Bus Terminal: The modular fieldbus system for automation, pages 141 to 150

Pages 141 to 150 of 156

The original document is the PDF (9.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Beckhoff KL1184, Beckhoff KL2022 and Beckhoff KL2184

Page 141

System Terminals

KL9400, KL9505

Bus Terminal

KL94xx, KL95xx | Power supply terminals The KL94xx and KL95xx terminal series are designed for the modified feeding of the operating voltage into the terminal strand. The KL9400 power supply terminal enables the refreshment of the K-bus, via which data exchange takes place between Bus Couplers and Bus Terminals. Each Bus Terminal requires a certain amount of current from the K-bus (see technical data: “Current consumption K-bus”). This current is fed into the K-bus by the relevant Bus Coupler’s power supply unit. When configuring a large number of Bus Terminals, the 5 V power supply to the K-bus can be increased by 2 A via the KL9400. The KL95xx power supply terminals produce different output voltages from the input voltage (24 V DC) that can be accessed at the terminals. The following Bus Terminals are also supplied with this voltage via the power contacts. The power LEDs indicate the operating states of the terminals; short-circuits or overloads are indicated by the overcurrent LEDs. There is no electrical isolation of the input and output voltage.

Power supply terminal

Power supply terminal, for refreshing the K-bus

5 V DC

Technical data

KL9400 | KS9400

KL9505 | KS9505

Technology power supply terminal power supply terminal, 5 V DC, with diagnostics

Diagnostics

– yes

+24 V

+24 V

0V

0V

1

5

1

5

2

6

2

6

3

7

3

7

4

8

4

8

The KL9505 generates 5 V from the fed-in 24 V without electrical isolation.

600

Input voltage

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

Output voltage

5 V DC

5 V DC ±1 %

Output current

2 A for K-bus supply

0.5 A

Short-circuit-proof yes yes

Residual ripple

–

< 5 mV

Current consumption

–

–

Electrical isolation

–

–

Special features

– stabilised analog voltage

Operating temperature

0…+55 °C

0…+55 °C

Approvals

CE, UL, Ex, GL

CE, UL, Ex

Weight approx. 65 g approx. 65 g

Further information www.beckhoff.com/KL9400 www.beckhoff.com/KL9505

K-bus

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 142

System Terminals

Power supply terminal,

Power supply terminal,

Power supply terminal,

Power supply terminal,

Power supply terminal,

8 V DC

10 V DC

12 V DC

15 V DC

24 V DC, electrical isolation

KL9508 | KS9508

KL9510 | KS9510

KL9512 | KS9512

KL9515 | KS9515

KL9560 | KS9560 power supply terminal, power supply terminal, power supply terminal, power supply terminal, power supply terminal,

8 V DC, with diagnostics

10 V DC, with diagnostics

12 V DC, with diagnostics

15 V DC, with diagnostics

24 V DC

+24 V

0V

+24 V

0V

+24 V

0V

+24 V

0V

+24 V

0V

1

5

1

5

1

5

1

5

1

5

2

6

2

6

2

6

2

6

2

6

3

7

3

7

3

7

3

7

3

7

4

8

4

8

4

8

4

8

4

8

The KL9508 generates 8 V from the fed-in 24 V without electrical isolation.

The KL9510 generates 10 V from the fed-in 24 V without electrical isolation.

The KL9512 generates 12 V from the fed-in 24 V without electrical isolation.

The KL9515 generates 15 V from the fed-in 24 V without electrical isolation.

The KL9560 generates potential-free 24 V from the fed-in 24 V with electrical isolation.

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

8 V DC ±1 %

10 V DC ±1 %

12 V DC ±1 %

15 V DC ±1 %

24 V DC (-15 %/+5 %)

0.5 A

0.5 A

0.5 A

0.5 A

≤ 0.1 A yes yes yes yes yes,

< 5 mV

< 5 mV

< 5 mV

< 5 mV no data

–

–

–

–

–

–

–

–

–

1,500 V AC automatic restart constant load input/output voltage stabilised analog voltage stabilised analog voltage stabilised analog voltage stabilised analog voltage analog voltage with electrical isolation

0…+55 °C

0…+55 °C

0…+55 °C

0…+55 °C

0…+55 °C

CE, UL, Ex

CE, UL, Ex

CE, UL, Ex

CE, UL, Ex

CE, UL, Ex, GL approx. 65 g approx. 65 g approx. 65 g approx. 65 g approx. 65 g www.beckhoff.com/KL9508 www.beckhoff.com/KL9510 www.beckhoff.com/KL9512 www.beckhoff.com/KL9515 www.beckhoff.com/KL9560

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Bus Terminal

KL95xx

601

Page 143

System Terminals

KL9520, KL9528

Bus Terminal

KL9520, KL9528 | AS-Interface system terminals

602

An AS-Interface network consists of a special power supply unit, a master and a larger number of slaves. Each communication device is connected in parallel to the AS-Interface cable, and receives its supply voltage and also exchanges its data via this connection. The transmitter changes its current consumption according to its transmission bits. The AS-Interface power supply unit converts this current change into a voltage change, which can be measured by all devices. An AS-Interface power supply unit supplies the network with a voltage of 30 V in order to ensure that sufficient voltage is available to all devices with maximum cable length and maximum current consumption. The KL9528 Bus Terminal is an AS-Interface power supply unit with an output current of up to 1.25 A. The AS-Interface supply voltage of 30 V is generated from the 24 V control voltage. The KL9520 Bus Terminal is intended for AS-Interface Power24V applications. Thanks to an internal circuit, the 24 V control voltage is usable for a simple AS-Interface network. An AS-Interface voltage of 24 V is sufficient in many small networks if the cable lengths and current consumption do not cause a large voltage drop.

AS-Interface potential

AS-Interface power supply feed terminal with filter terminal 24 V DC/30 V DC, 1.25 A

Technical data

KL9520 | KS9520

KL9528 | KS9528

Technology potential feed terminal power supply terminal

Diagnostics

–

U+

+24 V

U–

0V

1

5

1

5

1’

5’

2

6

2

6

2’

6’

3

7

3

7

3’

7’

4

8

4

8

4’

8’

The KL9520 potential feed terminal uncouples the input and output signal through an integrated filter and enables the supply of AS-Interface networks from standard power supply units or another AS-Interface network.

The KL9528 power supply terminal generates a 30 V DC output voltage from the 24 V DC control voltage with high-frequency decoupling for the operation of an AS-Interface network. The connection to the KL6201 AS-Interface master is established via plugs.

Input voltage up to 35 V

21...28.8 V DC

Output voltage up to 35 V

30 V DC (+5 %/- 5 %)

Output current

– max. 1.25 A

Short circuit current

– max. 1.3 A

Current load max. 2 A

–

Current consumption

– typ. 10 mA

Electrical isolation

–

1,500 V AC constant load

Special features no electrical isolation

–

Operating temperature

0…+55 °C

0…+55 °C

Approvals

CE

CE

Weight approx. 90 g approx. 150 g

Further information www.beckhoff.com/KL9520 www.beckhoff.com/KL9528

K-bus field side/K-bus

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 144

KL9540, KL9550

System Terminals

KL9540, KL9550 | Surge filter system and field supply System terminal,

System terminal, surge filter field supply surge filter system and field supply

Technical data

KL9540 | KS9540

KL9550 | KS9550

Technology surge filter field supply surge filter system and field supply

Diagnostics

–

1

+60 °C

+60 °C

-20 °C

-20 °C

5

1

U

5

U

2

6

2

6

3

7

3

7

4

8

4

8

Bus Terminal

The KL9540 system terminal contains an overvoltage filter for the 24 V field supply, the KL9550 for the 24 V field and system supply. The filter protects the Bus Terminals from line-bound surge voltages that can occur due to high-energy disturbances such as switching overvoltages at inductive consumers or lightning strikes at the supply lines. The Bus Terminals KL9540 or KL9550 protect the Bus Terminal station from damage in particularly harsh environments. The ship classification organisations require the use in shipbuilding applications and in the onshore/offshore sector.

603

Nominal voltage

24 V (-15 %/+20 %)

24 V (-15 %/+20 %)

Surge filter yes yes

– yes

PE connection yes

–

Operating temperature

-20…+60 °C

-20…+60 °C

Approvals

CE, UL, Ex, GL

CE, UL, Ex, GL

Weight approx. 40 g approx. 50 g

Further information www.beckhoff.com/KL9540 www.beckhoff.com/KL9550 field supply Surge filter system supply

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Page 145

System Terminals

KL9570

KL9570 | Buffer capacitor terminal The KL9570 Bus Terminal contains highperformance capacitors for stabilising supply voltages. It can be used in connection with small drive terminals. Low internal resistance and high pulsed current capability enable good buffering in parallel with a power supply unit. Return currents are stored, particularly in the context of drive applications, thereby preventing overvoltages. If the fed back energy exceeds the capacity of the capacitors, the KL9570 switches the load voltage through to the terminal points 1 and 5. The energy is dissipated by the connection of an external ballast resistor.

Technical data

KL9570 | KS9570

Technology buffer capacitor terminal

Diagnostics

–

550 1

5

2

6

3

7

4

8

Bus Terminal

10

KL25xx | Motion terminals see page

Buffer capacitor terminal

The KL9570 buffers the connected voltage via its integrated capacitors and connects the external brake resistor if the internal voltage of approx. 56 V is exceeded.

604

Nominal voltage

50 V

Capacity

500 µF

Ripple current

10 A in continuous operation

Internal resistance

< 10 mΩ

Surge voltage protection

> 56 V

Recommended

10 Ω, typ. 10 W ballast resistor Overvoltage

±2 V control range Ballast resistor load-dependent, 2-point control clock rate

BECKHOFF New Automation Technology

Electrical isolation

1,500 V (terminal/K-bus)

Operating temperature

0…+55 °C

Approvals

CE, Ex

Weight approx. 65 g

Further information www.beckhoff.com/KL9570

We reserve the right to make technical changes.

Page 146

Special Terminals

Ordering instructions for special terminals and couplers All Bus Couplers and Bus Terminals are supplied with a standard configuration. The settings can be found on the relevant catalog pages. In addition to this standard configuration, specific coupler and terminal types with modified software or hardware are available. These variants have an order number with additional four figures. Therefore, if you do require a configuration other than standard, quote this extended number when you place your order. The following table provides a summary of the Bus Couplers and Bus Terminals that are available with modified default settings.

Ordering information Bus Coupler BK8100-0060 watchdog special setting 60 s

BK8100-1001 watchdog special setting 10 s

Digital input KL1052-0010

96 V DC positive and negative switching, not in accordance with the EN 61131-2 specifications: plus-switching, positive edge-triggered input, 10 ms pulse extension, input filter 0.2 ms

KL1232-0002 plus-switching, positive edge-triggered input, 20 ms pulse extension, input filter 0.2 ms

KL1232-0010 plus-switching, positive edge-triggered input, 100 ms pulse extension, input filter 3.0 ms

KL1232-0100 plus-switching, negative edge-triggered input, 100 ms pulse extension, input filter 0.2 ms

KL1232-0110 plus-switching, negative edge-triggered input, 100 ms pulse extension, input filter 3.0 ms

KL1232-1000 negative switching, positive edge-triggered input, 100 ms pulse extension, input filter 0.2 ms

KL1232-1001

5 V, negative switching, negative edge-triggered input, 20 ms pulse extension, input filter 0.2 ms

KL1232-1010 negative switching, positive edge-triggered input, 100 ms pulse extension, input filter 3.0 ms

KL1232-1100 negative switching, negative edge-triggered input, 100 ms pulse extension, input filter 0.2 ms

KL1232-1110 negative switching, negative edge-triggered input, 100 ms pulse extension, input filter 3.0 ms

KL1232-2000 plus switching, positive edge-triggered input, 200 ms pulse extension, input filter 0.2 ms

KL1501-0010 gate-counter with auto-reset and setting A0

KL1501-0011 up/down counter with 5 V inputs, 24 V DC outputs

Bus Terminal

I high = 3 mA, I low = 0.5 mA KL1232-0001

KL1702-0010

230 V AC input circuit with type 2 characteristics

605

KL1712-0010

24 V AC/DC input circuit

Digital output KL2502-0012 time-delayed setting of the outputs

KL2502-3020

5 V output, 30 kHz limit frequency

KL2521-0010 with additional outputs (230 V AC/DC, 100 mA) instead of the additional inputs of the default variant

KL2521-0024 for 24 V signal level

KL2541-0006 stepper motor terminal 50 V DC, 5 A, 5 V encoder supply

KL2692-1001

2 digital inputs, 2 potential-free relays, end terminal variant

KL2702-0020

2-channel solid state load relay up to 230 V AC/DC, 1.5 A

KL2722-0010 without reciprocal locking of the channels, total current 1 A

KL2732-0010 without reciprocal locking of the channels, total current 1 A

KL2751-0011 dimmer terminal without power contacts

KL2751-1200 dimmer terminal for 120 V AC

KL2761-0011

1-channel universal dimmer terminal, 230 V AC, 600 VA (W), 50 Hz, without power contacts

KL2791-0011

1-channel AC motor speed controller, 230 V AC, 200 VA, max. 0.9 A, without power contacts

KL2791-1200

1-channel AC motor speed controller, 120 V AC, 100 VA

Analog input KL3002-0010

Siemens S5 format

KL3002-0011 fast µP, scan time approx. 0.5 ms

KL3002-0050

Siemens S7 format

KL3012-0011 altered range: 0…21.5 mA, maximum value corresponds to 21.5 mA instead of 20 mA

KL3012-0012 fast µP, scan time approx. 0.5 ms

KL3012-0050

Siemens S7 format

KL3022-0010

Siemens S5 format

KL3022-0011 fast µP, scan time approx. 0.5 ms

KL3022-0050

Siemens S7 format

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Page 147

Bus Terminal

Special Terminals

606

KL3042-0010

Siemens S5 format

KL3042-0011 fast µP, scan time approx. 0.5 ms

KL3042-0012 altered range: 0…21.5 mA, maximum value corresponds to 21.5 mA instead of 20 mA

KL3042-0050

Siemens S7 format

KL3052-0010

Siemens S5 format

KL3052-0011 fast µP, scan time approx. 0.5 ms

KL3052-0012 changed diagnostic level (< 3.5 mA or > 21.5 mA)

KL3052-0050

Siemens S7 format

KL3054-0050

Siemens S7 format

KL3062-0010

Siemens S5 format

KL3062-0011 voltage level 0…20 V

KL3062-0012 fast µP, scan time approx. 0.5 ms

KL3062-0013 voltage level 0…30 V

KL3062-0014 voltage level 0…50 V

KL3062-0050

Siemens S7 format

KL3064-0010

Siemens S5 format

KL3064-0011 voltage level 0…20 V

KL3064-0050

Siemens S7 format

KL3102-0050

Siemens S7 format

KL3112-0050

Siemens S7 format

KL3122-0050

Siemens S7 format

KL3172-0500

2-channel analog input terminal, 0…500 mV

KL3202-0010

PT200

KL3202-0011

PT200 in Siemens S5 format

KL3202-0012

PT500

KL3202-0013

PT500 in Siemens S5 format

KL3202-0014

PT1000

KL3202-0015

PT1000 in Siemens S5 format

KL3202-0016

Ni100

KL3202-0017

Ni100 in Siemens S5 format

KL3202-0020 resistance measurement 0…1.2 kΩ

KL3202-0021

PT100 in Siemens S5 format

KL3202-0023

Ni120

KL3202-0024

Ni120 in Siemens S5 format

KL3202-0025

Ni1000

KL3202-0026

Ni1000 in Siemens S5 format

KL3202-0027 resistance measurement 10…10 kΩ

KL3202-0028

Resolution increased to 0.01 °C; the measurement range is reduced to -40 °C to +128 °C. The absolute accuracy is 0.3 °C, differential error is 0.1 °C.

KL3202-0029

Ni1000 per Landis&Staefa characteristic curve (Siemens, 100° corresponds to 1,500 Ω)

KL3204-0014

PT1000

KL3204-0021

PT1000 in Siemens S5 format

KL3204-0025

Ni1000, 4-channel

KL3204-0029

Ni1000 per Landis&Staefa characteristic curve (Siemens, 100° corresponds to 1,500 Ω)

KL3312-0010 type J

KL3312-0011 type J in Siemens S5 format

KL3312-0012 type L

KL3312-0013 type L in Siemens S5 format

KL3312-0014 type B

KL3312-0015 type B in Siemens S5 format

KL3312-0016 type E

KL3312-0017 type E in Siemens S5 format

KL3312-0018 type N

KL3312-0019 type N in Siemens S5 format

KL3312-0020 type R

KL3312-0021 type R in Siemens S5 format

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 148

Special Terminals

KL3312-0022 type S

KL3312-0023 type S in Siemens S5 format

KL3312-0024 type T

KL3312-0025 type T in Siemens S5 format

KL3312-0026 type U

KL3312-0027 type U in Siemens S5 format

KL3312-0028

0…120 mV measurement

KL3312-0029 type K in Siemens S5 format

KL3312-0040 expanded temperature range for type S and L type S: -50…+1,700 °C (as supplied type L: -100…+900 °C)

KL3312-0110 type J, Fahrenheit scaling

KL3312-2000 setting of reference junction temperature via process image, unit 1/256° C in a 16 bit word

KL3312-2100 external reference point temperature specification via process image is possible, the unit is 1/256 °C in 16-bit format, fast conversion time 65 ms

KL3351-0001

1-channel resistor bridge terminal (strain gauge), with faster measurement time approx. 10 ms

KL3403-0010

3-phase power measurement terminal, current path designed for 5 A transducer (1 % measuring accuracy I)

KL3403-0020

3-phase power measurement terminal, current path designed for 20 mA, optimised for electronic current transformer

KL3403-0022

3-phase power measurement terminal, current path and voltage input designed for 20 mA

KL3403-0333

3-phase power measurement terminal, 500 V AC, 333 mV AC

KM3701-0340 differential pressure up to 340 hPa

KL4002-0010

Siemens S5 format

KL4002-0011 fast µP, scan time approx. 0.15 ms

KL4002-0050

Siemens S7 format

KL4004-0050

Siemens S7 format

KL4012-0010

Siemens S5 format

KL4012-0011 altered range: 0…21.5 mA, maximum value corresponds to 21.5 mA instead of 20 mA

KL4012-0050

Siemens S7 format

KL4022-0010

Siemens S5 format

Bus Terminal

Analog output

KL4022-0050

Siemens S7 format

607

KL4032-0010

Siemens S5 format

KL4032-0011 fast µP, scan time approx. 0.15 ms

KL4032-0050

Siemens S7 format

KL4034-0010

Siemens S5 format

KL4112-0010

Siemens S5 format

KL4112-0050

Siemens S7 format

KL4132-0010

Siemens S5 format

KL4132-0050

Siemens S7 format

Special functions KL5111-0010

A, B, C signals: 5 V inputs

KL5111-0011 special function: latch input sets counter to zero

KL5111-0012 latches on both edges, A, B, C inputs 24 V

KL5111-0013 latches on both edges, A, B, C inputs 5 V

KL5111-0015 frequency measurement over a selectable time window; 24 V inputs

KL5111-0016 frequency measurement over a selectable time window; 5 V inputs

KL5111-0020

12 V input circuit

KL5151-0021 incremental encoder 1 x 32 bits A, B, capture input and 1 driver output 24 V, 0.5 A

KL5151-0050 incremental encoder 2 x 32 bits A, B-track

KL6001-0020 standard format 5 bytes of user data

KL6011-0020 standard format 5 bytes of user data

KL6021-0020 standard format 5 bytes of user data (rest default)

KL6021-0021 standard format 5 bytes of user data (7 bits, even, 1 stop bit, 9,600 baud)

KL6201-0010 preset to 22 bytes K-bus interface (2 K-bus cycles 31 AS-Interface slaves)

KL6201-0011 preset to 38 bytes K-bus interface (4 K-bus cycles 62 AS-Interface slaves)

KL6904-0001

TwinSAFE Logic Bus Terminal, preconfigured ex factory to 15 TwinSAFE connections

System terminals KL9210-0020

We reserve the right to make technical changes.

with 2 A fuse (slow-blow) and modified label

BECKHOFF New Automation Technology

Page 149

Accessories

Accessories Bus Terminals

Bus Terminal

Connectors

608

Lightbus

Description

Z1000 standard connector for 1,000 µm plastic fibre

Z1010 standard connector for 200 µm PCS fibre

Z1020 coupling for Z1000

PROFIBUS

Description

ZB3100

9-pin D-sub connector for PROFIBUS (12 Mbaud) with switchable termination resistor

ZB3101

9-pin D-sub connector for PROFIBUS (12 Mbaud) with programming interface

ZB3102

9-pin D-sub connector for PROFIBUS (12 Mbaud) with programming interface (housing invers)

ZS1031-3000

9-pin D-sub connector for PROFIBUS (12 Mbaud) with integrated termination resistor

ZS1031-3500 fibre optic connector for Bus Coupler BK3500 and BK3520

Interbus

Description

Z1003

FSMA plug with knurled nut for 1,000 µm plastic fibre

ZB4100

9-pin D-sub socket for incoming remote bus

ZB4101

9-pin D-sub plug for outgoing remote bus

CANopen/DeviceNet

Description

ZS1051-3000

9-pin D-sub connector for CANopen with integrated termination resistor

ZS1052-3000

5-pin open style connector for CANopen/DeviceNet with integrated termination resistor

ZS1052-5150

CAN diagnostic interface

SERCOS interface

Description

Z1003

FSMA plug with knurled nut for 1,000 µm plastic fibre

Z1100 plastic fibre optic, single core, 1,000 µm, 2.2 mm

Z1101 plastic fibre optic, single core, 1,000 µm with protective PU cladding and Kevlar strain relief, drag chain suitable

Ethernet/EtherCAT

Description

ZS1090-0003

EtherCAT/Ethernet RJ 45 connector, IP 20, 4-pin, for field assembly, AWG 22-24, packing unit = 10

A

ZS1090-0005

EtherCAT/Ethernet RJ 45 plug, IP 20, 8-pin, field assembly, AWG 22-24, packing unit = 10

B

A

Pict.

B

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 150

Accessories

Bus interface connectors for PROFIBUS, CANopen/DeviceNet The Beckhoff bus interface connector for PROFIBUS and CAN Bus Couplers simplifies bus wiring considerably. There are separate terminals for incoming and outgoing leads. A large area of the screen is connected via the cable grip. The integrated termination resistor can be switched externally. When it is switched on, it makes a break in the outgoing bus lead – this allows rapid fault location and guarantees that no more than two resistors are active in the network. Technical data

ZS1031-3000

ZS1052-3000

Fieldbus

PROFIBUS

CANopen/DeviceNet

Bus plug

D-sub, 9-pin open style connector, 5-pin

Data transfer rates up to 12 Mbaud up to 1 Mbaud (CANopen) or 500 kbaud (DeviceNet)

Cable outgoing downwards (where Bus Terminals are assembled horizontally)

Cable diameter

4.5…8 mm

Wire cross section

0.34 mm wire

Connection method screw type terminal

0.2…0.5 mm litz wire or wire

Wire

PROFIBUS, type A, ZB3200 e.g. CANopen cable ZB5100 or DeviceNet cable ZB5200

Termination resistor network with 2 x 390 Ω, 1 x 220 Ω

120 Ω

Protection class

IP 40

Temperature range

-20…+75 °C

Dimensions (L x W x H)

approx. (65 x 50 x 16) mm

Packaging folding box with instructions

Ordering information

Description

ZK1010-8080-3003 ribbon cable (3 cm) for connecting two KL8001 (included in the scope of supply)

Bus Terminal

Cables for K-bus extension ZK1010-8080-3005 ribbon cable (5 cm) for connecting two KL8001, if a reversing contactor connection is used

609

ZK1010-8080-3010 ribbon cable (10 cm) for connecting the KL9060 with the KL8001 (included in the scope of supply for KL9060)

ZS1010-1610 end plug for KL8001 (included in the scope of supply for KL9060)

ZK1090-0101-1002 extension cable with two plugs, double screened, red, 20 cm, cable for TeSys module KL8601/KL8610

ZK1090-0101-1005 extension cable with two plugs attached, double screened, red, 50 cm, cable for TeSys module KL8601/KL8610

ZK1090-0101-1010 extension cable with two plugs attached, double screened, red, 100 cm

ZK1090-0101-1020 extension cable with two plugs attached, double screened, red, 200 cm

ZK1090-0101-1030 extension cable with two plugs attached, double screened, red, 300 cm

ZK1090-0101-1050 extension cable with two plugs attached, double screened, red, 500 cm

USB cable for KS2000 The KS2000 cable establishes a connection between the Bus Couplers or Bus Terminal Controllers and the PC. The KS2000 can be used for parametering Bus Terminals or Bus Couplers, local diagnostics, forcing Bus Terminal data, monitoring Bus Terminal values, updating firmware and programming Beckhoff mini PLCs via TwinCAT. The USB cable features electrical isolation. Status LEDs indicate whether data are sent or received. On the connected PC the USB cable behaves like a COM port and can therefore be used for all Beckhoff tools using serial communication. Ordering information

Description

KS2000-Z2-USB connection cable for KS2000 or TwinCAT for serial conversion from USB for Bus Couplers or Bus Terminal Controllers of the BK, BC or LC series, lenght 3 m

We reserve the right to make technical changes.