Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Beckhoff KL1184 Tech Manual

Manual · Beckhoff

Beckhoff KL1184 Tech Manual

Manual1 pagePDF 44 KB

The page is below, with its text.

Download the PDF44 KB

Covers · 1 model

The models it covers

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

One-page Beckhoff data sheet for the KL1184 and KL1194 4-channel 24 V DC digital input Bus Terminals that switch to negative potential. It gives the technical data, the contact layout and the 2-wire and 3-wire sensor connection, and notes that the two versions differ in input filter speed.

What it is
4-channel digital input Bus Terminal, 24 V DC, for sensors that switch to 0 V (ground) p. 1
Nominal voltage
24 V DC (-15 %/+20 %) p. 1
Signal levels
"0" signal 18…30 V; "1" signal 0…7 V p. 1
Input filter
KL1184: 3.0 ms; KL1194: 0.2 ms p. 1
Input current
typ. 5 mA p. 1
Operating temperature
0…+55 °C operating, -25…+85 °C storage; 95 % relative humidity, no condensation p. 1
Electrical isolation
500 Vrms (K-bus/field potential) p. 1
K-bus current
typ. 8 mA p. 1
Process image
4 inputs; no address or configuration setting p. 1
Sensor wiring
2-wire or 3-wire, with +24 V and 0 V power contacts p. 1
Indicators
One signal LED per channel p. 1
Protection class
IP 20, variable installation position p. 1
Weight
approx. 55 g p. 1
Pluggable version
KS1184 with pluggable wiring p. 1

What this manual walks you through

  • Connecting 2-wire and 3-wire sensors to the terminal p. 1
  • Reading the four signal LEDs p. 1

Questions this manual answers

What is the difference between the KL1184 and KL1194?

They differ in input filter speed: the KL1184 filters at 3.0 ms and the KL1194 at 0.2 ms. p. 1

What kind of sensors can be connected to the KL1184?

Sensors that switch to 0 V (ground); the inputs switch to negative potential. p. 1

What voltage counts as an on signal for the KL1184?

A "1" signal is 0 to 7 V and a "0" signal is 18 to 30 V. p. 1

Does the KL1184 need any address or configuration setting?

No; it maps 4 inputs into the process image with no address or configuration setting. p. 1

The file

Size and text

Pages1
PDF44 KB
TextText from the PDF itself.

Every page · 1

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Beckhoff KL1184 Tech Manual

The text of page 1, from the PDF itself

Digital Input

KL1184, KL1194

Signal LED1 Signal LED3

Signal LED2 Signal LED4

Input 1Input 2 152637+24 VPower contact +24 V0VPower contact 0 VnegativeInput 3Input 4 482-wireBus TerminalTop view482Contact assembly3-wireConnection

KL1184, KL1194 | 4-channel digital input terminals 24 V DC, switching to negative potential The KL1184 and KL1194 digital input terminals acquire the binary control signals from the process level and transmit them, in an electrically isolated form, to the higher-level automation unit. The KL1184 and KL1194 versions have input filters of different speeds. Sensors that switch to 0 V (ground) can be connected to the KL1184 and KL1194 versions. The Bus Terminals contain four channels that indicate their signal state by means of light emitting diodes.

Technical dataKL1184 | KS1184Number of inputs4Nominal voltage24 V DC (-15 %/+20 %)“0“ signal voltage18…30 V“1“ signal voltage0…7 VInput filter3.0 msInput currenttyp. 5 mA

Current consumption K-bus

typ. 8 mA

Electrical isolation

500 Vrms (K-bus/field potential)

Bit width in the process image

4 inputs

Configuration

no address or configuration setting

Weight

approx. 55 g

Operating/storage temperature

0…+55 °C/-25…+85 °CRelative humidity95 %, no condensation

Vibration/shock resistance

conforms to EN 60068-2-6/EN 60068-2-27/29

EMC immunity/emission

conforms to EN 61000-6-2/EN 61000-6-4

Protect. class/installation pos.

IP 20/variable

Pluggable wiring

for all KSxxxx Bus Terminals

Further information

www.beckhoff.com/KL1184

BECKHOFF New Automation Technology

KL1194 | KS1194

0.2 ms

We reserve the right to make technical changes.