Page 43
SC22-3/-3E Safety Controller Instruction Manual
One-Channel EDM Hookup to SC-IM9A Interface Module The SC-IM9A interface module depicted in the following figure is shown in one-channel EDM hookup. The SC-IM9B and SCIM9C modules are connected in the same manner, using individual one-channel EDM circuits (terminals 21/22 on each pair of contactors).
+24V dc
Machine Control
SC-IM9A Input Terminals Safety Controller
SO1 1A 1B
SO2 2A 2B
SO3 3A 3B
A2
13
21
33
43
A1
14
22
34
44
A2
13
21
33
43
A1
14
22
34
44
A2
Supplied Terminal Block
(To
(To
SO
SO
1A )
1B )
3 wires
*
MPCE 1 MPCE * 2
MPCE 3
*
+24V dc
0V dc
* Installation of transient (arc) suppressors across the coils of MPCE1, MPCE2, and MPCE3 is recommended (see Warning) Figure 30. One-channel EDM hookup to SC-IM9A interface module www.bannerengineering.com - Tel: 763.544.3164
43
Page 44
SC22-3/-3E Safety Controller Instruction Manual
Two-Channel EDM Hookup to IM-T-9A Interface Module The IM-T-9A interface module depicted in the following figure is shown in two-channel EDM hookup. The IM-T-11A module is connected in a similar manner. Depending on the application, each Safety Output requires a separate and individually wired IM-T-..A module.
Input Terminals Safety Controller SO1 1A
1B
SO2 2A
2B
SO3 3A
3B
0V dc
A2
IM-T-9A S1
S3 K2 +24V dc
Machine Control
K1
S4
S2
Y3
Y4
Y1
Y2
13
14
23
24
33
34
MPCE 1
* MPCE 2
*
Feedback (optional) * Installation of transient (arc) suppressors across the coils of MPCE1 and MPCE2 is recommended (see Warning) Figure 31. Hookup: Two-channel EDM hookup to IM-T-9A interface module
44 www.bannerengineering.com - Tel: 763.544.3164
Page 45
SC22-3/-3E Safety Controller Instruction Manual
One-Channel EDM Hookup to IM-T-9A Interface Module The IM-T-9A interface module depicted in the following figure is shown in one-channel EDM hookup. The IM-T-11A module is connected in a similar manner. Depending on the application, each Safety Output requires a separate and individually wired IM-T-..A module.
Input Terminals Safety Controller SO1 1A 1B
SO2 2A 2B
SO3 3A 3B
0V dc
A2
IM-T-9A S3
S1 K2
+24V dc
Machine Control
K1
S4
S2
Y3
Y4
Y1
Y2
13
14
23
24
33
34
MPCE 1
* MPCE 2
*
Feedback (optional) * Installation of transient (arc) suppressors across the coils of MPCE1 and MPCE2 is recommended (see Warning) Figure 32. Hookup: One-channel EDM hookup to IM-T-9A interface module www.bannerengineering.com - Tel: 763.544.3164
45
Page 46
SC22-3/-3E Safety Controller Instruction Manual
4.7.4 Common Wire Installation Keep in mind the lead wire resistance of the 0V common wire and the currents flowing in that wire to avoid nuisance lockout codes 1.1, 1.2, or 1.5. Note the location of the block in the diagram below representing lead wire resistance (RL).
Power Supply 0V
Safety Controller
24V dc
24V dc 0V
SO1
Other Equipment SO2
SO3
RL = Leadwire resistance Vo = Voltage > 0.9V when a safety output is off (or pulsing off) may cause error codes 1.1, 1.2, 1.5
Load Current Other Current
RL 6 Output Loads
Figure 33. DC-common wire installation
When a safety output turns Off, the voltage at the output terminal (VO ) must drop below 0.9V with respect to the 0V terminal of the Safety Controller. If the voltage is higher than 0.9V, the Controller may decide that the output is still on and lock out. This residual voltage may occur in several ways: • • • a large current flowing in a shared 0V conductor by other safety outputs that are still on a common mode current flowing from other equipment either of these, along with a 0V wire which is too small or too long
The solution is to increase the wire gauge of the 0V common wire and/or consider using the courtesy 0V terminals on the Safety Controller as shown in the following diagram. This eliminates the influence of common mode current from other equipment.
Power Supply 0V
Safety Controller
24V dc
24V dc 0V
SO1
Improved Wiring Scheme: - Either dashed wire is OK - Consider heavier wire - Better: Use separate 0V return for each pair of outputs (a+b) when heavily loaded
1 a
1 b
Other Equipment SO2
2 a
SO3
2 b
3 a
3 b
Load Current Other Current
6 Output Loads Figure 34. DC-common wire installation: eliminating the influence of common mode current from other equipment
4.8 Status Outputs 4.8.1 Status Output Signal Conventions Two signal conventions are selectable for each status output. The default convention provides a 24V dc signal when the monitored input or output is active (closed, high or ON), when the system is in a Lockout, when there is an I/O-fault, when the system is waiting for a Reset, when the output is waiting for a reset, or during an active mute cycle. If the above conditions are not true, the signal output would show 0V. Signal convention 2 is the reverse of the convention 1, as shown in the following table. Mapped Status Output(s) State Tracked Function
Track Input
46
Signal Convention 1 (default)
Signal Convention 2
24V dc = Run
0V dc = Run
Input Run
Input Stop
Input Run
Input Stop
24V dc
0V dc
0V dc
24V dc www.bannerengineering.com - Tel: 763.544.3164
Page 47
SC22-3/-3E Safety Controller Instruction Manual
Mapped Status Output(s) State Tracked Function
Track Output
Signal Convention 1 (default)
Signal Convention 2
24V dc = Run
0V dc = Run
Output ON
Output OFF
Output ON
Output OFF
24V dc
0V dc
0V dc
24V dc
Lockout
Run Mode
Lockout
Run Mode
24V dc
0V dc
0V dc
24V dc
Fault
No Fault
Fault
No Fault
24V dc
0V dc
0V dc
24V dc
System Waiting for Reset
Reset Required
Reset Not Required
Reset Required
Reset Not Required
24V dc
0V dc
0V dc
24V dc
Mute Status
Muted
No Mute
Muted
No Mute
24V dc
0V dc
0V dc
24V dc
Input That Turned OFF First
Other Linked Inputs
Input That Turned OFF First
Other Linked Inputs
24V dc
0V dc
0V dc
24V dc
Input Bypassed
Not Bypassed
Input Bypassed
Not Bypassed
24V dc
0V dc
0V dc
24V dc
Fault
No Fault
Fault
No Fault
24V dc
0V dc
0V dc
24V dc
OK
Not OK
OK
Not OK
24V dc
0V dc
0V dc
24V dc
System Lockout Status I/O Fault
Track Input Group
Bypass Status
Track Input Fault
OK to Cancel OFFDelay www.bannerengineering.com - Tel: 763.544.3164
47
Page 48
SC22-3/-3E Safety Controller Instruction Manual
4.8.2 Status Output Functionality Track Input A Status Output configured for this function will indicate the current state of an input. Track Output A Status Output configured for this function will indicate the current physical state of a Safety Output, either ON or OFF. Track Output’s Logical State When selecting the Status Output function ‘Track output,’ an option to track the logical state, rather than the physical state, of a Safety Output is provided. This option may be used to indicate a Safety Output has been commanded OFF, but is not OFF yet, such as during an OFF-delay. System Lockout Status A Status Output configured for this function will be active when a lockout that affects the entire Safety Controller has been detected, such as an internal memory fault. I/O Fault Status A Status Output configured for this function will be active when a lockout affecting a particular input or output has been detected, such as a failed input or an EDM fault. System Waiting for Reset A Status Output configured for this function will be active under the following conditions: • • • • • • •
A system fault has occurred and all Safety Outputs are OFF. An EDM fault has occurred. An AVM fault has occurred. A fault on a Safety Output has occurred. A fault for monitoring a mute lamp has occurred. The Safety Controller is configured for manual reset on power-up. A fault on a THC input has occurred.
The following conditions involve the use of the system reset but no indication is provided by a Status Output: • • •
Exiting Configuration Mode Exiting Enable Mode Re-enabling a Track Input Group function of a Status Output
Output Waiting for Reset A Status Output configured for this function will be active when a Safety Output is ready to be turned ON (a manual reset must be performed). Mute Status A Status Output configured for this function will be active for a particular mutable Safety Input under the following conditions: • • • •
ON during an active muting cycle. OFF during an inactive muting cycle. Flashing when all conditions for bypassing a mutable Safety Input (override) are present. ON when bypassing a mutable Safety Input.
Track Input Group Status Outputs configured for this function will indicate which Safety Input of a defined group of Safety Inputs turned OFF first. Use a system reset to re-enable the function after all Safety Inputs of the group are ON. Bypass Status Status Outputs configured for this function will indicate when an input is truly bypassed. A Safety Input is required to be determined inactive at least once before a bypass can take place. The Status Output is active when the input is bypassed. A bypass cannot take place (the input must be open) on power-up. Track Input Fault Status Outputs configured for this function will indicate any fault on an input. 48 www.bannerengineering.com - Tel: 763.544.3164
Page 49
SC22-3/-3E Safety Controller Instruction Manual OK to Cancel OFF-Delay Status Outputs configured for this function will indicate when an OFF-delay can be cancelled, that is, when the cancel delay input can be activated in order to keep the OFF-delayed Safety Output ON, or to immediately turn the Safety Output OFF.
4.9 Virtual Status Outputs Using the PCI, the Safety Controller (model SC22-3E only) can configure up to 32 virtual status outputs. These outputs can communicate the same information as the status outputs (see section Status Output Signal Conventions on page 46), but over a network. The virtual status outputs appear and can be configured after the Enable Network Interface box is checked on the Network Settings menu in section Ethernet Reference on page 116. The Auto Configure function, located in the Properties window, automatically configures the Virtual Status Outputs to a set of commonly used functions, based on the current configuration. This function is best used after the configuration has been determined. Virtual Status Output configuration can be manually revised after the Auto Configure function has been used, The information available over the network is consistent with the logical state of the inputs and outputs within 100 ms for the Virtual Status Output tables (viewable on the PCI) and within 1 second for the other tables (found on the included CD). The logical state of inputs and outputs is determined after all internal debounce and testing is complete. The PC Interface network functions are covered in more detail in the Ethernet Reference on page 116.
4.10 Commissioning Checkout After power is connected to the Controller, the EDM has been properly configured, and the safety outputs have been connected to the machine to be guarded, the operation of the Controller with the guarded machine must be verified before the combined system may be put into service. To do this, a Qualified Person must perform the commissioning checkout procedure; see section Commissioning Checkout Procedure on page 72.