Manual · Beckhoff
Beckhoff KL2184 Tech Manual
Manual1 pagePDF 816 KB
The page is below, with its text.
Covers · 1 model
The models it covers
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
One-page Beckhoff data sheet for the KL2184, a 4-channel 24 V DC digital output Bus Terminal that switches to negative potential. It gives the technical data and the contact layout of the outputs and power contacts.
- What it is
- 4-channel digital output Bus Terminal, 24 V DC, with four 0 V (ground) switching outputs p. 1
- Rated load voltage
- 24 V DC (-15 %/+20 %) p. 1
- Output current
- 0.5 A per channel, short-circuit-proof; short circuit current <7A p. 1
- Load type
- Ohmic, inductive, lamp load p. 1
- Connection
- 2-/3-wire, with +24 V and 0 V power contacts p. 1
- Operating temperature
- 0…+55 °C operating, -25…+85 °C storage; 95 % relative humidity, no condensation p. 1
- Breaking energy
- < 100 mJ/channel; reverse voltage protection p. 1
- Electrical isolation
- 500 V (K-bus/field potential) p. 1
- Current consumption
- Power contacts typ. 30 mA + load; K-bus typ. 9 mA p. 1
- Process image
- 4 outputs; no address or configuration setting p. 1
- Indicators
- One signal LED per channel p. 1
- Protection class
- IP 20, variable installation position p. 1
- Weight
- approx. 70 g p. 1
- Pluggable version
- KS2184 with pluggable wiring p. 1
What this manual walks you through
- Contact layout of the four outputs and power contacts p. 1
Questions this manual answers
How much current can each KL2184 output carry?
Up to 0.5 A per channel; the outputs are short-circuit-proof. p. 1
Does the KL2184 switch to 24 V or to ground?
Its four outputs switch to 0 V (ground), that is to negative potential. p. 1
What loads can the KL2184 drive?
Ohmic, inductive and lamp loads at a rated 24 V DC. p. 1
What is the operating temperature of the KL2184?
0 to +55 °C in operation and -25 to +85 °C in storage. p. 1
The file
Size and text
Every page · 1
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 1
Open in the PDF
The text of page 1, from the PDF itself
Digital OutputKL2184Signal LED1Signal LED2Signal LED3Signal LED4Output 1Output 2
+24 V Power contact +24 V
0V Power contact 0 VOutput 3Output 4Top viewContact assembly
KL2184 | 4-channel digital output terminal 24 V DC, switching to negative potential The KL2184 digital output terminal connects the binary control signals from the automation unit on to the actuators at the process level with electrical isolation. The KL2184 version has four 0 V (ground) switching outputs and generates load currents with outputs that are resistant to overload and short-circuit. The Bus Terminal contains four channels that indicate their signal state by means of light emitting diodes. Technical data
KL2184 | KS2184Connection technology2-/3-wireNumber of outputs4Rated load voltage24 V DC (-15 %/+20 %)Load type
ohmic, inductive, lamp load
Max. output current
0.5 A (short-circuit-proof) per channel
Short circuit current<7ABreaking energy< 100 mJ/channel
Reverse voltage protection
yes
Electrical isolation
500 V (K-bus/field potential)
Current consumption power contacts
typ. 30 mA + load
Current consumpt. K-bus
typ. 9 mA
Bit width in the process image
4 outputs
Configuration
no address or configuration setting
Weight
approx. 70 g
Operating/storage temperature
0…+55 °C/-25…+85 °CRelative humidity95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Pluggable wiring
for all KSxxxx Bus Terminals
Approvals
CE, UL, Ex
BECKHOFF New Automation Technology
We reserve the right to make technical changes.