The text of a manual · part 8 of 18

SC22-3/-3E Safety Controller Instruction Manual: 5 PC Interface Configuration (PCI)

Pages 50 to 58 of 122, from SC22-3/-3E Safety Controller Instruction Manual

The original document is the PDF (6.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Banner SC22-3E

Page 50

SC22-3/-3E Safety Controller Instruction Manual

5 PC Interface Configuration (PCI) 5.1 PC Interface (PCI) Overview The PC Interface (PCI) is a computer program with real-time display and diagnostic tools that can be used to: • • • •

Create, confirm, edit, store, send, and receive a configuration Display real-time Run mode information Record and display fault log data Record specific, user-defined information onto a "Notes" page.

The PCI program uses Input Device icons and circuit symbols to aid making appropriate device property selections. As the various device properties and I/O control relationships are established, the program automatically builds the corresponding wiring and ladder logic diagrams. These diagrams provide I/O device wiring detail for the installer and a symbolic representation of the Controller’s safeguarding logic for the use of the machine designer or controls engineer. See the Safety Controller PCI tutorial for further instruction.

5.1.1 Configuration Tools The PC Interface screen has a tool bar above the work area for creating and managing configuration files. Use the Live Display button to display real time Run mode data from a working Controller over a USB connection. The screen below shows the status after the Enable Network Interface button has been checked, enabling the Virtual Status Outputs and additional tabs above the documents section.

Send, receive and confirm buttons appear in color when a powered Controller or programming tool is connected to the PC

Access the live display

Add a non-safety Access Status input to the Output settings configuration Access Virtual Access Add a safety Status Output Safety Output input to the settings settings configuration

Access Network Settings

Access system settings

Tool Bar

Documents Section (Wiring Diagram shown)

I/O Properties Double-click to access property settings.

Figure 35. PCI Main screen components

50 www.bannerengineering.com - Tel: 763.544.3164

Page 51

SC22-3/-3E Safety Controller Instruction Manual

5.1.2 Build a Configuration To install the software on your computer, double-click on the Banner Safety Controller icon . Read and understand the warning on the Start-up page, and click OK. The main PCI screen should appear. The support documents, if opened at this point, show basic information, and auto-populate as the configuration develops; see following figure. Not shown is the Notes document, which remains blank until information is entered by the user, as desired.

Ladder Logic Diagram Configuration Summary

Wiring Diagram

Modbus/TCP Register Map for the Virtual Status Outputs EtherNet/IP Input Assemblies

PCCC N7 Register Map for the Virtual Status Outputs EtherNet/IP Explicit Messages

Column and row heading descriptions for the Ethernet forms are located in Appendix D.

Figure 36. Configuration support documentation (notes not shown)

www.bannerengineering.com - Tel: 763.544.3164

51

Page 52

SC22-3/-3E Safety Controller Instruction Manual

Create a New Configuration Open the software program, and a new un-named file is created. You may name the Configuration and the Author, and establish the system settings at this time. , on the right-hand side of the Tool Bar.

Double-click the System Settings icon

When the pop-up menu appears, name the configuration file, using up to 16 alphanumeric characters. Add your name in the Author’s name box (up to 10 characters; abbreviate as needed). Keep or change the default system settings: • • •

Power up mode: Auto, Manual, or Normal (default), see section System Settings on page 18 Mute on power up: ON or OFF (default), see section System Settings on page 18 Monitored system reset: OFF or ON (default), see section Non-Safety Input Devices on page 30

When complete, click OK.

Add an Input Device Refer to section Input Device and Safety Category Reference on page 86 for more information about each of the input device types. Click the Add Safety Input icon and the Safety Input Device selection menu appears. It displays the device types the Controller can accommodate. Safety Input Devices • • • • • • • • • • •

Emergency stop button Rope pull Gate (interlock) switch Optical sensor (single-/multiple-beam sensors, safety light curtain, area scanner, etc.) Two-hand control device Safety mat Protective stop (miscellaneous devices) Enabling device Muting sensors Bypass switches External device monitoring (EDM or AVM) contacts Figure 37. Safety Input Device Selection menu

Click the Non-Safety Input icon and the Non-Safety Input Device selection menu appears. Non-Safety Input Devices • • • •

Manual reset switch ON/OFF switch Mute enable switch Cancel OFF-delay switch

While their functions differ, the procedure to add and configure the two types of devices is virtually identical. Click on the appropriate icon to select the desired device and click OK (or double-click on the icon).

Figure 38. Non-Safety Input Device Selection menu

52 www.bannerengineering.com - Tel: 763.544.3164

Page 53

SC22-3/-3E Safety Controller Instruction Manual

Select the Input Device Properties After an input device is selected, the Properties menu for that device pops up. This menu presents the properties that must be established for each type of input device. The user-defined properties include (depending on the device): • • • • •

Name - The name (or circuit designation) of each specific device (not device type) Circuit Type - A list of the types of contact or solid-state circuits that can be used for that device type Reset Logic - Automatic (Trip mode) and Manual (Latch mode) options for that device Input Terminal Assignment - These are assigned automatically but can be changed to any unused input terminal. I/O map - Establishes relationships between input devices and outputs NOTE: Input device properties and functions are discussed in sections Safety Input Device Properties on page 27 and Input Device and Safety Category Reference on page 86.

Follow the configuration steps as they appear on the screen, as shown in the following figure. Name: Change the name to something meaningful to you, such as: E-STOP1. Any input device can be renamed during the configuration process. Circuit Type: Select the appropriate circuit type from the drop-down menu for your device. The selected circuit type will appear in the input terminals diagram, with automatically assigned terminal numbers; the terminal numbers can be reassigned using the drop-down menus. The plus signs at S13 and S15 designate that these terminals supply the +24V dc source for the device contacts. NOTE: See section Input Device and Safety Category Reference on page 86 for more information about safety circuit integrity levels and the capabilities of each circuit type. Reset Logic: Select between Manual or Automatic Reset from the drop-down menu. Mapping: Map each safety input device to one or more Safety Outputs (at least one must be selected) by checking or unchecking the boxes. (Click on a box to select or deselect it.) If the safety input device is a muting sensor, a bypass switch, or a mute enable sensor, map those inputs to at least one of the other safety input devices. When a safety input device with manual reset is added, a new window automatically appears to add a reset input device for that device. Any safety input device which keeps the default Manual reset logic setting requires a reset for any Safety Output mapped to that device. A separate reset may be assigned for each Safety Output. The wiring diagram will begin to populate with your chosen device(s), as will the ladder logic diagram and configuration summary.

Type in a name for the device Select a circuit type from the drop-down menu Select the reset logic from the drop-down menu Depicts the selected circuit type and terminal assignments + indicates the terminal that supplies the +24V dc source for the device Use the drop-down menus to change the terminal assignments Info button directs you to the appropriate section in Appendix A of the manual. Map each device to any 1, 2, or 3 Safety Outputs Advanced settings are dependent on device type (e.g., debounce time settings)

Figure 39. Safety Input Device Properties screen www.bannerengineering.com - Tel: 763.544.3164

53

Page 54

SC22-3/-3E Safety Controller Instruction Manual

Figure 40. Wiring diagram populates with devices and output mapping

Figure 41. Ladder logic diagram develops along with wiring diagram

Finish the Configuration Repeat the steps in the previous section to include additional safety or non-safety input devices. Select Safety Outputs or Status Outputs from the tool bar to configure properties for these outputs, using the same menu-driven process as that for the inputs. Safety Output Properties, assigned individually for each Safety Output. Select the output to be configured from the drop-down menu in the top field of the screen, and type in or select: • •

Name Delay type and duration

Status Output Properties, assigned individually for each Status Output. Select the output to be configured from the drop-down menu in the top field of the screen, and type in or select: • • • •

54

Name Function Source (depending on function selected) Signal convention (depending on function selected)

www.bannerengineering.com - Tel: 763.544.3164

Page 55

SC22-3/-3E Safety Controller Instruction Manual

Save and Confirm the Configuration You will need to confirm this new configuration before it can be used in a safeguarding application. A 4-digit Controller password is required to save and confirm a configuration and to enable it to run on a Safety Controller. The confirmation process has two parts: 1. Code validation: The microcontrollers in the Safety Controller receive and check a copy of the configuration to be sure that all safety-critical settings are appropriate (all device settings, control relationships, logic functions and other parameters are valid). 2. Configuration verification: When the validation step is complete, the Controller saves the configuration to the internal non-volatile memory, reads it back from memory, and sends a copy of the stored file back to the PCI for a manual content verification that the user performs. To confirm a configuration: 1. Save the configuration file to the PC: a. Go to File > Save. b. Name the configuration file and select a file location on your computer. c. Click Save. 2. Connect the Safety Controller to the PC using the USB cable (see section USB Connections on page 11). 3. Apply 24V dc power to the Controller. When the powered Controller is properly connected with the computer, the Receive, Send and Confirm buttons in the screen’s tool bar become active and convert from gray scale to color.

4. Click Confirm in the tool bar. A message asking if you want to save a copy of the Controller’s existing configuration will appear. The Controller used for the confirmation process may already have a user-defined configuration. Any configuration already loaded in the Controller will be overwritten during the confirmation process. It is the user’s responsibility to save the existing configuration, if needed. • Select Yes to save the configuration and to proceed to overwrite the Controller’s existing configuration. • Configure EDM, if desired. • Enter the password (the factory default is 0000) on the Confirm Configuration pop-up menu. • Click OK. • A pop-up warning message will ask if you want to continue; select Yes. The configuration validation process takes a few seconds and when complete, the Verification screen appears.

Figure 42. Verification screen, no devices yet confirmed by user

5. If the columns match, and no changes need to be made: • Verify that the properties in the right-hand column match those in the left-hand column. For each device, as you determine that its properties are correct, either click on Confirm or click in the corresponding checkbox. A check mark will appear in the box, and the section will compress to a list, as shown below.

www.bannerengineering.com - Tel: 763.544.3164

55

Page 56

SC22-3/-3E Safety Controller Instruction Manual

Figure 43. Confirm Configuration screen, all devices confirmed by user (checklist is compressed)

If the columns do not match, or if you wish to change any circuit: ◦ Select Edit for the device to be changed. ◦ The Properties menu for the device will open. ◦ Make the necessary change(s). ◦ Select OK. A message will appear asking whether you want to edit any other devices or if you want to restart the confirmation process.If any device properties are changed while in the manual verification stage of the confirmation, the Controller will proceed to re-validate the code. If the columns match, and no changes need to be made: • • •

Select Confirm for each device. The verification screen shows the summary that is created after each property has been verified. If you need to review a confirmed device property, un-check the checkbox and the Device Properties window will reappear. Edits may then be performed, as necessary. 6. When you are through with the manual verification, click OK. 7. When the verification process is complete, the Confirm Configuration summary screen is displayed. Select Close and perform a system reset; see section System Reset on page 56. 8. The Controller will activate the new configuration and will function according to the new parameters.

System Reset The Controller requires a system reset under certain conditions: • To place the Controller into Run mode after it has been configured. • To recover from certain conditions (for example, lockouts). To perform a system reset, either provide a 24V dc signal on the System Reset input (located next to the Status Output O10 terminal), or cycle power. When the configuration is successfully confirmed, the Controller will switch to Run mode.

5.1.3 Revise an Existing Configuration

When the software program opens, go to File > Open or click the icon to browse for the configuration to be changed. Make changes as described in section Build a Configuration on page 51.

5.1.4 Other Functions Receive a Configuration from the Safety Controller To receive a configuration from a Controller and display it in the PCI: 1. Connect the Safety Controller to the PC using the USB cable. 2. Apply 24V dc power to the Controller. 56 www.bannerengineering.com - Tel: 763.544.3164

Page 57

SC22-3/-3E Safety Controller Instruction Manual

3. Click Receive in the tool bar. 4. If the configuration is not already confirmed, you may choose to confirm it at this time.

Send a Configuration to the Safety Controller To send a configuration from the PCI to a Controller: 1. Connect the Safety Controller to the PC, using the USB cable. 2. Apply 24V dc power to the Controller. 3. Click Send in the tool bar.

Open a Configuration from the XM Card Both confirmed and unconfirmed configurations can be sent to or received from the XM card. To open a copy of a configuration from the XM card and display it in the PCI: 1. Connect the SC-XMP programming tool to the PC using the USB cable. 2. Insert the XM card into the programming tool. 3. Go to File > Open From XM Card in the upper-left corner of the screen. A message appears when the operation is complete.

Send a Configuration to the XM Card Both confirmed and unconfirmed configurations can be sent to or received from the XM card. To send a copy of a configuration from the PCI to the XM card (via the programming tool): 1. Connect the SC-XMP programming tool to the PC using the USB cable. 2. Insert the XM card into the programming tool. 3. Select Open Folder in the tool bar and open the intended configuration file. 4. Go to File > Send To XM Card in the upper-left corner of the screen. A message appears when the operation is complete.

Lock the XM Card It is important to note that this operation cannot be undone. Once the card is locked, another configuration can never be stored on it. This operation is useful when the XM card and its configuration will be transported to another Controller, or for storing and archiving a configuration. To lock the XM card so that the stored configuration cannot be changed: 1. Insert the XM card into the SC-XMP programming tool. 2. Verify that the correct file is stored on the XM card. 3. Go to File > Lock XM Card in the upper left of the tool bar. A message appears when the operation is complete.

Changing the Password Using the Personal Computer Interface (PCI) For this procedure, the PC must be connected to the Controller via USB cable, and the Controller must be ON. 1. Go to File > Change Safety Controller Password. The Change Password screen appears. 2. Fill in the boxes for Safety Controller password, new password, and new password again. Click OK. The Entering Configuration Mode screen appears with the message, “Are you sure you want to do this? All Safety Outputs will be turned off.” (If you click Yes, all Safety Outputs will turn OFF, along with the machine or system the Safety Controller is monitoring.) 3. Click Yes. The Change Password screen reappears. 4. Click Close. The password is changed. Record the password for safekeeping.

Figure 44. Change Password screen www.bannerengineering.com - Tel: 763.544.3164

57

Page 58

SC22-3/-3E Safety Controller Instruction Manual

NOTE: If the password becomes lost, contact Banner Engineering for assistance.

Export Documents Configuration notes can be exported in different formats. To export a configuration document: 1. Open the configuration file that you want to save. 2. Go to File > Export in the upper left of the tool bar. 3. Select the configuration document you want to export. 4. Verify that the File name is correct and pick the Save as type file option you need. 5. Select Save.

Figure 45. Save As screen

Print Options To print a configuration file: 1. 2. 3. 4.

58

Open the configuration file that you want to print. Go to File > Print in the upper left of the tool bar. Select the configuration document you want to print. A Page Setup menu will appear. Make the page and printer choices and click OK. (Hint: Wiring diagrams typically fit the page better when “landscape” is selected; the other documents fit better on “portrait.”)

www.bannerengineering.com - Tel: 763.544.3164