Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 2 of 16

Bus Terminal: The modular fieldbus system for automation, pages 11 to 20

Pages 11 to 20 of 156

The original document is the PDF (9.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Beckhoff KL1184, Beckhoff KL2022 and Beckhoff KL2184

Page 11

Product overview Bus Terminals

Digital output: KL2xxx | KS2xxx Signal 1-channel

2-channel

4-channel

5 V DC 24 V DC

KL2012 | KS2012

535

IMAX = 0.5 A

KL2032 | KS2032

KL2022 | KS2022

535

IMAX = 2.0 A

534

IMAX = 0.5 A

KL2212 | KS2212

KL2124 | KS2124

537

KL2114 | KS2114

534

IMAX = 0.5 A

535

IMAX = 0.5 A, diagnostic,

KL2134 | KS2134

534

IMAX = 0.5 A

KL2184 | KS2184

538

IMAX = 0.5 A, negative switching

Bus Terminal protected sensor supply

KL2442

KL2404 | KS2404

534

2 x 4 A/1 x 8 A

533

IMAX = 0.5 A, 4 x 2-wire

KL2424 | KS2424

533

IMAX = 2.0 A, 4 x 2-wire

KL2904

537

TwinSAFE, 4 safe outputs

470

24 V AC/DC

KL2784 | KS2784

539

IMAX = 2.0 A, solid state relay

125 V AC

KL2612 | KS2612

KL2794 | KS2794

539

IMAX = 2.0 A, solid state relay

540 relay, change-over

230 V AC

KL2641

540

KL2602 | KS2602 relay, make contact, manual, 16 A relay, make contact

KL2751 | KS2751

KL2652 | KS2652

549 universal dimmer, 300 W

KL2761 | KS2761

549

KL2712 | KS2712

541

545

KL2732 | KS2732

541

KL2702 | KS2702

545 solid state relay, 0.3 A

544 triac solid state relay, 3 A

KL2622 | KS2622 relay, make contact, no power cont.

relay, change-over universal dimmer, 600 W

KL2701 | KS2701

541

KL2722 | KS2722

544 triac, mutually locked outputs

544 triac, mutually locked outputs,

KL2692 | KS2692

546 cycle monitoring (watchdog)

no power contacts

400 V AC

KL2631 | KS2631

541 relay, make contact

PWM

KL2502 | KS2502

548

24 V DC, 0.1 A

KL2535 | KS2535

KL2512 | KS2512

548

24 V DC, 1.5 A, negative switching

548

KL2545 | KS2545

548

50 V DC, 3.5 A, current-controlled

50 V DC, 3.5 A, current-controlled

DC motor

KL2532 | KS2532

KL2552 | KS2552 output stage

24 V DC, 1 A

Frequency outp.

KL2521

547

Stepper motor

KL2531 | KS2531

550

IMAX = 1.5 A

KL2541 | KS2541

550

IMAX = 5 A

AC motor speed

KL2791 | KS2791 controller

230 V AC, 200 VA

552

552

50 V DC, 5 A

553

KLxxxx: Standard Bus Terminals, KSxxxx: Bus Terminals with pluggable wiring level

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 12

KM2xxx 8-channel 532

IMAX = 0.5 A

KL2488 | KS2488

KL2872

4-, 16-, 32-, 64-channel 535

IMAX = 0.5 A, flat-ribbon cable

KL2872-0010

538

IMAX = 0.5 A, flat-ribbon cable,

IMAX = 0.5 A, negative switching

IMAX = 0.5 A, 8 x 0 V

536

IMAX = 0.5 A, 32-channel

KL1859 KL2808

536

KM2004 negative switching

538

KM2002 IMAX = 0.5 A, 16-channel

533

533

8 inputs, 8 outputs, filter 3.0 ms,

KM2008 type 3, IMAX = 0.5 A

IMAX = 0.5 A, 64-channel

KL2809 IMAX = 0.5 A

533

KL2889 IMAX = 0.5 A, negative switching

538

Bus Terminal

KL2408 | KS2408

16-channel

536

KM2042

535

IMAX = 0.5 A, 16-channel, D-sub

KM2604

471

542 relay, 16 A, 4-channel

KM2642

KM2614

542 relay, 16 A, 4-channel, manual operation

543

KM2652

543 relay, 6 A, manual/automatic operation, relay, 6 A, manual/automatic operation, relay state readable switch and relay state readable

KM2774

545 triac outputs for 4 blind motors

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Page 13

Product overview Bus Terminals

Analog input: KL3xxx | KS3xxx, KM3xxx Signal 1-channel

2-channel

4-channel

0…2 V,

KL3172 | KS3172 557

KL3172-0500

0…500 mV

0…2 V, 16 bit, 0.05 %

0…500 mV, 16 bit, 0.05 %

±2 V

KL3182 | KS3182 557

8-channel

557

16 bit, 0.05 %

Bus Terminal

0...10 V

± 10 V

472

KL3061 | KS3061 556

KL3062 | KS3062 556

KL3064 | KS3064 556 single-ended, 12 bit single-ended, 12 bit single-ended, 12 bit

KL3162 | KS3162 557

KL3464 | KS3464 556

16 bit, 0.05 % single-ended, 12 bit single-ended, 12 bit

KL3001 | KS3001 554

KL3002 | KS3002 554

KL3404 | KS3404 555

KL3408 | KS3408 555 differential input, 12 bit differential input, 12 bit single-ended, 12 bit single-ended, 12 bit

KL3102 | KS3102 555 0...20 mA

4...20 mA

KL3468 | KS3468 557

KL3132 | KS3132 555 differential input, 16 bit

16 bit, 0.05 %

KL3011 | KS3011 558

KL3041 | KS3041 559

KL3012 | KS3012 558

KL3112 | KS3112 559

KL3444 | KS3444 558

KL3448 | KS3448 559 differential input, 12 bit with sensor supply, 12 bit differential input, 12 bit differential input, 16 bit single-ended, 12 bit single-ended, 12 bit

KL3042 | KS3042 559

KL3142 | KS3142 559

KL3044 | KS3044 558 with sensor supply, 12 bit

16 bit, 0.05 % single-ended, 12 bit

KL3021 | KS3021 560

KL3051 | KS3051 561

KL3022 | KS3022 560

KL3052 | KS3052 561

KL3454 | KS3454 560

KL3458 | KS3458 561 differential input, 12 bit with sensor supply, 12 bit differential input, 12 bit with sensor supply, 12 bit single-ended, 12 bit single-ended, 12 bit

KL3122 | KS3122 561

KL3152 | KS3152 561

KL3054 | KS3054 560 differential input, 16 bit

16 bit, 0.05 %

Resistance ther-

KL3201 | KS3201 562

KL3202 | KS3202 563

KL3222

562

KL3204 | KS3204 563 single-ended, 12 bit

KL3208-0010 mometer (RTD)

PT100…1000, Ni100, 16 bit

PT100…1000, Ni100, 16 bit

PT100, 4-wire connection,

PT100…1000, Ni100, 16 bit

PT1000, Ni1000, PTC

563

KL3228 | KS3228 563 high-precision

PT1000, Ni1000, PTC

Thermo-

KL3311 couples/mV type J, K, L,…U, 16 bit

Resistor bridge

KL3351 | KS3351 566

KL3312

564

KL3314

565 type J, K, L,…U, 16 bit strain gauge, 16 bit

565 type J, K, L,…U, 16 bit

KL3356 | KS3356 566 strain gauge, 16 bit, self-calibration

Oscilloscope

KL3361 | KS3361 567

KL3362 | KS3362 567 oscilloscope terminal, oscilloscope terminal,

±16 mV

±10 V

Measurement

KL3681 | KS3681 569

KL3403 | KS3403 568

KL3403-0010 technology digital multimeter terminal,

3-phase power measure-

3-phase power measure- ment terminal, 1 A ment terminal, 5 A

18 bit

Pressure

KM3701 measuring

KM3701-0340 570

KM3702 differential pressure differential pressure relative pressure measuring, relative pressure measuring, measuring, -100…+100 hPa measuring, up to 340 hPa

7,500 hPa

-1,000…+1,000 hPa

570

571

KM3712

568

571

KLxxxx: Standard Bus Terminals, KSxxxx: Bus Terminals with pluggable wiring level

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 14

Analog output: KL4xxx | KS4xxx

KM4xxx

Signal KL4001 | KS4001

2-channel 574

12 bit, potential-free output

KL4002 | KS4002

4-channel 574

12 bit

KL4004 | KS4004

8-channel

12 bit

KL4404 | KS4404

KL4031 | KS4031

572

12 bit, potential-free output

KL4032 | KS4032

572

12 bit

KL4034 | KS4034

575 manual/automatic operation

575

12 bit

± 10 V

2-channel KM4602

574

KL4408 | KS4408

575

12 bit

Bus Terminal

1-channel 0...10 V

573

12 bit

473

KL4434 | KS4434

573

12 bit

KL4132 | KS4132

KL4438 | KS4438

573

12 bit

573

16 bit

KL4494 | KS4494

573

2 x input, 2 x output, 12 bit

0...20 mA

KL4011 | KS4011

576

12 bit

KL4012 | KS4012

576

12 bit

KL4414 | KS4414

577

12 bit

KL4112 | KS4112

KL4418 | KS4418

577

12 bit

577

16 bit

4...20 mA

KL4021 | KS4021 12 bit

578

KL4022 | KS4022

578

12 bit

KL4424 | KS4424 12 bit

We reserve the right to make technical changes.

579

KL4428 | KS4428

579

12 bit

BECKHOFF New Automation Technology

Page 15

Product overview Bus Terminals

Special functions: KL | KS5xxx, KL | KS6xxx

Power terminals: KL8xxx

Safety terminals: KLx904

Signal

Signal

Signal

KL5001 | KS5001 580

KL5051 | KS5051 580 measurement

SSI encoder interface bidirectional SSI switching capacity 5.5 kW,

TwinSAFE, encoder interface nominal current 0.9 to 9.9 A,

4-channel digital

KL5101 | KS5101 582

KL5111 | KS5111 583 connection mechanism for input terminal, incremental encoder incremental encoder

Siemens contactors (Sirius

IEC 61508 SIL 3 and interface, differential input interface

3R series)

DIN EN ISO 13849-1:

Bus Terminal

Position

400 V AC 3~

KL8001

592

24 V DC

KL5151 | KS5151 583

KL1904

531

2008 PLe incremental encoder interface, 32 bit

KL5121 | KS5121 581

KL5152 | KS5152 583 incremental encoder inter-

2-channel incremental

KL8601 face with program. outputs encoder interface, 32 bit communication module

TwinSAFE,

Communi-

KL6001 | KS6001 584

KL6031 | KS6031 584 for Schneider TeSys U

4-channel digital cation serial interface RS232, serial interface RS232, output terminal,

19.2 kbaud

115.2 kbaud

IEC 61508 SIL 3 and

KL6011 | KS6011 585

KL6051 | KS6051 585

DIN EN ISO 13849-1:

serial interface TTY, data exchange terminal,

2008 PLe

20 mA current loop

32 bit

KL6021 | KS6021 585

KL6041 | KS6041 585 serial interface RS422/RS485, serial interface RS422/RS485,

KL8610

19.2 kbaud

115.2 kbaud adapter terminal for

474

KL6023

589

KL6021-0023 wireless adapter for

RS485 interface for

EnOcean radio technology

EnOcean signals

KL6581

KL6583

588

EnOcean master

588

IO-Link master wireless data exchange

593

Controller

KL6904

591

TwinSAFE Logic

588

Bus Terminal, with 4 digital outputs, and receiver

KM6551

537

Schneider TeSys U

EnOcean transmitter

KL6224 | KS6224 589

KL2904

593

IEC 61508 SIL 3 and

587

DIN EN ISO 13849-1: 2008 PLe terminal

KL6201 | KS6201 586 AS-Interface master terminal

KL6211 | KS6211 586 AS-Interface master terminal with power contacts

KL6301 | KS6301 589

KL6401 | KS6401 590

EIB Bus Terminal

LON Bus Terminal

KL6771 | KS6771 590

KL6811 | KS6811 590

MP-Bus master terminal

DALI/DSI master and power supply terminal

KLxxxx: Standard Bus Terminals, KSxxxx: Bus Terminals with pluggable wiring level

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 16

System terminals: KL9xxx | KS9xxx Signal

System

System

KL9010

Signal

Potential supply

24 V DC

KL9100 | KS9100

Power supply and accessories

598

594 bus end terminal

K-bus power supply, 2 A

598 terminal bus extension end terminal

KL9050

KL9110 | KS9110

594 diagnostic

598

KL9200

598

595 with fuse

595 diagnostic, with fuse

595

KL9515 | KS9515 input 24 V DC,

596 602

AS-Interface potential supply

KL9560 | KS9560

597 with electrical isolation

597

50 V DC

KL9570 | KS9570 500 µF, 50 V DC

595

120...230 V AC 603 surge filter terminal for field supply

KL9300 | KS9300

KL9160 | KS9160

594 595 with fuse

KL9260

599

595 diagnostic, with fuse

599

7 diodes, common cathode

KL9302 | KS9302

594

KL9250

603

4 diodes, potential-free

KL9301 | KS9301

KL9150 | KS9150 diagnostic surge filter terminal for system/field supply

Diode array

604 buffer capacitor terminal, shield terminal

KL9550 | KS9550

601 output 24 V DC, 0.1 A,

597 potential distribution terminal, 16 x 0 V DC

KL9540 | KS9540

602 input 24 V DC, potential distribution terminal, 16 x 24 V DC

KL9195 | KS9195

KL9528 | KS9528 AS-Interface power supply terminal potential distribution terminal, 8 x 0 V

KL9189

601 output 15 V DC, 0.5 A

KL9520 | KS9520

597 potential distribution terminal, 8 x 24 V

KL9188

601 output 12 V DC, 0.5 A

597

KL9185 | KS9185

KL9187 | KS9187

475 input 24 V DC, potential distrib. terminal, 8 x 24 V DC, 8 x 0 V DC

KL9186 | KS9186

601 output 10 V DC, 0.5 A

KL9512 | KS9512

596 potential distrib. terminal, only 2 power contacts

Filter

KL9510 | KS9510 input 24 V DC, potential distribution terminal

KL9184

601 output 8 V DC, 0.5 A

KL9210 isolation terminal

KL9180 | KS9180

KL9508 | KS9508 input 24 V DC,

595 shield terminal

KL9080

600 output 5 V DC, 0.5 A adapter terminal for power terminal KL8xxx

KL9070 | KS9070

KL9505 | KS9505 input 24 V DC, terminal bus extension coupler terminal

KL9060

600 input 24 V DC,

Bus Terminal

KL9020

KL9400 | KS9400

599 up to 400 V AC

KL9190 | KS9190

594

KL9290

595 with fuse

7 diodes, common anode

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Page 17

Potential feeder terminals enable to set up different potential groups.

Bus Coupler: the link between Bus Terminals and fieldbus Bus Terminals in 1-, 2-, 4-, 8- and 16-channel modularity with combinations of any desired types of signal

Bus Terminal

The Bus Terminal system

476

The I/O signals are wired in a decentralised way to fieldbus devices or centrally to the controller. The available manufacturer-specific fieldbus devices with fixed input/output configurations and design often make it necessary to use an entire group of devices with similar functions. This costly method of signal acquisition gives rise to high material, installation, planning and documentation costs as well as high costs for subsequent modification or expansion. Inventory management and service staff are put under unnecessary strain. Flexible and stable The Beckhoff Bus Terminal is an open and fieldbus-neutral I/O system consisting of electronic terminal blocks. The head of an electronic terminal block is the Bus Coupler with the interface to the fieldbus. Bus Couplers are available for the following bus systems: – EtherCAT, the fast real-time Ethernet fieldbus, – Lightbus, the fast fibre optic fieldbus, – PROFIBUS DP/FMS conforms to the European standard EN 50170, – Interbus, which has been on the market since 1987, – CANopen, multi-masters in the actuator/sensor area, – DeviceNet, the device bus with CAN technology, – ControlNet, the standardised fieldbus, – Modbus, the open fieldbus,

BECKHOFF New Automation Technology

–

Fipio, the fieldbus according to the WorldFIP standard, – CC-Link, the fieldbus for the Asian market, – SERCOS interface, the bus from the drives engineering field, – RS232/RS485, the network for the most economical solution, – Ethernet TCP/IP, the network bus, – Ethernet/IP, Industrial Ethernet solution from ODVA, – PROFINET, Industrial Ethernet solution from PNO, – USB, the fast interface for the laboratory. With the master terminals, fieldbus functionalities are also available in form of a standard Bus Terminal. This is particularly advantageous for bus systems that are integrated as subsystems into a higher-level system. It means that only one system is required for the subsystem and for the higher-level bus interface. Master terminals are available for the following bus systems: – AS-Interface, the sensor/actuator bus for the lower control level, – EIB, LON, DALI, i.e. the communication standards in building automation. Automation standard The Beckhoff Bus Terminal ensures that control cabinets and terminal boxes are constructed more economically. Using the 4-wire terminating system, all of the usual sensors and actuators with different types of signals can be connected directly without other connection systems. It is no longer necessary to wire the field devices between the first terminal connection in the control cabinet or in the terminal box and the controller. This significantly reduces the costs involved in controller design and saves space, material, work, and money. The field devices can be wired using the Beckhoff Bus Terminal system on site where the signals occur. Installation and wiring of the Beckhoff Bus Terminal is thus simple like that of a standard terminal block. The Bus Terminal can be connected to the controller by connecting a Bus Coupler via the fieldbus as required. The Beckhoff Bus Terminals have been tried and tested in a wide range of sectors worldwide, from machine construction to building management. Beckhoff Bus Terminal technology makes design, construction, wiring, commissioning and maintenance of equipment and machines very cost-effective. Design The robust housing, secure contacts and the solidly built electronics are prominent features of our components. A station consists of one Bus Coupler and up to 64 electronic terminal blocks. With the K-bus extension it is possible to operate up to 255 Bus Terminals on one Bus Coupler. The electronic terminal blocks are clipped onto the Bus Coupler. They connect

We reserve the right to make technical changes.

Page 18

Operation of up to 64 Bus Terminals on one Bus Coupler (255 with K-bus extension KL9020 and KL9050)

Bus end terminal

Fast and secure data connections by means of a serial terminal bus by simply latching together. This means that each electronic terminal block can be exchanged separately and can be mounted on a standard mounting rail. In addition to horizontal type mounting, all other mounting types are permitted in the majority of the cases. The Beckhoff Bus Terminal with its outside contour adjusts perfectly to the measurements of terminal boxes. The clear front panel of the terminal with light-emitting diodes for status display, plug-in contact labelling and detachable labelling fields guarantee clarity. The 3-wire system supplemented by a protective conductor terminal makes it possible to wire sensors/actuators directly. Free mix of signals The Beckhoff I/O system supports about 400 Bus Terminals and is thus probably the most comprehensive system on the market. The components enable users to operate mixed signal configurations without restriction at each station. This means that a single non-central input/output node can map all the necessary signals. Appropriate Bus Terminals are available for any digital or analog automation signal type, for currents and voltages with standardised signal levels and for PT100 and thermocouple signals. Intelligent devices can be connected via Bus Terminals with serial interfaces in accordance with RS232, RS485 or 20 mA TTY.

We reserve the right to make technical changes.

The fine granularity of the Bus Terminals enables bit-precise composition of the required I/O channels. The digital Bus Terminals are available as 2-, 4-, 8- or 16-channel terminals. In the 16-channel variant, digital input and output signals are arranged in an ultra-compact way within a standard Bus Terminal housing across a width of only 12 mm. The standard analog signals of -10…+10 V, 0…+10 V, 0…20 mA and 4…20 mA are all available as 1-, 2-, 4- and 8-channel variants within a standard housing. The system is thus highly modular and can be projected costeffectively with an accuracy down to a single channel. The KMxxxx terminal modules with plug-in wiring combine 16, 32 or 64 digital I/Os within a very small space and with high packing density.

Project engineering and parameterisation If the TwinCAT automation software from Beckhoff is used, the I/O stations can be integrated and parameterised conveniently via the TwinCAT System Manager. As a “configuration centre”, the System Manager links the PLC programs and the connected I/O channels.

Economical and small For the user, Beckhoff Bus Terminals offer independence from the particular fieldbus and terminal block design. Digital and analog signals can be mixed without restriction, starting with one or two signals per terminal. They replace manufacturer-specific designs and all the intermediate terminal positions. The Bus Terminal ensures transparency and flexibility. Distributors and terminal boxes become smaller, more economical, and in some cases can be omitted. Plants and machinery equipped with Beckhoff Bus Terminals offer significant competitive advantages.

BECKHOFF New Automation Technology

Bus Terminal

Power contacts for automatic transfer of supply voltage

477

Page 19

KLxxxx | The standard KL type Bus Terminals include electronics and connection level in a single housing.

KSxxxx | The KS series Bus Terminals feature a pluggable connection level enabling the complete wiring to be removed as a plug connector from the top of the housing for servicing.

The Bus Terminals with 16 terminal points offers a very high packing density in 12 mm.

Bus Terminal

Flexible connection system KLxxxx | Standard

KSxxxx | Pluggable wiring wiring

478

The Bus Terminal system offers different connection options for optimum adaptation to the respective application. The KLxxxx Bus Terminals include electronics and connection level in a single enclosure. The KSxxxx type Bus Terminals feature a pluggable connection level. The KM modules integrate a wide range of I/Os within a very small area. All terminal types are bus-neutral and can be combined as required. The standard KL Bus Terminals have been tried and tested for years. They feature integrated screwless spring loaded technique for fast and simple assembly.

The HD Bus Terminals (High Density) with 16 terminal points are distinguished by a particularly compact design, as the packaging density is twice as large as that of the standard 12 mm Bus Terminals. Singlewire conductors and conductors with a wire end sleeve can be inserted directly into the spring loaded terminal point without tools.

BECKHOFF New Automation Technology

The KS type Bus Terminals feature a pluggable connection level. The assembly and wiring procedure for the KS series is the same as for the KL series. The KS series Bus Terminals enable the complete wiring to be removed as a plug connector from the top of the housing for servicing. The lower section can be removed from the Bus Terminal assembly by pulling the unlocking tab. Insert the new component and plug in the connector with the wiring. This reduces the installation time and eliminates the risk of wires being mixed up. The familiar dimensions of the Bus Terminal only had to be changed slightly. The new connector adds about 3 mm. The maximum height of the Bus Terminal remains unchanged. The overview and nomenclature of the product names has been retained: The plug connector variant is identified in the part number by an additional letter. Conductor cross sections between 0.08 mm² and 2.5 mm² can continue to be used with the proven spring loaded technique. A tab for strain relief of the cable simplifies assembly in many applications and prevents tangling of individual connection wires when the connector is removed.

We reserve the right to make technical changes.

Page 20

KMxxxx | The KM type terminal modules feature pluggable wiring, combining 16, 32 or 64 digital I/Os in a very small area with high packing density.

with high packing density

More sensor and actuator functionality makes machines and systems more and more powerful. The Bus Terminal reliably meets increased requirements for I/O signals through its modularity and compact design. The existing Bus Terminal system is complemented by the compact version of the KMxxxx terminal module with increased packing density. In many areas of application, cost benefits can be realised through lower overall installed size and applicationspecific signal mix. The terminal modules are fully system-compatible. Like the Bus Terminals, they are bus-neu-

We reserve the right to make technical changes.

tral and can therefore be operated with any Beckhoff Bus Coupler or Bus Terminal Controller. Like the standard Bus Terminals, the KM modules are integrated in the I/O system and connected with the internal terminal bus (K-bus). Bus Terminals and terminal modules can be combined without restriction. Like for the Bus Terminals, no tools are required for the wiring. Spring-loaded terminals are used, however with connectors (cable cross section 0.5…1.5 mm²). The terminal modules combine 16, 32 or 64 digital inputs or outputs on a very small area. This compact and slimline design enables very high packing densities, leading to smaller control cabinets and terminal boxes. Digital l/O modules with up to 64 channels The KM modules are used, for example, in applications with high demand for standard signal types such as digital I/Os. The very compact digital KM1xxx and KM2xxx input/output terminal modules have 16, 32 or 64 channels. Each I/O connector has eight inputs or outputs. LEDs integrated in the connector indicate the signal state for each channel directly at the wire. Depending on the connection type, the terminal modules are available with 1- or 3-pin plug connector and enable connection with 1, 2 or 3 wires. Customer-specific signal mix In addition to the standard I/O types, the terminal modules are also available as customerspecific types, e.g. for use in production machines with identical I/O combinations. The combination terminal modules consolidate typical automation signal combinations. This enables smaller physical size and quantity of parts with significant cost savings.

Interface standards within the Bus Terminal In addition to plug-in wiring, sensor-specific plug connectors such as D-sub, RJ 45 or BNC simplify the application of the Bus Terminal system. Sensors and actuators with pre-assembled connectors can be connected directly and quickly with the Bus Terminal system. Relay or power modules are also available, which are either equipped with standard relays or with integrated electronics to connect wattages up to 16 A.

BECKHOFF New Automation Technology

Bus Terminal

KMxxxx | Pluggable wiring

479