The text of a manual · part 7 of 18

SC22-3/-3E Safety Controller Instruction Manual: 4 System Installation, pages 43 to 49

Pages 43 to 49 of 122, from SC22-3/-3E Safety Controller Instruction Manual

The original document is the PDF (6.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Banner SC22-3E

Page 43

SC22-3/-3E Safety Controller Instruction Manual

One-Channel EDM Hookup to SC-IM9A Interface Module The SC-IM9A interface module depicted in the following figure is shown in one-channel EDM hookup. The SC-IM9B and SCIM9C modules are connected in the same manner, using individual one-channel EDM circuits (terminals 21/22 on each pair of contactors).

+24V dc

Machine Control

SC-IM9A Input Terminals Safety Controller

SO1 1A 1B

SO2 2A 2B

SO3 3A 3B

A2

13

21

33

43

A1

14

22

34

44

A2

13

21

33

43

A1

14

22

34

44

A2

Supplied Terminal Block

(To

(To

SO

SO

1A )

1B )

3 wires

*

MPCE 1 MPCE * 2

MPCE 3

*

+24V dc

0V dc

* Installation of transient (arc) suppressors across the coils of MPCE1, MPCE2, and MPCE3 is recommended (see Warning) Figure 30. One-channel EDM hookup to SC-IM9A interface module www.bannerengineering.com - Tel: 763.544.3164

43

Page 44

SC22-3/-3E Safety Controller Instruction Manual

Two-Channel EDM Hookup to IM-T-9A Interface Module The IM-T-9A interface module depicted in the following figure is shown in two-channel EDM hookup. The IM-T-11A module is connected in a similar manner. Depending on the application, each Safety Output requires a separate and individually wired IM-T-..A module.

Input Terminals Safety Controller SO1 1A

1B

SO2 2A

2B

SO3 3A

3B

0V dc

A2

IM-T-9A S1

S3 K2 +24V dc

Machine Control

K1

S4

S2

Y3

Y4

Y1

Y2

13

14

23

24

33

34

MPCE 1

* MPCE 2

*

Feedback (optional) * Installation of transient (arc) suppressors across the coils of MPCE1 and MPCE2 is recommended (see Warning) Figure 31. Hookup: Two-channel EDM hookup to IM-T-9A interface module

44 www.bannerengineering.com - Tel: 763.544.3164

Page 45

SC22-3/-3E Safety Controller Instruction Manual

One-Channel EDM Hookup to IM-T-9A Interface Module The IM-T-9A interface module depicted in the following figure is shown in one-channel EDM hookup. The IM-T-11A module is connected in a similar manner. Depending on the application, each Safety Output requires a separate and individually wired IM-T-..A module.

Input Terminals Safety Controller SO1 1A 1B

SO2 2A 2B

SO3 3A 3B

0V dc

A2

IM-T-9A S3

S1 K2

+24V dc

Machine Control

K1

S4

S2

Y3

Y4

Y1

Y2

13

14

23

24

33

34

MPCE 1

* MPCE 2

*

Feedback (optional) * Installation of transient (arc) suppressors across the coils of MPCE1 and MPCE2 is recommended (see Warning) Figure 32. Hookup: One-channel EDM hookup to IM-T-9A interface module www.bannerengineering.com - Tel: 763.544.3164

45

Page 46

SC22-3/-3E Safety Controller Instruction Manual

4.7.4 Common Wire Installation Keep in mind the lead wire resistance of the 0V common wire and the currents flowing in that wire to avoid nuisance lockout codes 1.1, 1.2, or 1.5. Note the location of the block in the diagram below representing lead wire resistance (RL).

Power Supply 0V

Safety Controller

24V dc

24V dc 0V

SO1

Other Equipment SO2

SO3

RL = Leadwire resistance Vo = Voltage > 0.9V when a safety output is off (or pulsing off) may cause error codes 1.1, 1.2, 1.5

Load Current Other Current

RL 6 Output Loads

Figure 33. DC-common wire installation

When a safety output turns Off, the voltage at the output terminal (VO ) must drop below 0.9V with respect to the 0V terminal of the Safety Controller. If the voltage is higher than 0.9V, the Controller may decide that the output is still on and lock out. This residual voltage may occur in several ways: • • • a large current flowing in a shared 0V conductor by other safety outputs that are still on a common mode current flowing from other equipment either of these, along with a 0V wire which is too small or too long

The solution is to increase the wire gauge of the 0V common wire and/or consider using the courtesy 0V terminals on the Safety Controller as shown in the following diagram. This eliminates the influence of common mode current from other equipment.

Power Supply 0V

Safety Controller

24V dc

24V dc 0V

SO1

Improved Wiring Scheme: - Either dashed wire is OK - Consider heavier wire - Better: Use separate 0V return for each pair of outputs (a+b) when heavily loaded

1 a

1 b

Other Equipment SO2

2 a

SO3

2 b

3 a

3 b

Load Current Other Current

6 Output Loads Figure 34. DC-common wire installation: eliminating the influence of common mode current from other equipment

4.8 Status Outputs 4.8.1 Status Output Signal Conventions Two signal conventions are selectable for each status output. The default convention provides a 24V dc signal when the monitored input or output is active (closed, high or ON), when the system is in a Lockout, when there is an I/O-fault, when the system is waiting for a Reset, when the output is waiting for a reset, or during an active mute cycle. If the above conditions are not true, the signal output would show 0V. Signal convention 2 is the reverse of the convention 1, as shown in the following table. Mapped Status Output(s) State Tracked Function

Track Input

46

Signal Convention 1 (default)

Signal Convention 2

24V dc = Run

0V dc = Run

Input Run

Input Stop

Input Run

Input Stop

24V dc

0V dc

0V dc

24V dc www.bannerengineering.com - Tel: 763.544.3164

Page 47

SC22-3/-3E Safety Controller Instruction Manual

Mapped Status Output(s) State Tracked Function

Track Output

Signal Convention 1 (default)

Signal Convention 2

24V dc = Run

0V dc = Run

Output ON

Output OFF

Output ON

Output OFF

24V dc

0V dc

0V dc

24V dc

Lockout

Run Mode

Lockout

Run Mode

24V dc

0V dc

0V dc

24V dc

Fault

No Fault

Fault

No Fault

24V dc

0V dc

0V dc

24V dc

System Waiting for Reset

Reset Required

Reset Not Required

Reset Required

Reset Not Required

24V dc

0V dc

0V dc

24V dc

Mute Status

Muted

No Mute

Muted

No Mute

24V dc

0V dc

0V dc

24V dc

Input That Turned OFF First

Other Linked Inputs

Input That Turned OFF First

Other Linked Inputs

24V dc

0V dc

0V dc

24V dc

Input Bypassed

Not Bypassed

Input Bypassed

Not Bypassed

24V dc

0V dc

0V dc

24V dc

Fault

No Fault

Fault

No Fault

24V dc

0V dc

0V dc

24V dc

OK

Not OK

OK

Not OK

24V dc

0V dc

0V dc

24V dc

System Lockout Status I/O Fault

Track Input Group

Bypass Status

Track Input Fault

OK to Cancel OFFDelay www.bannerengineering.com - Tel: 763.544.3164

47

Page 48

SC22-3/-3E Safety Controller Instruction Manual

4.8.2 Status Output Functionality Track Input A Status Output configured for this function will indicate the current state of an input. Track Output A Status Output configured for this function will indicate the current physical state of a Safety Output, either ON or OFF. Track Output’s Logical State When selecting the Status Output function ‘Track output,’ an option to track the logical state, rather than the physical state, of a Safety Output is provided. This option may be used to indicate a Safety Output has been commanded OFF, but is not OFF yet, such as during an OFF-delay. System Lockout Status A Status Output configured for this function will be active when a lockout that affects the entire Safety Controller has been detected, such as an internal memory fault. I/O Fault Status A Status Output configured for this function will be active when a lockout affecting a particular input or output has been detected, such as a failed input or an EDM fault. System Waiting for Reset A Status Output configured for this function will be active under the following conditions: • • • • • • •

A system fault has occurred and all Safety Outputs are OFF. An EDM fault has occurred. An AVM fault has occurred. A fault on a Safety Output has occurred. A fault for monitoring a mute lamp has occurred. The Safety Controller is configured for manual reset on power-up. A fault on a THC input has occurred.

The following conditions involve the use of the system reset but no indication is provided by a Status Output: • • •

Exiting Configuration Mode Exiting Enable Mode Re-enabling a Track Input Group function of a Status Output

Output Waiting for Reset A Status Output configured for this function will be active when a Safety Output is ready to be turned ON (a manual reset must be performed). Mute Status A Status Output configured for this function will be active for a particular mutable Safety Input under the following conditions: • • • •

ON during an active muting cycle. OFF during an inactive muting cycle. Flashing when all conditions for bypassing a mutable Safety Input (override) are present. ON when bypassing a mutable Safety Input.

Track Input Group Status Outputs configured for this function will indicate which Safety Input of a defined group of Safety Inputs turned OFF first. Use a system reset to re-enable the function after all Safety Inputs of the group are ON. Bypass Status Status Outputs configured for this function will indicate when an input is truly bypassed. A Safety Input is required to be determined inactive at least once before a bypass can take place. The Status Output is active when the input is bypassed. A bypass cannot take place (the input must be open) on power-up. Track Input Fault Status Outputs configured for this function will indicate any fault on an input. 48 www.bannerengineering.com - Tel: 763.544.3164

Page 49

SC22-3/-3E Safety Controller Instruction Manual OK to Cancel OFF-Delay Status Outputs configured for this function will indicate when an OFF-delay can be cancelled, that is, when the cancel delay input can be activated in order to keep the OFF-delayed Safety Output ON, or to immediately turn the Safety Output OFF.

4.9 Virtual Status Outputs Using the PCI, the Safety Controller (model SC22-3E only) can configure up to 32 virtual status outputs. These outputs can communicate the same information as the status outputs (see section Status Output Signal Conventions on page 46), but over a network. The virtual status outputs appear and can be configured after the Enable Network Interface box is checked on the Network Settings menu in section Ethernet Reference on page 116. The Auto Configure function, located in the Properties window, automatically configures the Virtual Status Outputs to a set of commonly used functions, based on the current configuration. This function is best used after the configuration has been determined. Virtual Status Output configuration can be manually revised after the Auto Configure function has been used, The information available over the network is consistent with the logical state of the inputs and outputs within 100 ms for the Virtual Status Output tables (viewable on the PCI) and within 1 second for the other tables (found on the included CD). The logical state of inputs and outputs is determined after all internal debounce and testing is complete. The PC Interface network functions are covered in more detail in the Ethernet Reference on page 116.

4.10 Commissioning Checkout After power is connected to the Controller, the EDM has been properly configured, and the safety outputs have been connected to the machine to be guarded, the operation of the Controller with the guarded machine must be verified before the combined system may be put into service. To do this, a Qualified Person must perform the commissioning checkout procedure; see section Commissioning Checkout Procedure on page 72.