One-page Beckhoff data sheet for the KL1184 and KL1194 4-channel 24 V DC digital input Bus Terminals that switch to negative potential. It gives the technical data, the contact layout and the 2-wire and 3-wire sensor connection, and notes that the two versions differ in input filter speed.
- What it is
- 4-channel digital input Bus Terminal, 24 V DC, for sensors that switch to 0 V (ground) p. 1
- Nominal voltage
- 24 V DC (-15 %/+20 %) p. 1
- Signal levels
- "0" signal 18…30 V; "1" signal 0…7 V p. 1
- Input filter
- KL1184: 3.0 ms; KL1194: 0.2 ms p. 1
- Input current
- typ. 5 mA p. 1
- Operating temperature
- 0…+55 °C operating, -25…+85 °C storage; 95 % relative humidity, no condensation p. 1
- Electrical isolation
- 500 Vrms (K-bus/field potential) p. 1
- K-bus current
- typ. 8 mA p. 1
- Process image
- 4 inputs; no address or configuration setting p. 1
- Sensor wiring
- 2-wire or 3-wire, with +24 V and 0 V power contacts p. 1
- Indicators
- One signal LED per channel p. 1
- Protection class
- IP 20, variable installation position p. 1
- Weight
- approx. 55 g p. 1
- Pluggable version
- KS1184 with pluggable wiring p. 1
What this manual walks you through
Questions this manual answers
What is the difference between the KL1184 and KL1194?
They differ in input filter speed: the KL1184 filters at 3.0 ms and the KL1194 at 0.2 ms. p. 1
What kind of sensors can be connected to the KL1184?
Sensors that switch to 0 V (ground); the inputs switch to negative potential. p. 1
What voltage counts as an on signal for the KL1184?
A "1" signal is 0 to 7 V and a "0" signal is 18 to 30 V. p. 1
Does the KL1184 need any address or configuration setting?
No; it maps 4 inputs into the process image with no address or configuration setting. p. 1
The file
Size and text
Every page · 1
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 1
Open in the PDF
The text of page 1, from the PDF itself
Digital Input
KL1184, KL1194
Signal LED1 Signal LED3
Signal LED2 Signal LED4
Input 1Input 2 152637+24 VPower contact +24 V0VPower contact 0 VnegativeInput 3Input 4 482-wireBus TerminalTop view482Contact assembly3-wireConnection
KL1184, KL1194 | 4-channel digital input terminals 24 V DC, switching to negative potential The KL1184 and KL1194 digital input terminals acquire the binary control signals from the process level and transmit them, in an electrically isolated form, to the higher-level automation unit. The KL1184 and KL1194 versions have input filters of different speeds. Sensors that switch to 0 V (ground) can be connected to the KL1184 and KL1194 versions. The Bus Terminals contain four channels that indicate their signal state by means of light emitting diodes.
Technical dataKL1184 | KS1184Number of inputs4Nominal voltage24 V DC (-15 %/+20 %)“0“ signal voltage18…30 V“1“ signal voltage0…7 VInput filter3.0 msInput currenttyp. 5 mA
Current consumption K-bus
typ. 8 mA
Electrical isolation
500 Vrms (K-bus/field potential)
Bit width in the process image
4 inputs
Configuration
no address or configuration setting
Weight
approx. 55 g
Operating/storage temperature
0…+55 °C/-25…+85 °CRelative humidity95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Pluggable wiring
for all KSxxxx Bus Terminals
Further information
www.beckhoff.com/KL1184
BECKHOFF New Automation Technology
KL1194 | KS1194
0.2 ms
We reserve the right to make technical changes.