The text of a manual · part 3 of 16

Bus Terminal: The modular fieldbus system for automation, pages 21 to 30

Pages 21 to 30 of 156

The original document is the PDF (9.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Beckhoff KL1184, Beckhoff KL2022 and Beckhoff KL2184

Page 21

Bus Terminal features

Status LEDs for reliable and fast startup

Marking material for standard terminal blocks

Supply point for downstream inputs and outputs Detachable labelling fields for clear text labels

Power contacts connect the

Bus Terminal supply for sensors/actuators

480 automatically.

Supply point for Bus Couplers and downstream inputs and outputs

Bus Couplers represent a universal interface to the fieldbuses.

Terminal block design W x H x D (mm): 12 x 100 x 68

Assembly on 35 mm DIN mounting rail with no accessories

Ethernet TCP/IP

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 22

Screwless connection: using the reliable springloaded technique with vertical cable inlet

Master terminals enable the integration of subsystems such as AS-Interface. Contacts for data transmission and power supply to the K-bus vertical removal from terminal strip; release slide does not require a tool.

Bus Terminal

Symmetric release enables

481

Tongue and groove connection makes terminal strip structure secure and stable.

Fipio

Leading PE power contact

DALI

The 4-wire terminating system (signal, 24 V DC,

MP-Bus

0 V, PE) reduces assembly costs.

EIB We reserve the right to make technical changes.

LON BECKHOFF New Automation Technology

Page 23

Beckhoff Bus Terminals: The complete automation kit

Bus Coupler series BK, the link between Bus Terminals and fieldbus

The head station

Free mix of signals:

Potential feed of the Bus Terminals:

about 400 different terminals enable from Bus Coupler

Bus Terminals for configuration with fieldbus interface connection to all of different to Embedded PC common sensors potential groups.

Bus Terminal and actuators

Bus Terminal Controller series BC with integrated IEC 61131-3 PLC

482

Bus Terminals in

The terminal modules

1-, 2-, 4-, 8- and 16- with plug-in wiring channel modularity combine 16, 32 or 64 digital I/Os within a very small space and with high packing

Bus Terminal Controller series BX with integrated IEC 61131-3 PLC and extended interfaces density.

Embedded PC series CX for PLC and Motion Control applications

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 24

Integrated safety:

measurement capability the TwinSAFE Bus enables all relevant

Terminals enable electrical data of the the connection of all supply network to be common safety sensors measured.

and actuators.

Bus end terminal

The terminal bus extension enables the connection of up to 255 Bus Terminals (instead of 64) to a single station.

Bus Terminal

3-phase power

483

Bus Terminals with

Communication a maximum measure- terminals enable ment error of ±0.01% the integration of expand the range of subsystems such applications to high- as AS-Interface, precision measure-

RS232 and RS485.

ment technology.

The power terminal transforms a standard contactor into a motor protection relay with comprehensive diagnostic functions.

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Page 25

The coupler terminal KL9050 starts a further remote bus terminal block.

Via the K-bus extension, the Bus Coupler “Economy plus” enables the connection of up to 255 Bus Terminals.

Operation of up to 64 Bus Terminals

Operation of up to 64 Bus Terminals

Bus end terminal KL9010

K-bus extension via screened Industrial Ethernet cable with two RJ 45 plugs (distance up to 5 m)

Terminal bus extension, end terminal KL9020

Through the K-bus interconnection it is possible to connect a further 30 stations (total extension 155 m).

Bus Terminal

Terminal bus extension

484

The BKxxxx Bus Coupler links the bus systems to the modular, extendable electronic terminal blocks. One unit consists of one Bus Coupler, any number of terminals between 1 and 64, and a bus end terminal. The “Economy plus” and “Compact” series support all Bus Terminals of the Beckhoff system. It is also possible to operate up to 255 Bus Terminals on this Bus Coupler series with the K-bus extension. The Bus Terminal extension allows Bus Terminals to be located in up to 31 blocks in the control cabinet or in the application. With a distance of up to 5 m between the Bus Terminal blocks, the Bus Terminal system can be used over a wider area and helps save costs. The Bus Coupler recognises the terminals to which it is connected, and performs the assignment of the inputs and outputs to the bytes of the process image automatically. The blocks with terminal bus extensions are treated as one unit by the Bus Coupler. The extension is transparent for the fieldbus and higher-level systems. The system of Bus Coupler and Bus Terminal can be extended by replacing the end terminal KL9010 with the extension KL9020. The KL9020 makes available the K-bus signals in a RJ 45 socket for transmission onwards via a screened Industrial Ethernet cable. The coupler terminal KL9050 starts a further remote Bus Terminal block and provides the logical connection to the Bus Coupler via the Ethernet cable. 24 V DC, electrically isolated, for the field level can be input at this coupler terminal. The internal K-bus shares the same potential as the K-bus of the coupler. The KL9050 can be used via a second socket for the extension to the next Bus Terminal block. This Bus Terminal block starts in the same way as the one with a coupler terminal KL9050. This coupling works at up to 31 stations. The maximum distance between two Bus Terminal blocks is 5 m and allows a total extension of 155 m. The system uses screened Industrial Ethernet cables with two RJ 45 plugs for the transmission. The cable is supplied ready-made in different lengths or can be made-to-measure for applications with conventional Ethernet tools. Data transfer is based on the interference-free and RS485 industry standard in a double-screened cable.

Operation with up to 64 Bus Terminals to one

Operation with up to 255 Bus Terminals to one Bus Coupler with terminal bus extension

Bus Coupler with KL9010 bus end terminal end terminal KL9020 and coupler terminal KL9050

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 26

Certification: all TwinSAFE devices are subjected to a prototype test according to IEC 61508 and DIN EN ISO 13849-1:2008 PLe.

The TwinSAFE Bus Terminals enable the connection of all common safety sensors and actuators.

The KL2904 Safety Bus Terminal is a digital output terminal with four channels. The terminal switches 24 V DC actuators with up to 0.5 A total current.

The KL6904 TwinSAFE Logic Bus Terminal enables communication with up to 15 TwinSAFE devices. The Bus Terminal features certified safety blocks for functions such as emergency stop, safety door monitoring, etc. In addition, the TwinSAFE Logic Bus Terminal has four safe digital 24 V DC outputs.

The KL1904 digital input terminal for sensors with potential-free contacts for 24 V DC: the Safety Bus Terminal has 4 fail-safe inputs.

TwinSAFE | Safety and I/O technology in one system TwinSAFE – the safety solution from Beckhoff – integrates safety functionalities into the existing control architecture. TwinSAFE from Beckhoff provides a consistent hardware and software technology for achieving integrated and simplified handling, ranging from safe input and output terminals and safe miniature controllers for the Bus Terminal system and the AX5000 Servo Drives to the PCbased Safety PLC.

Input terminal KL1904

Bus Terminal

The following TwinSAFE Bus Terminals are available: – KL1904 | 4-channel digital input – KL2904 | 4-channel digital output – KL6904 | TwinSAFE Logic Bus Terminal with 4 digital outputs

485

For further information on TwinSAFE and the TwinSAFE products see page 828

K1

K3

K1

K2

K2

K4

K3

K4

Output terminal KL2904

Logic Terminal KL6904 TwinSAFE option card

EtherCAT

PROFIBUS

Open control technology for safety integration: the TwinSAFE protocol enables transfer of safety-relevant data via any medium.

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Page 27

46 mm 18 mm

100 mm

100 mm

100 mm

94 mm 100 mm

15 mm

43 mm

Bus Coupler Housing

47 mm

42 mm

49 mm

44 mm

BKxxxx, BCxxxx

BKxx50, BCxx50

81 mm

21 mm

BXxxxx

LCxxxx

Bus Terminal

Technical data – Bus Coupler housing The Beckhoff Bus Coupler electronics can be mounted in a variety of housings. A housing has three power contacts, which, if the application requires, automatically implement a continued connection, carrying the potential of the power circuit to the next Bus Terminal. The supply voltage that is connected to the Bus Coupler spring-loaded terminals is 24 V DC. If a different voltage is required for the power contacts, the appropriate power feed terminal must be inserted after the Bus Coupler.

486

Mechanical data

BKxxxx, BCxxxx

Design form compact terminal housing with signal LED

BKxx50, BCxx50

Material polycarbonate

Dimensions (W x H x D)

49 mm x 100 mm x 68 mm

44 mm x 100 mm x 68 mm

BXxxxx

LCxxxx

81 mm x 100 mm x 89 mm

21 mm x 100 mm x 68 mm

(BX8000: 61 mm x 100 mm x 89 mm) Installation on 35 mm DIN rail, conforming to EN 50022 with lock

Side by side mounting by double slot and key connection means of Marking standard terminal block marking

Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29

EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4

Connection

BKxxxx, BCxxxx

Wiring spring-loaded technique

Connection cross-section

0.08…2.5 mm², AWG 28-14, stranded wire, solid wire

Stripping length

8…9 mm

Fieldbus connection depending on fieldbus

Power contacts

3 spring contacts

Current load

IMAX: 10 A (125 A short-circuit)

Nominal voltage

24 V DC

BECKHOFF New Automation Technology

BKxx50, BCxx50 depending on fieldbus

BXxxxx

LCxxxx depending on fieldbus spring-loaded terminals

We reserve the right to make technical changes.

Page 28

100 mm

46 mm 18 mm

46 mm

100 mm

18 mm

100 mm

46 mm

18 mm

18 mm

46 mm

100 mm

100 mm

18 mm

46 mm

Bus Terminal Housing

12 mm

24 mm

12 mm

12 mm

12 mm

KLxxxx

KLxxxx

KSxxxx

KLx80x, KLx81x, KLx889

KL1862, KLx872

The Beckhoff Bus Terminal electronics can be mounted in a variety of housings. Bus Terminals are available with up to three power contacts, and can have a variety of voltages. Care should be taken to ensure that a change in voltage always starts with a power feed terminal.

Mechanical data Design form

KLxxxx

KL5101

KL5102

KSxxxx

KLx80x, KLx81x,

KL1862,

KLx889

KLx872 compact terminal compact terminal compact terminal terminal housing compact terminal compact terminal housing with housing with housing with with pluggable housing with housing with signal LED signal LED signal LED wiring level signal LED signal LED

Material polycarbonate

Dimensions (W x H x D)

12 mm x 100 mm

24 mm x 100 mm

24 mm x 100 mm

12/24 mm x

12 mm x 100 mm

12 mm x 100 mm x 68 mm x 68 mm x 68 mm

100 mm x 71 mm x 68 mm x 68 mm

– standard terminal

Installation on 35 mm DIN rail, conforming to EN 50022 with lock

Side by side mounting by double slot and key connection means of Marking standard terminal standard terminal standard terminal standard terminal block marking block marking block marking block marking

Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29

EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4

Connection

KLxxxx

KL5101 spring-loaded

KL5102 spring-loaded

KSxxxx block marking

KLx80x, KLx81x,

KL1862,

KLx889

KLx872 spring-loaded direct plug-in flat-ribbon cable connection

Wiring spring-loaded technique technique technique technique technique

Connection cross-section s, st*: 0.08… s, st*: 0.08… s, st*: 0.08… s, st*: 0.08… s*: 0.08…1.5 mm²; common flat-

2.5 mm²,

2.5 mm²,

2.5 mm²,

1.5 mm², st: 0.25…1.5 mm²; ribbon cables,

AWG 28-14

AWG 28-14

AWG 28-14

AWG 28-16 f: 0.14…0.75 mm² AWG 28, spacing

Stripping length

8…9 mm

8…9 mm

8…9 mm

9…10 mm

8…9 mm

–

Power contacts up to 3 blade/ none

2 blade/

2 blade/

2 blade/ none spring contacts spring contacts spring contacts

Current load

IMAX: 10 A (125 A short-circuit)

Nominal voltage depends on Bus Terminal type

1.27 mm spring contacts

*s: solid wire; st: stranded wire; f: ferrule We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Bus Terminal

Technical data – Bus Terminal housing

487

Page 29

46 mm 18 mm

100 mm

100 mm

18 mm

46 mm

KM Housing

24 mm

51 mm

73 mm

35 mm

26.5 mm

71 mm

75 mm

55 mm

KM10x4, KM20x4

KM10x2, KM20x2

Bus Terminal

Technical data – Terminal module housing The Beckhoff terminal modules with pluggable connection level are mounted in enclosures of different size. Like for the HD Bus Terminals, spring-loaded terminals are used and no tools are required for the wiring.

488

Mechanical data

KMx0x2

Design form compact terminal module with pluggable wiring level

Dimensions (W x H x D)

26.5 mm x 100 mm x 71 mm

Installation on 35 mm DIN rail, conforming to EN 50022 with lock

Side by side mounting by double slot and key connection means of Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29

EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4

Connection

KMx0x2, KMx0x4

Wiring spring-loaded technique

Connection cross-section

0.08…1.5 mm², stranded wire, solid wire

Stripping length

8 mm

Power contacts none

Nominal voltage depends on Bus Terminal type, max. 60 V DC

BECKHOFF New Automation Technology

KMx0x4 75 mm x 100 mm x 55 mm

We reserve the right to make technical changes.

Page 30

46 mm 18 mm

100 mm

KM Housing

121 mm

35 mm

123 mm

55 mm

Bus Terminal

KM10x8, KM20x8

489

Mechanical data

KMx0x8

Design form compact terminal module with pluggable wiring level

Dimensions (W x H x D)

123 mm x 100 mm x 55 mm

Installation on 35 mm DIN rail, conforming to EN 50022 with lock

Side by side mounting by double slot and key connection means of Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29

EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4

Connection

KMx0x8

Wiring spring-loaded technique

Connection cross-section

0.08…1.5 mm², stranded wire, solid wire

Stripping length

8 mm

Power contacts none

Nominal voltage depends on Bus Terminal type, max. 60 V DC

We reserve the right to make technical changes.

BECKHOFF New Automation Technology