Manual · Beckhoff
Bus Terminal: The modular fieldbus system for automation
Manual156 pagesPDF 9.3 MB
Beckhoff catalog chapter on the Bus Terminal I/O system: Bus Couplers, controllers and terminals such as the KL1184, KL2022 and KL2184.
What this file really is
The old site listed this file as “Beckoff PLC Overview Manual” for the Beckhoff KL1184, KL2022 and KL2184. This is not a PLC overview manual but the Bus Terminal chapter of a Beckhoff product catalog.
Filed under · 3 models
Filed under these models in the old catalog
Summary
What is in it
The Bus Terminal chapter of a Beckhoff product catalog. It gives a system overview and product overview tables, describes the fieldbus-neutral Bus Terminal I/O system and its features and technical data, then presents Bus Couplers for many fieldbuses, Bus Terminal Controllers, and digital, analog, safety, special function and system terminals with accessories. Product pages include the KL1184 digital input terminal and the KL2022 and KL2184 digital output terminals.
Its parts
- System overview
- Product overview
- System description
- Features
- Technical data
- Bus Couplers
- Bus Terminal Controllers
- Bus Terminals digital I/O
- Safety terminals
- Bus Terminals analog I/O
- Bus Terminals special functions
- System terminals
- Special terminals
- Accessories
From the manual
Key facts from this manual
Each line names its page in the PDF.
Beckhoff catalog section on the Bus Terminal modular fieldbus I/O system, covering Bus Couplers, Bus Terminal Controllers and the digital, analog and special-function Bus Terminals of the KL and KS series. For the KL1184, KL2022 and KL2184 it gives short descriptions and technical data tables beside their sister terminals. It helps a reader pick a coupler for a fieldbus and match terminals to signal types.
- What it is
- Catalog of the Bus Terminal modular fieldbus system: Bus Couplers, Bus Terminal Controllers and Bus Terminals p. 2, 3
- Nominal voltage
- KL1184, KL2022 and KL2184: 24 V DC (-15 %/+20 %) p. 63, 76, 79
- Operating temperature
- KL1184, KL2022 and KL2184: 0…+55 °C p. 63, 76, 79
- KL1184 inputs
- KL1184: 24 V DC digital input terminal for negative switching sensors, input filter 3.0 ms p. 9, 63
- KL2184 outputs
- KL2184: four negative switching outputs, 0.5 A per channel (short-circuit-proof), with 24 V DC and 0 V for each channel p. 11, 79
- KL2184 protection
- KL2184: breaking energy < 100 mJ/channel, reverse voltage protection, short circuit current <7A p. 79
- KL2022 outputs
- KL2022: 24 V DC digital output terminal that switches actuators electrically isolated p. 76
- Station size
- Up to 64 Bus Terminals on one Bus Coupler, 255 with K-bus extension KL9020 and KL9050 p. 18
- Mounting
- 35 mm DIN rail conforming to EN 50022, side by side by double slot and key p. 28
- Power contacts
- Up to three per Bus Terminal, IMAX 10 A (125 A short-circuit) p. 28
- Fieldbuses
- Bus Couplers for EtherCAT, Lightbus, PROFIBUS, Interbus, CANopen, DeviceNet, ControlNet, Modbus, Fipio, CC-Link, SERCOS, RS232/RS485, Ethernet TCP/IP, Ethernet/IP, PROFINET and USB p. 17
- Bus Coupler supply
- 24 V DC on the Bus Coupler spring-loaded terminals p. 27
- EMC and vibration
- EMC per EN 61000-6-2/EN 61000-6-4; vibration and shock per EN 60068-2-6/EN 60068-2-27/29 p. 28
- Software
- I/O stations configured with the TwinCAT System Manager p. 18
What this manual walks you through
- Choosing a Bus Coupler for a given fieldbus p. 7, 17
- Comparing Bus Coupler and Bus Terminal Controller features p. 5, 6
- Finding a digital input terminal by signal and filter time p. 9
- Finding a digital output terminal by signal and current p. 11
- Technical data of negative switching digital input terminals p. 63
- Technical data of negative switching digital output terminals p. 79
- Housing, wiring and mounting data for couplers and terminals p. 27, 28
Good to know
- A change of voltage along the terminal row must always start with a power feed terminal. p. 28
- If the power contacts need a voltage other than the coupler's, a power feed terminal goes after the Bus Coupler. p. 27
Questions this manual answers
What voltage do the KL1184 and KL2184 terminals run on?
What kind of sensors can be wired to a KL1184?
Negative switching sensors; the catalog lists it with a 3.0 ms input filter. p. 9, 63
How many Bus Terminals can one Beckhoff Bus Coupler run?
Up to 64, or up to 255 with the K-bus extension KL9020 and KL9050. p. 18
How are Beckhoff Bus Terminals mounted?
They latch side by side on a 35 mm DIN rail conforming to EN 50022. p. 28
The whole text · 16 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 101-10
- Pages 11 to 2011-20
- Pages 21 to 3021-30
- Pages 31 to 4031-40
- Pages 41 to 5041-50
- Pages 51 to 6051-60
- Pages 61 to 7061-70
- Pages 71 to 8071-80
- Pages 81 to 9081-90
- Pages 91 to 10091-100
- Pages 101 to 110101-110
- Pages 111 to 120111-120
- Pages 121 to 130121-130
- Pages 131 to 140131-140
- Pages 141 to 150141-150
- Pages 151 to 156151-156
The file