Bus Terminal: The modular fieldbus system for automation, pages 101 to 110

Pages 101 to 110 of 156

The original document is the PDF (9.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Beckhoff KL1184, Beckhoff KL2022 and Beckhoff KL2184

Page 101

Analog Input

KL30xx, KL3454

Analog input | 4…20 mA 1-channel analog

2-channel analog

4-channel analog

4-channel analog input terminal, input terminal, input terminal, input terminal,

4…20 mA, 12 bits,

4…20 mA, 12 bits,

4…20 mA, 12 bits,

4…20 mA, 12 bits, differential input differential input single-ended single-ended

Technical data

KL3021 | KS3021

KL3022 | KS3022

KL3054

KL3454 | KS3454

Signal current

4…20 mA

Resolution

12 bits

Technology differential input differential input single-ended single-ended

Conversion time

~ 1 ms

~ 2 ms

~ 4 ms

~ 2 ms

Number of inputs

1

2

4

4

+60 °C

1

5

1

5

1

5

1

5

2

6

2

6

2

6

2

6

Bus Terminal

-20 °C

3

7

3

7

3

7

3

7

560

4

8

4

8

4

8

4

8

The KL3021 analog input terminal is characterised by its fine granularity and electrical isolation. The input channels of the Bus Terminal have differential inputs and possess a common, internal ground potential.

The KL3022 analog input terminal combines two differential inputs with a common internal ground potential in one housing.

The KL3054 analog input terminal has four inputs, which are implemented in 2-wire technique. The common reference ground of the inputs is the internal ground.

In the KL3454 Bus Terminal, the four inputs are 2-wire versions and have a common ground potential. The 24 V power contact is connected to the terminal in order to enable the connection of 2-wire sensors.

< ±0.3 % (relative

< ±0.3 % (relative

< ±0.3 % (relative

< ±0.3 % (relative to full scale value)

to full scale value)

to full scale value)

to full scale value)

Current consum. pow.cont.

– (no power contacts)

– (no power contacts)

– (no power contacts)

only load

Current consumpt. K-bus typ. 60 mA typ. 60 mA typ. 75 mA typ. 85 mA

Internal resistance

80 Ω + 0.7 V

80 Ω + 0.7 V

80 Ω + 0.7 V

< 85 Ω

Common-mode voltage UCM

35 V max.

35 V max.

–

–

Surge voltage resistance

35 V DC

35 V DC

35 V max.

30 V DC

Special features

–

– for 2-wire sensors

–

Operating temperature

0…+55 °C

-20…+60 °C

0…+55 °C

0…+55 °C

Approvals

CE, UL, Ex

CE, UL, Ex, GL

CE, UL, Ex, GL

CE, UL, Ex, GL

Weight approx. 70 g approx. 70 g approx. 70 g approx. 75 g

Further information www.beckhoff.com/KL3021 www.beckhoff.com/KL3022 www.beckhoff.com/KL3054 www.beckhoff.com/KL3454

Special terminals

KL3022-00xx

KL3054-0050

Distinguishing features special terminals see

Measuring error

BECKHOFF New Automation Technology

605

Siemens S7 format

We reserve the right to make technical changes.

Page 102

KL3xxx

Analog Input

8-channel analog

1-channel analog

2-channel analog

2-channel analog

2-channel analog input terminal, input terminal, input terminal, input terminal, input terminal,

4…20 mA, 12 bits,

4…20 mA, 12 bits,

4…20 mA, 12 bits,

4…20 mA, 15/16 bits,

4…20 mA, 16 bits, single-ended with sensor supply with sensor supply differential input differential input

KL3458 | KS3458

KL3051 | KS3051

KL3052 | KS3052

KL3122

KL3152

15 bit, configurable to 16 bit

16 bits differential input single-ended single-ended single-ended differential input

~ 4 ms

~ 1 ms

~ 2 ms

140 ms, configurable to 2 ms

140 ms, configurable

8

1

2

2

2

+60 °C

-20 °C

-20 °C

1

5

1

5

1

5

1

5

1

5

2

6

2

6

2

6

2

6

2

6

3

7

3

7

3

7

3

7

3

7

Bus Terminal

+60 °C

4

8

4

8

4

8

4

8

4

8

561

The KL3458 analog input terminal combines eight inputs in one housing. The use of single conductor connection technology enables the connection of multi-channel sensor technology with minimum space requirements. The reference ground for all inputs is the 0 V power contact.

The job of the KL3051 and KL3052 analog input terminals is to supply power to measuring transducers located in the field and to transmit analog measurement signals with electrical isolation to the automation device. The voltage for the sensors is supplied to the terminals via the power contacts. The power contacts can optionally be supplied with operating voltage in the standard way or via a power feed terminal (KL9xxx) with electrical isolation. The 0 V power contact is the reference potential for the inputs.

The KL3122 analog input terminal combines two differential inputs with a common internal ground potential in one housing.

The KL3152 analog input terminal is optimised for highly accurate control processes due to its low measuring error of ±0.05 % (in relation to the full scale value). The differential inputs have a common, internal ground potential.

< ±0.3 % (relative

< ±0.3 % (relative

< ±0.3 % (relative

< ±0.3 % (relative

< ±0.05 % (relative to full scale value)

to full scale value)

to full scale value)

to full scale value)

to full scale value)

– only load only load

– (no power contacts)

– typ. 105 mA typ. 65 mA typ. 65 mA typ. 60 mA typ. 85 mA

< 85 Ω

80 Ω + 0.7 V

80 Ω + 0.7 V

50 Ω typ. shunt,

1 Ω typ. shunt load: 60 Ω + diode voltage –

–

–

35 V max.

±10 V max.

30 V DC

35 V max.

35 V max.

35 V DC

35 V DC high packing density with sensor supply with sensor supply

– increased measuring accuracy

-20…+60 °C

0…+55 °C

-20…+60 °C

0…+55 °C

0…+55 °C

CE, UL, Ex, GL

CE, UL, Ex, GL

CE, UL, Ex, GL

CE, UL, Ex

CE, UL, Ex approx. 75 g approx. 70 g approx. 70 g approx. 70 g approx. 70 g www.beckhoff.com/KL3458 www.beckhoff.com/KL3051 www.beckhoff.com/KL3052 www.beckhoff.com/KL3122 www.beckhoff.com/KL3152

KL3052-00xx

KL3122-0050 special terminals see

We reserve the right to make technical changes.

605 special terminals see

605

BECKHOFF New Automation Technology

Page 103

Analog Input

KL3222, KL3201

Bus Terminal

Analog input | Resistance thermometer (RTD, PT100) The KL32xx Bus Terminals are intended for direct connection of resistance thermometers. The resistance is measured with a small measurement current and the temperature value is calculated by a linearisation corresponding to the sensor type which has been implemented. In practice, platinum and nickel sensors with different resistance values are used. The resistance value of the sensor is always defined at 0 °C: – PT100 = 100 Ω at 0 °C – PT1000 = 1000 Ω at 0 °C – Ni100 = 100 Ω at 0 °C – … The Bus Terminals support 2-, 3- or 4-wire measurement. The measurement and the sensor can be used in any combination, depending on the type of application. For 2-wire measurement 1000 Ω sensors are recommended to reduce the influence of the conductor resistance.

2-channel analog

1-channel analog input terminal, input terminal,

PT100 (RTD),

PT100 (RTD)

high-precision Technical data

KL3222 | KS3222

KL3201 | KS3201

Sensor types

PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement (e.g. potentiometer, 10 Ω…1.2/5 kΩ)

Resolution

0.01 °C per digit

Technology

2-/3-/4-wire

2-/3-wire

Conversion time typ. 50 ms

~ 200 ms

Number of inputs

2

1

562

Measuring error

1

5

2

6

3

7

4

8

+R

+RL

-R

-RL

1

5

2

6

3

7

4

8

The Bus Terminal’s standard settings are: resolution 0.01 °C in the temperature range of PT100 sensors in 4-wire connection.

The Bus Terminal’s standard settings are: resolution 0.1 °C in the temperature range of PT100 sensors in 3-wire connection.

0.1 °C at 40 °C ambient

< ±1 °C temperature, 4-wire connection, PT100 sensors and 50 Hz filter Measuring range

-200…+850 °C (PT sensors);

-200…+850 °C (PT sensors);

-60…+250 °C (Ni sensors);

-60…+250 °C (Ni sensors)

-200…+320 °C (high-precision) Current consumption

–

– (no power contacts)

Current consumpt. K-bus typ. 60 mA typ. 60 mA

Measuring current typ. 0.5 mA typ. 0.5 mA

Special features open-circuit recognition, open-circuit recognition power contacts high-precision Operating temperature

0…+55 °C

0…+55 °C

Approvals

CE

CE, UL, Ex

Weight approx. 70 g approx. 70 g

Further information www.beckhoff.com/KL3222 www.beckhoff.com/KL3201

Special terminals Distinguishing features

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 104

KL32xx

Analog Input

2-channel analog

4-channel analog

8-channel analog

8-channel analog input terminal, input terminal, input terminal, input terminal,

PT100 (RTD)

PT100 (RTD)

PT1000, Ni1000 (RTD)

PT1000, Ni1000 (RTD)

KL3202 | KS3202

KL3204 | KS3204

KL3208-0010

KL3228 | KS3228

PT1000, Ni1000, PTC

2-/3-wire

2-wire

2-wire

1-wire

~ 250 ms

~ 250 ms

~1s

~1s

2

4

8

8

2

5

6

+60 °C

-20 °C

-20 °C

+R

+R

RL

RL υ

3

4

7

1

-R

2

5

6

+R 1

-R

υ

2

10

3

11

4

12

5

13

υ

-R

3

8

4

7

8

+R

-R

+R1

-R1

+R2

-R2

+R3

-R3

+R 1

5

+24 V

2

6

0V

3

7

4

8

9

6

14

7

15

8

16

+R4

-R4

+R5

-R5

+R6

-R6

+R7

-R7

+R8

-R8

υ

+R υ

+R υ

+R υ

The Bus Terminal’s standard settings are: resolution 0.1 °C in the temperature range of PT100 sensors in 3-wire connection.

The Bus Terminal’s standard settings are: resolution 0.1 °C in the temperature range of PT100 sensors.

The Bus Terminal’s standard settings are: resolution 0.25 °C in the temperature range of Ni1000 sensors.

The Bus Terminal’s standard settings are: resolution 0.1 °C in the temperature range of Ni1000 sensors. The inputs have a common, internal ground potential.

< ±1 °C

< ±1 °C

-20…+60 °C: ±0.25 °C at 25 °C

~ ±1 °C, depending on wiring ambient temperature; -50…+150 °C: ±1.5 °C -200…+850 °C (PT sensors);

-200…+850 °C (PT sensors);

-50…+150 °C (PT sensors);

-50…+150 °C (PT sensors);

-60…+250 °C (Ni sensors)

-60…+250 °C (Ni sensors)

-50…+150 °C (Ni sensors)

-50…+150 °C (Ni sensors)

– (no power contacts)

– (no power contacts)

–

– typ. 60 mA typ. 60 mA typ. 85 mA typ. 85 mA typ. 0.5 mA typ. 0.5 mA

~ 0.5 mA typ.

~ 0.5 mA typ.

open-circuit recognition open-circuit recognition open-circuit recognition, cable resist- open-circuit recognition ance calibration, particularly suitable for building automation -20…+60 °C

-20…+60 °C

0…+55 °C

0…+55 °C

CE, UL, Ex

CE, UL, Ex

CE

CE, UL, Ex approx. 70 g approx. 70 g approx. 75 g approx. 75 g www.beckhoff.com/KL3202 www.beckhoff.com/KL3204 www.beckhoff.com/KL3208 www.beckhoff.com/KL3228

KL3202-00xx special terminals see

605

For availability status see Beckhoff website at: www.beckhoff.com/KL3208

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Bus Terminal

1

+60 °C

563

Page 105

Analog Input

KL3311

Bus Terminal

Analog input | Thermocouple

564

Thermocouples can be classified as active transducers. They exploit the thermo-electric effect (Seebeck, Peltier, Thomson). Where two electrical conductors of different materials (e.g. iron and constantan) make contact, a contact voltage occurs at the contact points, which is clearly a function of temperature and so is called thermovoltage. Due to changes in the material during the implementation of a thermocouple, at least two of such material pairings occur. One is placed at the measurement location, the other is the so-called comparison point, which is normally located in the measurement device. In order to compensate for the reference point effect, the temperature at the reference point must be known. For the KL331x this is the connection point of the thermocouple to the terminal contacts, which is why the terminal contact temperature is specially measured here. Thermocouples represent economical and easy to install sensors for temperature measurement with reduced need for accuracy. Depending on the type of thermocouple, temperatures from -200 to +2,300 °C can be measured. The linearisation and cold junction compensation is carried out by a characteristic curve on a microprocessor. The directions in the documentation, concerning earthing and thermocouples which are not potentialfree, must be observed. An error LED indicates a broken wire.

1-channel analog input terminal, thermocouple with open-circuit recognition

Technical data

KL3311

Thermocouple types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement sensor types Resolution

0.1 °C per digit

Technology

2-wire

Conversion time

~ 200 ms

Number of inputs

1

+TC 1

5

2

6

3

7

4

8

–TC

The analog input terminal KL3311 enables direct connection of a thermocouple. The circuit of the Bus Terminal can operate thermocouples using 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. Compensation for the cold junction is made through an internal temperature measurement at the terminal. The KL3311 can also be used for mV measurement. Measuring error

< ±0.5 % (relative to full scale value)

Measuring range in the range defined in each case for the sensor (default setting: type K; -100…+1,370 °C); mV measurement: ±30 mV…±120 mV

Current consumption

– (no power contacts)

power contacts Current consumpt. K-bus typ. 65 mA

Special features electrically isolated

Operating temperature

0…+55 °C

Approvals

CE, UL, Ex

Weight approx. 70 g

Further information www.beckhoff.com/KL3311

Special terminals Distinguishing features

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 106

KL3312, KL3314

2-channel analog input terminal,

4-channel analog input terminal, thermocouple with open-circuit recognition thermocouple with open-circuit recognition

KL3312

KL3314

2-wire

2-wire

~ 250 ms

~ 250 ms

2

4

5

2

+TC 1

5

6

2

6

3

7

3

7

4

8

4

8

–TC

Bus Terminal

+TC 1

Analog Input

–TC

565

+TC

–TC

The KL3312 analog input terminal allows two thermocouples to be connected directly. The circuit of the Bus Terminal can operate thermocouples using 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. Compensation for the cold junction is made through an internal temperature measurement at the terminals. The KL3312 can also be used for mV measurement.

The KL3314 analog input terminal allows four thermocouples to be connected directly. The circuit of the Bus Terminals can operate thermocouples using 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. Compensation for the cold junction is made through an internal temperature measurement at the terminals. The KL3314 can also be used for mV measurement.

< ±0.5 % (relative to full scale value)

< ±0.5 % (relative to full scale value)

in the range defined in each case for the sensor in the range defined in each case for the sensor

(default setting: type K; -100…+1,370 °C);

(default setting: type K; -100…+1,370 °C);

mV measurement: ±30 mV…±120 mV mV measurement: ±30 mV…±120 mV

– (no power contacts)

– (no power contacts)

typ. 65 mA typ. 75 mA

–

–

0…+55 °C

0…+55 °C

CE, UL, Ex

CE, UL, Ex approx. 70 g approx. 75 g www.beckhoff.com/KL3312 www.beckhoff.com/KL3314

KL3312-xxxx special terminals see page

We reserve the right to make technical changes.

605

BECKHOFF New Automation Technology

Page 107

Analog Input

KL3351, KL3356

Analog input | Resistor bridge

Technical data Signal voltage

1-channel analog input terminal,

1-channel analog input terminal, resistor bridge (strain gauge)

accurate resistor bridge evaluation

KL3351 | KS3351

KL3356 | KS3356

UD: -16…+16 mV

UD: -20…+20 mV

UREF: -10…+10 V

UREF: -12…+12 V

Resolution

16 bits

Technology

DMS connection

DMS connection

Conversion time

< 250 ms, configurable

< 250 ms, configurable

Number of inputs

2, for one resistor bridge

2, for one resistor bridge

+UV +UREF

+UV +UREF

1

5

1

5

+Uv

2

6

–Uv

3

7

4

8

-UD

-UD

+UD

6

Bus Terminal

+UD 2

3

7

566

4

8

-UREF -UV

The KL3351 analog input terminal permits direct connection of a resistor bridge. The bridge voltage, UD, and the supply voltage, UREF, to the bridge are digitised with 16 bit resolution, and are transmitted along an electrically isolated channel to the supervising automation system. The input channels are available in the form of two 16 bit values for further processing. The resulting measurement can be calculated from the formula: measurement = UD / UREF. Precise acquisition of the supply voltage along with the bridge voltage compensates for long-term and temperature drift.

-UREF -UV

The KL3356 analog input terminal permits direct connection of a resistor bridge. Its improved input circuit makes the KL3356 significantly more accurate than the KL3351. The ratio between the bridge voltage UD and the supply voltage UREF is determined in the input circuit. In order to achieve good long-term stability, the complete circuit is re-calibrated at least every three minutes. This procedure can be synchronised by the control in order to prevent the calibration leading to a delay in the production process.

Measuring error

< ±0.1 % (relative to full scale value)

< ±0.01 % (relative to full scale value)

Current consumption

– (no power contacts)

only load

Current consumpt. K-bus typ. 65 mA typ. 85 mA

Internal resistance

> 200 kΩ (UREF), > 1 MΩ (UD)

> 200 kΩ (UREF), > 1 MΩ (UD)

Power supply UV

5 V DC, max. 20 mA via power contacts

Filter

50 Hz, configurable

50 Hz, configurable

Special features with internal bridge supply increased measuring accuracy, self-calibration

Operating temperature

0…+55 °C

0…+55 °C CE, UL, Ex power contacts

Approvals

CE, UL, Ex

Weight approx. 70 g approx. 75 g

Further information www.beckhoff.com/KL3351 www.beckhoff.com/KL3356

Special terminals

KL3351-0001

Distinguishing features with faster measurement time approx. 10 ms

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 108

KL3361, KL3362

Analog Input

Analog input | Oscilloscope 1-channel analog input terminal,

2-channel analog input terminal, oscilloscope, -16…+16 mV oscilloscope, -10…+10 mV

Technical data

KL3361 | KS3361

KL3362 | KS3362

Signal voltage

UIN: -16…+16 mV

-10…+10 V

Resolution

14 bits + sign

Technology high-speed data logger

Conversion time

< 100 µs, configurable (10 µs with fast sampling mode)

high-speed data logger < 100 µs, configurable (10 µs with fast sampling mode)

Number of inputs

1 analog, 1 trigger

2 analog, 1 trigger

+UV

1

5

1

5

2

6

-UB 6

3

7

3

7

Bus Terminal

+UB 2

4

8

4

8

567

-UV

The KL3361 and KL3362 analog input terminals make it possible to perform non-central preliminary processing of analog values. The input values are digitised with a 14-bit resolution and written into an internal memory. An efficient processor can pre-process the values. Limit values, maximum and minimum values will be determined or monitored. The Bus Terminals can also carry out envelope curve monitoring. A trigger starts cyclical processes. The result or all the measured values are transported to the higher-level automation unit.

Measuring error

< ±1 % (relative to full scale value)

< ±0.5 % (relative to full scale value)

Current consumption

– (no power contacts)

– (no power contacts)

Current consumption typ. 120 mA with external DMS power supply, typ. 140 mA typ. 120 mA

K-bus with internal DMS power supply from terminal (4 x 350 Ω)

Internal resistance

> 1 MΩ (UB)

> 500 kΩ

Supply voltage

5 V DC, max. 20 mA

– via the K-bus power contacts

Power supply via the K-bus

Internal memory

32 kbytes

32 kbytes

Special features high-speed strain gauge analysis (for all fieldbuses)

high-speed analog analysis

Operating temperature

0…+55 °C

0…+55 °C

Approvals

CE, UL, Ex

CE, UL, Ex

Weight approx. 55 g approx. 55 g

Further information www.beckhoff.com/KL3361 www.beckhoff.com/KL3362

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Page 109

Analog Input

KL3403

Analog input | Power measurement 3-phase power measurement terminal

Technical data

KL3403 | KS3403

Measuring voltage max. 500 V AC 3~ (ULX-N: max. 288 V AC)

Resolution

16 bits (21 bits, internal)

Technology

3-phase connection technique

Update time

50 ms per measured value preset, free configurable

Number of inputs

3 phases + N

6 500 k

2

L1

40 m

5 500 k

1

KL3403-0010

L2

40 m

Bus Terminal

The KL3403 Bus Terminal enables the measurement of all relevant electrical data of the supply network. The voltage is measured via the direct connection of L1, L2, L3 and N. The current of the three phases L1, L2 and L3 is fed via simple current transformers. All measured currents and voltages are available as root-mean-square values. In the KL3403 version, the effective power and the energy consumption for each phase are calculated. Through the relationship of the root-mean-square values of voltage and current all other information, such as effective power P, apparent power S or phase shift angle cos φ can be derived. For each fieldbus, KL3403 provides a comprehensive network analysis and an energy management option.

568 7

4

L3

40 m

500 k

3

8

Measuring error

0.5 % relative to full scale value (U, I), 1 % calculated value

Current consumption

– (no power contacts)

power contacts Current consumpt. K-bus typ. 115 mA

Measuring procedure true RMS with 64,000 samples/s

Measured values current, voltage, effective power, energy, cos φ, peak values U, I and P, frequency

Measuring current max. 1 A, via measuring max. 5 A (AC/DC), via meas- transformers x A/1 A uring transformers x A/5 A

Electrical isolation

1,500 V (terminal/K-bus)

Special features energy meter, power measurement, True RMS

Operating temperature

0…+55 °C

Approvals

CE, UL

Weight approx. 75 g

Further information www.beckhoff.com/KL3403

Special terminals

KL3403-0020

KL3403-0022

Distinguishing features current path designed for current path and voltage

20 mA, optimised for elec- input designed for 20 mA tronic current transformer

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 110

KL3681

Analog Input

Analog input | Digital multimeter Digital multimeter terminal

KL3681 | KS3681

Measuring voltage

300 mV, 3 V, 30 V, 300 V

Resolution

18 bit + sign in each measurement range

Technology wide-range current and voltage measurement

Update time

0.5 s, 1 s for measuring range selection

Number of inputs

1 voltage; 2 current (10 A/1 A)

5

12.5 M

1

6

0.2

2

3

7

4

8

Measuring error

0.01 % DC voltage measurement at 25 °C

Current consumption

– (no power contacts)

power contacts Current consumpt. K-bus typ. 100 mA

Measuring procedure

DC with arithmetic averaging, AC with true RMS value calculation

Measured values current, voltage

Measuring current

100 mA, 1 A and 10 A via high-current path

Electrical isolation

1,500 V (terminal/K-bus)

Special features automatic measuring range selection

Operating temperature

0…+55 °C

Approvals

CE

Weight approx. 70 g

Further information www.beckhoff.com/KL3681

For availability status see Beckhoff website at: www.beckhoff.com/KL3681

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Bus Terminal

Technical data

3m

The KL3681 Bus Terminal enables measurement of currents and voltages in a wide input range. The measuring ranges are switched automatically, as usual in advanced digital multimeters. There are two current paths available for current measurement. One of them is a high current path for up to 10 A. The current and the voltage measurement facility can be used for DC and AC. The alternating parameters are output as true RMS values. The measurement readings can be read and processed with commercially available fieldbuses. At the same time the KL3681 enables the measuring type and range to be set via the bus. Excellent interference immunity is achieved through the fully electrically isolated design of the electronic measuring system and the dual slope conversion system. High precision and simple, high impedance measurement from 300 mV to 300 V allow the Bus Terminal to be used like a modern digital multimeter. In measuring applications in particular, the voltage to be expected is often not yet known during the planning phase. Automatic adjustment of the measurement range simplifies use and reduces stock levels. The selected measuring type and overload are indicated by LEDs.