
Dual-channel EDM is used to monitor both MPCE feedback signals. If the channels are not in the same state, the system goes into a Lockout condi tion.
+24V dc
Figure 24. Two-channel EDM hookup
ON OFF Closed Open
Don’t Care
Don’t Care 250 ms Max.
Figure 25. Timing logic: One-channel EDM status, with respect to Safety Output
For two-channel EDM, as shown below, both channels must be closed before the Safety Output(s) turn On.
Safety Output
EDM 1
EDM 2
Safety Output
Don’t Care
Closed
EDM 1
Open Closed Open
250 ms Max.
250 ms Max.
Figure 26. Timing logic: Two-channel EDM, timing between channels
EDM 2
ON OFF Closed Open Closed Open
Must Match EDM 2
Must Match EDM 2
Must Match EDM 1
Must Match EDM 1
Figure 27. Timing logic: Two-channel EDM status, with respect to Safety Output
4.7.2 Safety Outputs The Safety Controller has three pairs of solid-state Safety Outputs (SO1 a and b, SO2 a and b, and SO3 a and b). Each pair consists of two output signal switching devices (OSSDs). The solid-state Safety Outputs are actively monitored to detect short circuits to the supply voltage, to each other, and to other sources of electrical energy. If a failure is detected, 38 www.bannerengineering.com - Tel: 763.544.3164
Page 39
SC22-3/-3E Safety Controller Instruction Manual the outputs will switch to an Off state. For circuits requiring the highest level of safety and reliability, either OSSD must be capable of stopping the motion of the guarded machine controlled by a safety output in an emergency. OSSD Output Connections The output signal switching device (OSSD) outputs must be connected to the machine control such that the machine’s safety related control system interrupts the circuit or power to the machine primary control element(s) (MPCE), resulting in a non-hazardous condition. Final switching devices (FSDs) typically accomplish this when the safety outputs go to the Off state. Refer to the Safety Outputs (6 terminals, 3 redundant outputs) on page 23 and the Warning below before making OSSD connections and interfacing the Controller to the machine. ON-Delays and Off-Delays Each safety output can be configured to function with either an On-delay or an Off-delay (see Figure below), where the output turns On or Off only after the time limit has elapsed. An output cannot have both On- and Off-delays. The On and Off time delay limit options are from 100 milliseconds to 5 minutes, in 100 millisecond increments. Current operation is to honor the Off-delay for internal and system faults, whenever possible. Safety Input
SO 1 (ON-Delay) SO 2 (OFF-Delay)
Delay
Delay 500 ms
Figure 28. Timing logic: Safety Output with Off-delay
NOTE: Safety Outputs are Dual-Channel. An individual safety output is not, by itself, capable of meeting Category 4 applications (per ISO13849-1). When the risk assessment or relevant regulations require high levels of safety integrity (such as Category 4), both the output signal switching device (OSSD) outputs must be connected to the machine control so that the machine’s safety related control system interrupts the circuit or power to the machine primary control element(s) (MPCEs), resulting in a non-hazardous condition. Final switching devices (FSDs) typically accomplish this when the OSSDs enter the Off state. WARNING: Off-Delays A safety output Off-Delay time will be honored even if the safety input that caused the Off-Delay timer to start changes back to the Run state before the delay time expires. However, in cases of a power interruption or a power loss, an Off-Delay time can end immediately. If such an immediate machine stop condition could cause a potential danger, additional safeguarding measures must be taken to prevent injuries. WARNING: Interfacing of Both OSSDs Both OSSD (Output Signal Switching Device) outputs must be connected to the machine control so that the machine’s safety-related control system interrupts the circuit to the machine primary control element(s), resulting in a non-hazardous condition. Never wire an intermediate device(s) (for example, PLC, PES, or PC) that can fail in such a manner that there is the loss of the safety stop command, OR in such a manner that the safety function can be suspended, overridden, or defeated, unless accomplished with the same or greater degree of safety. WARNING: Safety Output Lead Resistance To ensure proper operation, the resistance in the safety output wires should not exceed 10 ohms. A resistance higher than 10 ohms may mask a short between the dual-channel safety outputs and create an unsafe condition that may lead to serious bodily injury or death.
www.bannerengineering.com - Tel: 763.544.3164
39
Page 40
SC22-3/-3E Safety Controller Instruction Manual
4.7.3 FSD Interfacing Connections Final switching devices (FSDs) may take many forms, though the most common are forced-guided (mechanically linked) relays or Interfacing Modules. The mechanical linkage between the contacts allows the device to be monitored by the external device monitoring circuit for certain failures. Depending on the application, the use of FSDs can facilitate controlling voltage and current that differs from the OSSD outputs of the Controller. FSDs may also be used to control an additional number of hazards by creating multiple safety stop circuits.
Safety (Protective) Stop Circuits A safety stop allows for an orderly cessation of motion or hazardous situation for safeguarding purposes, which results in a stop of motion and removal of power from the MPCEs (assuming this does not create additional hazards). A safety stop circuit typically comprises a minimum of two normally open contacts from forced-guided (mechanically linked) relays (external device monitoring), which are monitored to detect certain failures so that the loss of the safety function does not occur. Such a circuit can be described as a “safe switching point.” Typically, safety stop circuits are a series connection of at least two N.O. contacts coming from two separate, positiveguided relays, each controlled by one separate safety output of the Controller. The safety function relies on the use of redundant contacts to control a single hazard, so that if one contact fails On, the second contact stops the hazard and prevents the next cycle from occurring. Interfacing safety stop circuits must be wired so that the safety function cannot be suspended, overridden, or defeated, unless accomplished in a manner at the same or greater degree of safety as the machine’s safety-related control system that includes the Controller. The normally open outputs from an interfacing module are a series connection of redundant contacts that form safety stop circuits and can be used in either single-channel or dual-channel control methods (see wiring diagrams). Dual-Channel Control. Dual-channel (or two-channel) control has the ability to electrically extend the safe switching point beyond the FSD contacts. With proper monitoring, such as EDM, this method of interfacing is capable of detecting certain failures in the control wiring between the safety stop circuit and the MPCEs. These failures include a short-circuit of one channel to a secondary source of energy or voltage, or the loss of the switching action of one of the FSD outputs, which may lead to the loss of redundancy or a complete loss of safety if not detected and corrected. The possibility of a wiring failure increases as the physical distance between the FSD safety stop circuits and the MPCEs increase, as the length or the routing of the interconnecting wires increases, or if the FSD safety stop circuits and the MPCEs are located in different enclosures. Thus, dual-channel control with EDM monitoring should be used in any installation where the FSDs are located remotely from the MPCEs. Single-Channel Control. Single-channel (or one-channel) control uses a series connection of FSD contacts to form a safe switching point. After this point in the machine’s safety-related control system, failures that would result in the loss of the safety function can occur, for example, a short-circuit to a secondary source of energy or voltage. Thus, this method of interfacing should be used only in installations where FSD safety stop circuits and the MPCEs are physically located within the same control panel, adjacent to each other, and are directly connected to each other; or where the possibility of such a failure can be excluded. If this cannot be achieved, then two-channel control should be used. Methods to exclude the possibility of these failures include, but are not limited to: • Physically separating interconnecting control wires from each other and from secondary sources of power • Routing interconnecting control wires in separate conduit, runs, or channels • Routing interconnecting control wires with low voltage or neutral that cannot result in energizing the hazard • Locating all elements (modules, switches, devices under control, etc.) within the same control panel, adjacent to each other, and directly connected with short wires • Properly installing multi-conductor cabling and multiple wires that pass through strain-relief fittings. Overtightening of a strain-relief can cause short circuits at that point • Using positive-opening or direct-drive components installed and mounted in a positive mode WARNING: Use of Transient Suppressors Transient suppressors are recommended. They MUST be installed across the coils of the FSDs. NEVER install suppressors directly across the contacts of the FSDs. It is possible for suppressors to fail as a short circuit. If installed directly across the contacts of the FSDs, a short-circuited suppressor creates an unsafe condition.
40 www.bannerengineering.com - Tel: 763.544.3164
Page 41
SC22-3/-3E Safety Controller Instruction Manual
WARNING: OSSD Interfacing To ensure proper operation, the Banner device output parameters and machine input parameters must be considered when interfacing the solid state safety outputs to the machine inputs. Machine control circuitry must be designed so that: • The maximum open ground leakage current must not result in an On condition • The maximum cable resistance value between the Safety Controller solid-state safety outputs and the machine inputs is not exceeded • The Safety Controller’s solid-state safety output maximum Off state voltage does not result in an On condition • The Safety Controller’s solid-state safety output maximum leakage current, due to the loss of 0 V, does not result in an On condition Failure to properly interface the safety outputs to the guarded machine may result in serious bodily injury or death. WARNING: Shock Hazard and Hazardous Energy Always disconnect power from the safety system (for example, device, module, interfacing, etc.) and the machine being controlled before making any connections or replacing any component. Electrical installation and wiring must be made by Qualified Personnel5 and must comply with the relevant electrical standards and wiring codes, such as the NEC (National Electrical Code), ANSI NFPA79, or IEC 60204-1, and all applicable local standards and codes. Lockout/tagout procedures may be required. Refer to OSHA 29CFR1910.147, ANSI Z244-1, ISO 14118, or the appropriate standard for controlling hazardous energy. WARNING: Proper Wiring The generalized wiring configurations shown are provided only to illustrate the importance of proper installation. The proper wiring of the Safety Controller to any particular machine is solely the responsibility of the installer and end user.
Generic Hookup: 1-channel, 2-channel, and No EDM Options The following figure is generic in nature and represents all three EDM options: • • •
Safety Output SO1 is shown with No EDM configured (typically used with self-monitored devices) Safety Output SO2 is shown with Two-Channel EDM configured Safety Output SO3 is shown with One-Channel EDM configured
Any particular Safety Controller configuration may use any combination of external device monitoring options, depending on the application.
5 A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.
www.bannerengineering.com - Tel: 763.544.3164
41
Page 42
SC22-3/-3E Safety Controller Instruction Manual
SO2 2A 2B
SO3 3A 3B
FSD 3A 3B
Safety Stop Circuit
+24V dc
Dual-Channel
SO1 1A 1B
Single-Channel
Safety Controller
Dual-Channel
Input Terminals
Single-Channel
Safety Stop Circuit
FSD 2A 2B +24V dc
FSD 1A 1B Figure 29. Generic Hookup: 1-channel, 2-channel, and no EDM