Bus Terminal: The modular fieldbus system for automation, pages 31 to 40

Pages 31 to 40 of 156

The original document is the PDF (9.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Beckhoff KL1184, Beckhoff KL2022 and Beckhoff KL2184

Page 31

BKxxxx | Bus Couplers The interface between fieldbus and terminals

Bus Terminal

Power LEDs

Bus Coupler supply

490

Fieldbus connection

K-bus

Power contacts Address selector Configuration interface

Input for power contacts

For further information on the individual fieldbuses see page 242

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 32

Economy | BKxx10

The Bus Couplers link the modularly expandable electronic terminal blocks with the respective fieldbus systems. The Bus Coupler performs all the monitoring and control tasks that are necessary for operation of the connected Bus Terminals. The specific settings of analog and multifunctional Bus Terminals are adapted to the application via the KS2000 configuration software. In the standard Bus Couplers a unit consists of a Bus Coupler, any number of up to 64 terminals and a bus end terminal. The “Economy” versions enable particularly cost-effective configuration of peripheral interfacing connections with up to 64 digital input/output terminals.

Economy plus | BKxx20

Compact | BKxx50

In addition to digital signal types, the “Economy plus” Bus Couplers also support all other types. Up to 255 Bus Terminals can be connected via the K-bus extension. The “Compact” Bus Couplers have a particularly compact housing and also enable connection of up to 255 Bus Terminals via the terminal bus extension. The “Low Cost” Bus Couplers are characterised by small dimensions and costeffective connection technology and enable connection of up to 64 digital input/output terminals.

Low Cost | LCxx00

The Bus Terminal system has stood the test of time in machine or building automation applications where a temperature range of 0 to 55 °C is sufficient. For requirements beyond that, the operating temperature range of selected standard Bus Terminals and Couplers has been extended to -20 to +60 °C. The storage temperature of these ET components (Extended Temperature Range) has also been adapted and is now -40 to +85 °C. The exact definition of the operating conditions in temperature ranges outside 0 to 55 °C, installation requirements that possibly deviate from the standard and, if applicable, deviating technical data can be found in the documentation. Bus Couplers that have been qualified for the extended temperature range are identified accordingly. +60 °C -20 °C

Technical data

BKxxxx, LCxxxx

Power supply

24 V DC (-15 %/+20 %)

Operating/storage temperature

0…+55 °C/-25…+85 °C (extended temperature range: -20…+60 °C/-40…+85 °C)

Relative humidity

95 %, no condensation

Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29

EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4

Protect. class/installation pos.

IP 20/variable www. beckhoff.com/Bus-Coupler We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Bus Terminal

Standard | BKxx00

491

Page 33

EtherCAT

BK1120, BK1250

Bus Terminal

EtherCAT | Bus Coupler

492

The EtherCAT BK1120 “Economy plus” Bus Coupler is used for connection of different Bus Terminals to the EtherCAT fieldbus system. EtherCAT enables the Ethernet star topology to be replaced with a simple line structure. The upper Ethernet interface of the BK1120 is the network connection. The lower RJ 45 socket can be used for connecting further EtherCAT devices to the same strand. The BK1250 “Compact” Coupler enables mixed application of EtherCAT Terminals (ELxxxx) and standard Bus Terminals (KLxxxx) in a bus station. The “Bus Coupler in terminal housing” integrates the Bus Terminals directly into the EtherCAT terminal strand, thereby enabling compact control solutions. The wide range of Bus Terminal products can thus be optimally combined with the communication speed and the large choice of EtherCAT Terminals. The EtherCAT Terminals are connected via suitable EtherCAT couplers of EKxxxx type (see page 316 ).

EtherCAT “Economy plus”

“Compact” coupler

Bus Coupler for up to between E-bus and K-bus

64 Bus Terminals

Terminals

(255 with K-bus extension) Technical data

BK1120

BK1250

Number of Bus Terminals

64 (255 with K-bus extension)

Max. number of bytes

1,024 byte input and 1,024 byte output fieldbus Current supply K-bus

1,750 mA

500 mA +60 °C -20 °C

The BK1120 Bus Coupler connects EtherCAT, the realtime Ethernet system, with the modular, extendable electronic terminal blocks. A unit consists of a Bus Coupler, any number (between 1 and 64) of terminals (255 with K-bus extension) and one end terminal.

The BK1250 is a “Bus Coupler in terminal housing” for mixed application of EtherCAT Terminals (ELxxxx) and standard Bus Terminals (KLxxxx) in a bus station. Up to 64 Bus Terminals (with K-bus extension up to 255) can be connected to a BK1250.

Bus interface

2 x RJ 45

E-bus contacts on the left/

Data transfer rates

100 Mbaud

100 Mbaud

Weight approx. 150 g approx. 55 g

Operating temperature

-20…+60 °C

0…+55 °C

Approvals

CE, UL, Ex

CE, UL, Ex

Further information www.beckhoff.com/BK1120 www.beckhoff.com/BK1250

K-bus contacts on the right

Accessories

BECKHOFF New Automation Technology

Cordsets and connectors see page

608 see page

608

PC Fieldbus Cards

FC90xx

706

FC90xx

706

We reserve the right to make technical changes.

Page 34

BK20xx

Lightbus

Lightbus | Bus Coupler

Lightbus Bus Coupler

Lightbus Bus Coupler

Lightbus “Economy plus” for up to 64 Bus Terminals for up to 64 digital

Bus Coupler for up to

Bus Terminals

64 Bus Terminals (255 with K-bus extension)

Technical data

BK2000

BK2010

BK2020

Number of Bus Terminals

64

Max. number of bytes

512 byte input and 512 byte output

32 byte input and 32 byte output

512 byte input and 512 byte output

1,750 mA

500 mA

1,750 mA

64 (255 with K-bus extension)

fieldbus

Bus Terminal

Current supply K-bus

493

The BK2000 Bus Coupler connects the Lightbus system to the electronic terminal blocks, which can be expanded in modular fashion. One unit consists of one Bus Coupler, any number of up to 64 terminals and one end terminal.

The BK2010 „Economy“ variant permits particularly economical creation of peripheral interfacing connections. Up to 64 digital input/output terminals can be connected. –

– distance between stations: 45 m for APF fibre, 300 m HCS fibre distance between stations: 45 m for APF fibre, 300 m HCS fibre

With the K-bus extension technology, the “Economy plus” Bus Coupler BK2020 allows the connection of up to 255 spatially distributed Bus Terminals to one Bus Coupler. The “Economy plus” series supports all Beckhoff system Bus Terminals. It can process in its full configuration 1,020 digital signals and a maximum of 128 analog input and output channels per slave. –

Bus interface distance between stations: 45 m for APF fibre, 300 m HCS fibre

2 x standard fibre optic connector Z1000

2 x standard fibre optic connector Z1000

2 x standard fibre optic connector Z1000

(plastic fibre), Z1010 (HCS fibre)

(plastic fibre), Z1010 (HCS fibre)

(plastic fibre), Z1010 (HCS fibre)

Data transfer rates

2.5 Mbaud

2.5 Mbaud

2.5 Mbaud

Weight approx. 150 g approx. 130 g approx. 150 g

Operating temperature

0…+55 °C

0…+55 °C

0…+55 °C

Approvals

CE, UL, Ex

CE, UL, Ex

CE, UL, Ex

Further information www.beckhoff.com/BK2000 www.beckhoff.com/BK2010 www.beckhoff.com/BK2020

Accessories Cordsets and connectors see page

608 see page

608 see page

608

PC Fieldbus Cards

FC200x

701

FC200x

701

FC200x

701

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Page 35

PROFIBUS

BK3010, BK31xx

PROFIBUS | Bus Coupler

PROFIBUS Bus Coupler

PROFIBUS DP/FMS Bus Coupler

PROFIBUS Bus Coupler for up to 64 digital Bus Terminals, for up to 64 Bus Terminals, for up to 64 digital Bus Terminals,

1.5 Mbaud

12 Mbaud

12 Mbaud

Technical data

BK3010

BK3100

BK3110

Number of Bus Terminals

64

Max. number of bytes

64 byte input and

64 byte input and 64 byte output

64 byte input and fieldbus

64 byte output

(DP and FMS mode), 128 byte input

64 byte output and 128 byte output (only DP mode) 500 mA

1,750 mA

500 mA

The BK3010 „Economy“ variant permits particularly economical creation of peripheral interfacing connections. Up to 64 digital input/output terminals can be connected.

The BK3100 Bus Coupler connects the PROFIBUS system to the electronic terminal blocks, which can be extended in modular fashion. One unit consists of the Bus Coupler, any number of up to 64 terminals and one end terminal.

The BK3110 „Economy“ variant permits particularly economical creation of peripheral interfacing connections. Up to 64 digital input/output terminals can be connected.

Bus interface

1 x D-sub 9-pin socket with shielding

1 x D-sub 9-pin socket with shielding

1 x D-sub 9-pin socket with shielding

Data transfer rates automatic detection

12 Mbaud

12 Mbaud

Bus Terminal

Current supply K-bus

494 up to max. 1.5 Mbaud Weight approx. 150 g approx. 170 g approx. 150 g

Operating temperature

0…+55 °C

0…+55 °C

0…+55 °C

Approvals

CE, UL, Ex, GL

CE, UL, Ex, GL

CE, UL, Ex, GL

Further information www.beckhoff.com/BK3010 www.beckhoff.com/BK3100 www.beckhoff.com/BK3110

Accessories Cordsets and connectors see page

608 see page

608 see page

608

PC Fieldbus Cards

FC310x

702

FC310x

702

FC310x

702

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 36

BK3xxx, LC3100

PROFIBUS

PROFIBUS “Economy plus”

PROFIBUS “Compact”

PROFIBUS Bus Coupler

PROFIBUS “Economy plus”

PROFIBUS “Low Cost”

Bus Coupler for up to 64 Bus

Bus Coupler for up to 64 Bus with fibre optic connection

Bus Coupler for up to 64 Bus

Bus Coupler for up to

Terminals (255 with K-bus

Terminals (255 with K-bus for up to 64 Bus Terminals,

Terminals (255 with K-bus

64 digital Bus Terminals, extension), 12 Mbaud extension), 12 Mbaud

1.5 Mbaud extension), 12 Mbaud

12 Mbaud

BK3120

BK3150

BK3500

BK3520

LC3100

64

64 (255 with

64

64 (255 with K-bus extension)

K-bus extension)

128 byte input and

64 byte input and

128 byte output

64 byte output

1,750 mA

1,000 mA

1,750 mA +60 °C

-20 °C

-20 °C

500 mA

Bus Terminal

+60 °C

1,750 mA

495

The “Economy plus“ version extends the existing PROFIBUS Bus Coupler series BK3xx0. The K-bus extension technology allows the connection of up to 255 spatially distributed Bus Terminals to one Bus Coupler.

The “Compact” Bus Coupler BK3150 for PROFIBUS extends the Beckhoff Bus Terminal system by a cost-optimised version in a compact housing.

The particular feature of the BK3500 Bus Coupler is its fibre optic connection. The fibre optics mean that the transmission is particularly safe from interference and has absolute electrical isolation. –

The particular feature for the BK3520 Bus Coupler is its fibre optic connection and its high transmission rate of up to 12 Mbaud. –

The LC3100 “Low Cost” Bus Coupler is marked by a smaller design and a more economical connection method.

distance between stations: up to 40 m distance between stations: up to 25 m

1 x D-sub 9-pin socket

1 x D-sub 9-pin socket

2 x HP-Simplex sockets

4 x HP-Simplex sockets connection via with shielding with shielding

(HP-Simplex plugs included)

(HP-Simplex plugs ZS1031-

Bus Terminal

3500 included) automatic detection automatic detection automatic detection automatic detection up to 12 Mbaud up to 12 Mbaud up to max. 1.5 Mbaud up to 12 Mbaud approx. 170 g approx. 100 g approx. 170 g approx. 170 g approx. 100 g

-20…+60 °C

-20…+60 °C

0…+55 °C

0…+55 °C

0…+55 °C

CE, UL, Ex, GL

CE, UL, Ex

CE, UL, Ex

CE, UL, Ex

CE, UL, Ex www.beckhoff.com/BK3120 www.beckhoff.com/BK3150 www.beckhoff.com/BK3500 www.beckhoff.com/BK3520 www.beckhoff.com/LC3100 see page

608 see page

608 see page

608 see page

608 see page

608

FC310x

702

FC310x

702

FC310x

702

FC310x

702

FC310x

702

We reserve the right to make technical changes.

up to 12 Mbaud

BECKHOFF New Automation Technology

Page 37

Interbus

BK40xx

Interbus, CANopen | Bus Coupler

Interbus Bus Coupler

Interbus Bus Coupler

Interbus “Economy plus” Bus Coupler for up to 64 Bus Terminals for up to 64 digital Bus Terminals for up to 64 Bus Terminals (255 with K-bus extension)

Technical data

BK4000

BK4010

BK4020

Number of Bus Terminals

64

Max. number of bytes

64 byte input and 64 byte output

8 byte input and 8 bytes output

64 byte input and 64 byte output

1,750 mA

500 mA

1,750 mA

The BK4000 Bus Coupler connects the Interbus bus system to the electronic terminal blocks, which can be extended in modular fashion. One unit consists of one Bus Coupler, any number of up to 64 terminals and one end terminal.

The BK4010 „Economy“ variant permits particularly economical creation of peripheral interfacing connections. Up to 64 digital input/output terminals can be connected.

With the K-bus extension technology, the “Economy plus” Bus Coupler BK4020 allows the connection of up to 255 spatially distributed Bus Terminals to one Bus Coupler. The “Economy plus” coupler supports all Beckhoff system Bus Terminals and can process 512 bit digital inputs and outputs per slave.

2 x D-sub plug, 9-pin, plug and socket

2 x D-sub plug, 9-pin, plug and socket

2 x D-sub plug, 9-pin, plug and socket with screening and vibration lock with screening and vibration lock with screening and vibration lock

Data transfer rates

500 kbaud

500 kbaud

500 kbaud

Weight approx. 170 g approx. 150 g approx. 170 g

Operating temperature

0…+55 °C

0…+55 °C

0…+55 °C

Approvals

CE, UL, Ex

CE, UL, Ex

CE, UL, Ex

Further information www.beckhoff.com/BK4000 www.beckhoff.com/BK4010 www.beckhoff.com/BK4020

64 (255 with K-bus extension)

fieldbus

Bus Terminal

Current supply K-bus

496

Bus interface

Accessories Cordsets and connectors see page

PC Fieldbus Cards

–

BECKHOFF New Automation Technology

608 see page –

608 see page

608

–

We reserve the right to make technical changes.

Page 38

BK4500, BK51xx

Interbus, CANopen

Interbus Bus Coupler

CANopen Bus Coupler

CANopen “Economy plus”

CANopen “Compact” with fibre optic connection for up to 64 digital

Bus Coupler for up to

Bus Coupler for up to for up to 64 Bus Terminals

Bus Terminals

64 Bus Terminals

64 Bus Terminals

(255 with K-bus extension)

(255 with K-bus extension) BK5150

BK4500

BK5110

BK5120

64

64

64 (255 with K-bus extension)

5 Tx/Rx PDOs

16 Tx/Rx PDOs

500 mA

1,750 mA

1,750 mA

1,000 mA +60 °C

Bus Terminal

-20 °C

497

The particular feature for the BK4500 Bus Coupler is its fibre optic connection. Its functions correspond to those of the BK4000 Bus Coupler in relation to the Bus Terminals and the fieldbus properties. The fibre optics mean that the transmission is particularly safe from interference, and has absolute electrical isolation.

The BK5110 “Economy” variant permits particularly economical creation of peripheral interfacing connections. Up to 64 digital input/ output terminals can be connected.

With the K-bus extension technology, the “Economy plus” Bus Coupler BK5120 allows the connection of up to 255 spatially distributed Bus Terminals to one Bus Coupler. The Bus Coupler works on the CAN protocol basis as defined in ISO 11898.

The “Compact” Bus Coupler BK5150 for CANopen extends the Beckhoff Bus Terminal system by a cost-optimised version in a compact housing. Up to 64 Bus Terminals are supported; with the terminal bus extension, up to 255 Bus Terminals can be connected. The CANopen Bus Coupler offers automatic baud rate detection up to 1 Mbaud and two address selection switches for address assignment.

2 x 2 FSMA plugs

1 x open style connector, 5-pin,

1 x open style connector, 5-pin, open style connector, 5-pin included included

500 kbaud up to 1 Mbaud up to 1 Mbaud automatic detection up to 1 Mbaud approx. 170 g approx. 130 g approx. 150 g approx. 100 g

0…+55 °C

0…+55 °C

-20…+60 °C

0…+55 °C

CE, UL, Ex

CE, UL, Ex, GL

CE, UL, Ex, GL

CE, UL, Ex www.beckhoff.com/BK4500 www.beckhoff.com/BK5110 www.beckhoff.com/BK5120 www.beckhoff.com/BK5150 see page

608

–

We reserve the right to make technical changes.

see page

608 see page

608 see page

608

FC510x

703

FC510x

703

FC510x

703

BECKHOFF New Automation Technology

Page 39

CANopen, DeviceNet BK5xxx, LC5100

CANopen, DeviceNet | Bus Coupler

CANopen “Compact” Bus Coupler

CANopen “Low Cost” Bus Coupler

DeviceNet Bus Coupler for up to 64 Bus Terminals for up to 64 digital Bus Terminals for up to 64 Bus Terminals

(255 with K-bus extension)

(255 with K-bus extension)

Technical data

BK5151

LC5100

BK5200

Number of Bus Terminals

64 (255 with K-bus extension)

64 byte input and 64 byte output

64

Max. number of bytes

16 Tx/Rx PDOs

5 Tx/Rx PDOs

512 byte input and 512 byte output

1,000 mA

500 mA

1,750 mA

In contrast to the BK5150, the BK5151 has a 9-pin D-sub connector as a bus interface.

The LC5100 “Low Cost” Bus Coupler is marked by a smaller design and a more economical connection method. All the bit-oriented terminals can be connected to the LC5100. All the digital input and output terminals are supported with the exception of the KL15xx, KL25x2, KL2692 and KL27x1 terminals. All the system terminals, with and without diagnostics, can also be connected.

The BK5200 Bus Coupler connects the DeviceNet bus system to the electronic terminal blocks, which can be extended in modular fashion. One unit consists of one Bus Coupler, any number of up to 64 terminals and one end terminal.

Bus interface

D-sub 9-pin socket connection via Bus Terminal

1 x open pluggable connector, 5-pin,

Data transfer rates automatic detection up to 1 Mbaud up to 1 Mbaud automatic detection up to 500 kbaud

Weight approx. 100 g approx. 100 g approx. 150 g

Operating temperature

0…+55 °C

0…+55 °C

0…+55 °C

Approvals

CE, UL, Ex

CE, UL, Ex

CE, UL, Ex

Further information www.beckhoff.com/BK5151 www.beckhoff.com/LC5100 www.beckhoff.com/BK5200 fieldbus

Bus Terminal

Current supply K-bus

498 included

Accessories Cordsets and connectors see page

608 see page

608 see page

608

PC Fieldbus Cards

FC510x

703

FC510x

703

FC520x

704

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 40

BK52xx, LC5200

DeviceNet

DeviceNet Bus Coupler

DeviceNet “Economy plus” Bus

DeviceNet “Compact” Bus Coupler

DeviceNet “Low Cost” Bus Coupler for up to 64 digital Bus Terminals

Coupler for up to 64 Bus Terminals for up to 64 Bus Terminals for up to 64 digital Bus Terminals

(255 with K-bus extension)

(255 with K-bus extension)

(255 with K-bus extension)

BK5220

BK5250

LC5200

BK5210

64 (255 with K-bus extension)

64

32 byte input and 32 byte output

512 byte input and 512 byte output

32 byte input and 32 byte output

500 mA

1,750 mA

500 mA

Bus Terminal

1,000 mA

499

The BK5210 “Economy” variant permits particularly economical creation of peripheral interfacing connections. Up to 64 digital input/ output terminals can be connected.

With the K-bus extension technology, the “Economy plus” Bus Coupler BK5220 allows the connection of up to 255 spatially distributed Bus Terminals to one Bus Coupler. The “Economy plus” series supports all Beckhoff system Bus Terminals and it can process in its full configuration 1,020 digital signals and a maximum of 256 analog input and output channels per slave.

The “Compact” Bus Coupler BK5250 for DeviceNet extends the Beckhoff Bus Terminal system by a costoptimised version in a compact housing. The DeviceNet Bus Coupler offers automatic baud rate detection up to 500 kbaud and two address selection switches for address assignment. A 5-pin connector for the fieldbus connection is included in the scope of supply.

The LC5200 “Low Cost” Bus Coupler is marked by a smaller design and a more economical connection method. All the bit-oriented terminals can be connected to the LC5200. All the digital input and output terminals are supported with the exception of the KL15xx, KL25x2, KL2692 and KL27x1 terminals. All the system terminals, with and without diagnostics, can also be connected.

1 x open pluggable connector, 5-pin,

1 x open pluggable connector, 5-pin, open style connector, 5-pin connection via Bus Terminal included included automatic detection up to 500 kbaud automatic detection up to 500 kbaud automatic detection up to 500 kbaud automatic detection up to 500 kbaud approx. 130 g approx. 130 g approx. 100 g approx. 100 g

0…+55 °C

0…+55 °C

0…+55 °C

0…+55 °C

CE, UL, Ex, GL

CE, UL, Ex, GL

CE, UL, Ex

CE, UL, Ex www.beckhoff.com/BK5210 www.beckhoff.com/BK5220 www.beckhoff.com/BK5250 www.beckhoff.com/LC5200 see page

608 see page

608 see page

608 see page

608

FC520x

704

FC520x

704

FC520x

704

FC520x

704

We reserve the right to make technical changes.

BECKHOFF New Automation Technology