The text of a manual · part 12 of 16
Bus Terminal: The modular fieldbus system for automation, pages 111 to 120
Pages 111 to 120 of 156
The original document is the PDF (9.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Beckhoff KL1184, Beckhoff KL2022 and Beckhoff KL2184
Page 111
Analog Input
KM3701
Bus Terminal
Analog input | Pressure measuring
570
The pressure measuring terminals are divided into two groups: differential pressure measurement with the measurement between two connections and relative pressure measurement with duplicate measurement against ambient. The Bus Terminal can be used for measurement of the pressure or also as a replacement for a pressure switch. Through the pressure value in the control unit the switching threshold for a logical linking can be stored as a parameter. Manual setting of the pressure switch in the practice is no longer necessary. The measuring hoses can simply be connected by plugging them into a quick coupling. Normal 4 mm compressed air hoses are used. With the direct integration of the pressure measurement into the Bus Terminal system the installation of a pressure measurement unit including its wiring can be omitted. The pressure measurement terminals are suitable for the measurement of non-aggressive gases. Water or gases which encourage oxidation should not be allowed to get into the Bus Terminal.
1-channel differential pressure measuring terminal -100…+100 hPa
Technical data
KM3701
KM3701-0340
Technology differential pressure measurement
Resolution
0.1 hPa (0.1 mbar) per digit
Number of inputs
1 (differential pressure)
The KM3701 pressure measuring terminal enables direct measurement of pressure differences between two hose connections. The pressure difference is available in the fieldbus as a 16 bit value and can be measured between any points up to an ambient pressure of 10 bar. The status LEDs indicate proper function or errors such as over-range.
Measuring range
-100…+100 hPa up to 340 hPa (340 mbar)
(-100…+100 mbar) Current consumption
– (no power contacts)
power contacts Current consumpt. K-bus typ. 15 mA
Max. overload
500 hPa (500 mbar) differential, 5,000 hPa (5 bar) to ambient
BECKHOFF New Automation Technology
Medium non-aggressive gases
Special features
–
Operating temperature
0…+55 °C
Approvals
CE, UL
Weight approx. 95 g
Further information www.beckhoff.com/KM3701
We reserve the right to make technical changes.
Page 112
KM3702, KM3712
2-channel relative pressure
2-channel relative pressure measuring terminal 7,500 hPa measuring terminal -1,000…+1,000 hPa
KM3702
KM3712
Analog Input relative pressure measurement
2
Bus Terminal
2
571
The KM3702 pressure measuring terminal enables direct measurement of two pressure values at the hose connections. The pressure is determined as a pressure difference to the ambiance of the KM3702 and is available in the fieldbus as a 16 bit value. The status LEDs indicate proper function or errors such as over-range.
The KM3712 pressure measuring terminal enables direct measurement of two negative pressure values at the hose connections. The pressure is determined as a pressure difference to the ambiance of the KM3712 and is available in the fieldbus as a 16 bit value. The status LEDs indicate proper function or errors such as over-range.
0…7,500 hPa (7.5 bar)
-1,000…+1,000 hPa (-1…+1 bar)
– (no power contacts)
– (no power contacts)
typ. 15 mA typ. 15 mA
10,000 hPa (10 bar)
5,000 hPa (5 bar)
non-aggressive gases non-aggressive gases
–
–
0…+55 °C
0…+55 °C
CE, UL
CE, UL approx. 95 g approx. 95 g www.beckhoff.com/KM3702 www.beckhoff.com/KM3712
We reserve the right to make technical changes.
BECKHOFF New Automation Technology
Page 113
Analog Output
KL4031, KL4032
Bus Terminal
Analog output | -10…+10 V
572
The KL4xxx Bus Terminals provide analog signal voltages in the common standard signal range of -10 to +10 V, 0 to 10 V, 0 to 20 mA and 4 to 20 mA. Inside the terminal the field side is electrically isolated from the K-bus and enables the interconnection to the desired potential groups. The 1-channel Bus Terminals are available for application instances, in which each signal must be completely electrically isolated. An additional electrically isolated 24 V DC supply can be created by the introduction of the KL9560 power supply terminal. The Bus Terminals of this group differ in their different resolutions of the analog/ digital conversion, conversion speed and accuracy. For 1- and 2-channel Bus Terminals 1-, 2-, 3- and 4-wire sensor connections are available. 4-channel Bus Terminals can only be used with 1- and 2-wire connections. The current output terminals 0…20 mA and 4…20 mA are fed from the 24 V DC supply and are electrically connected with it. The signal current flows from the output to ground. Most Bus Terminals with voltage outputs are supplied from the internal K-bus. These Bus Terminals are potential-free and must be connected with the actuator through an additional ground wire. In contrast, the KL4404/08 and KL4434/38 Bus Terminals are supplied by the 24 V from the power contacts and use a power contact as a reference ground.
1-channel analog
2-channel analog output terminal, output terminal,
-10…+10 V, 12 bits
-10…+10 V, 12 bits
Technical data
KL4031 | KS4031
KL4032 | KS4032
Signal voltage
-10…+10 V
Resolution
12 bits
Technology
– single-ended
Conversion time
~ 1.5 ms
~ 1.5 ms
Number of outputs
1
2 +60 °C -20 °C
1
5
1
5
2
6
2
6
3
7
3
7
4
8
4
8
The KL4031 analog output terminal generates signals in the range from -10 to +10 V. It combines two output channels, which have a common ground potential in one housing.
The KL4032 analog output terminal generates signals in the range from -10 to +10 V. It combines two output channels, which have a common ground potential in one housing.
< ±0.1 % (relative
< ±0.1 % (relative
KL9570 | Power supply terminal see page 601 Output error to end value)
to end value)
– (no power contacts)
– (no power contacts)
Current consumpt. K-bus typ. 75 mA typ. 75 mA
Load
> 5 kΩ (short-circuit-proof)
> 5 kΩ (short-circuit-proof)
Special features potential-free output
–
Operating temperature
0…+55 °C
-20…+60 °C
Approvals
CE, UL, Ex, GL
CE, UL, Ex, GL
Weight approx. 85 g approx. 85 g
Further information www.beckhoff.com/KL4031
Current consumption power contacts www.beckhoff.com/KL4032
Special terminals
KL4032-00xx
Distinguishing features for special terminals see page
BECKHOFF New Automation Technology
605
We reserve the right to make technical changes.
Page 114
KL4xxx
Analog Output
4-channel analog
4-channel analog
8-channel analog
2-channel analog input,
2-channel analog output terminal, output terminal, output terminal,
2-channel analog output output terminal,
-10…+10 V, 12 bits
-10…+10 V, 12 bits
-10…+10 V, 12 bits terminal, -10…+10 V, 12 bits
-10…+10 V, 16 bits
KL4034 | KS4034
KL4434 | KS4434
KL4438 | KS4438
KL4494 | KS4494
KL4132 | KS4132 single-ended single-ended single-ended single-ended single-ended
~ 2 ms
~ 4 ms
~ 8 ms
< 2ms
~ 1.5 ms
4
4
8
2 outputs + 2 inputs
2
1
5
1
5
1
5
1
5
1
5
2
6
2
6
2
6
2
6
2
6
3
7
3
7
3
7
3
7
3
7
4
8
4
8
4
8
4
8
4
8
Bus Terminal
16 bits
573
The KL4034 analog output terminal generates signals in the range from -10 to +10 V. It combines four output channels, which have a common ground potential in one housing.
The KL4434 analog output terminal generates signals in the range from -10 to +10 V. It combines four output channels, which have a common ground potential in one housing.
The KL4438 analog output terminal generates signals in the range from -10 to +10 V. It combines eight output channels in one housing and is thus particularly suited for space-saving use in the control cabinet. The 0 V power contact serves as the common ground potential.
The KL4494 analog output terminal combines two analog inputs and two analog outputs. The input and output channels of the Bus Terminal have a common ground potential. –
The KL4132 analog output terminal generates signals in the range from -10 to +10 V. It combines two output channels, which have a common ground potential in one housing.
input internal resistance: > 130 kΩ
< ±0.1 % (relative
< ±0.1 % (relative
< ±0.2 % (relative
< ±0.3 % (relative
< ±0.1 % (relative to end value)
to end value)
to end value)
to end value)
to end value)
– (no power contacts)
only load only load only load
– (no power contacts)
typ. 85 mA typ. 20 mA typ. 20 mA typ. 70 mA typ. 75 mA
> 5 kΩ (short-circuit-proof)
> 5 kΩ (short-circuit-proof)
> 5 kΩ (short-circuit-proof)
> 5 kΩ (short-circuit-proof)
> 5 kΩ (short-circuit-proof)
–
– high packing density input/output terminal increased resolution
0…+55 °C
0…+55 °C
0…+55 °C
0…+55 °C
0…+55 °C
CE, UL, Ex, GL
CE, UL, Ex, GL
CE, UL, Ex, GL
CE, UL, Ex
CE, UL, Ex approx. 85 g approx. 75 g approx. 75 g approx. 55 g approx. 85 g www.beckhoff.com/KL4034 www.beckhoff.com/KL4434 www.beckhoff.com/KL4438 www.beckhoff.com/KL4494 www.beckhoff.com/KL4132
KL4034-0010
KL4132-00xx
Siemens S5 format for special terminals see page
We reserve the right to make technical changes.
605
BECKHOFF New Automation Technology
Page 115
Analog Output
KL400x
Analog output | 0…10 V 1-channel analog
2-channel analog
4-channel analog output terminal, output terminal, output terminal,
0…10 V, 12 bits
0…10 V, 12 bits
0…10 V, 12 bits
Technical data
KL4001 | KS4001
KL4002 | KS4002
KL4004 | KS4004
Signal voltage
0…10 V
Resolution
12 bits
Technology
– single-ended single-ended
Conversion time
~ 1.5 ms
~ 1.5 ms
~ 2 ms
Number of outputs
1
2
4
+60 °C
Bus Terminal
-20 °C
1
5
1
5
1
5
2
6
2
6
2
6
3
7
3
7
3
7
4
8
4
8
4
8
574
The KL4001 analog output terminal generates signals in the range from 0 to +10 V. It combines two output channels, which have a common ground potential in one housing.
The KL4002 analog output terminal generates signals in the range from 0 to +10 V. It combines two output channels, which have a common ground potential in one housing.
The KL4004 analog output terminal generates signals in the range from 0 to +10 V. It combines four output channels, which have a common ground potential in one housing.
Output error
< ±0.1 % (relative to end value)
< ±0.1 % (relative to end value)
< ±0.1 % (relative to end value)
Current consumption
– (no power contacts)
– (no power contacts)
– (no power contacts)
Current consumpt. K-bus typ. 75 mA typ. 75 mA typ. 85 mA
Load
> 5 kΩ (short-circuit-proof)
> 5 kΩ (short-circuit-proof)
> 5 kΩ (short-circuit-proof)
Special features potential-free output
–
–
Operating temperature
0…+55 °C
-20…+60 °C
0…+55 °C
Approvals
CE, UL, Ex
CE, UL, Ex
CE, UL, Ex
Weight approx. 85 g approx. 85 g approx. 85 g
Further information www.beckhoff.com/KL4001 www.beckhoff.com/KL4002 www.beckhoff.com/KL4004 power contacts
Special terminals
KL4002-00xx
Distinguishing features special terminals see page
BECKHOFF New Automation Technology
KL4004-0050 605
Siemens S7 format
We reserve the right to make technical changes.
Page 116
KL4404, KL4408
4-channel analog
8-channel analog
2-channel analog output terminal, output terminal, output terminal,
0…10 V, 12 bits
0…10 V, 12 bits
0…10 V, 12 bits,
Analog Output manual/automatic operation KL4408 | KS4408
KM4602 single-ended single-ended single-ended
~ 4 ms
~ 8 ms
~ 1.5 ms
4
8
2
1
5
1
5
2
6
2
6
3
7
3
7
4
8
4
8
Bus Terminal
KL4404 | KS4404
575
The KL4404 analog output terminal generates signals in the range from 0 to +10 V. It combines four output channels, which have a common ground potential in one housing.
The KL4408 analog output terminal generates signals in the range from 0 to +10 V. It combines eight output channels in one housing and is thus particularly suited to space-saving use in the control cabinet. The 0 V power contact serves as the common ground potential.
The analog KM4602 output terminal has two potential-free analog 0…10 V outputs. Both are connected internally to common ground. For each channel a switch enables selection of automatic or manual mode. In automatic mode, an analog value is issued depending on the process data. With the manual switch settings, the value set via the potentiometer is applied to the output. For manual mode a 24 V supply is required for the Bus Coupler. The switch state can be read by the controller.
< ±0.1 % (relative to end value)
< ±0.2 % (relative to end value)
< ±0.1 % (relative to end value)
only load only load
– (no power contacts)
typ. 20 mA typ. 20 mA typ. 75 mA
> 5 kΩ (short-circuit-proof)
> 5 kΩ (short-circuit-proof)
> 5 kΩ (short-circuit-proof)
– high packing density manual/automatic operation
0…+55 °C
0…+55 °C
0…+55 °C
CE, UL, Ex, GL
CE, UL, Ex, GL
CE approx. 75 g approx. 75 g approx. 85 g www.beckhoff.com/KL4404 www.beckhoff.com/KL4408 www.beckhoff.com/KM4602
We reserve the right to make technical changes.
BECKHOFF New Automation Technology
Page 117
Analog Output
KL4011, KL4012
Analog output | 0…20 mA 1-channel analog
2-channel analog output terminal, output terminal,
0…20 mA, 12 bits
0…20 mA, 12 bits
Technical data
KL4011 | KS4011
KL4012 | KS4012
Signal current
0…20 mA
Resolution
12 bits
Technology single-ended single-ended
Conversion time
~ 1.5 ms
~ 1.5 ms
Number of outputs
1
2
+60 °C
Bus Terminal
-20 °C
1
5
1
5
2
6
2
6
3
7
3
7
4
8
4
8
576
The KL4011 analog output terminal generates analog output signals in the range from 0 to 20 mA.
The KL4012 analog output terminal generates signals in the range from 0 to 20 mA. It combines two output channels, which have a common ground potential with the 24 V DC supply, in one housing. The output stages are powered by the 24 V DC supply.
Output error
< ±0.1 % (relative to end value)
< ±0.1 % (relative to end value)
Current consumption typ. 30 mA + load typ. 50 mA + load power contacts Current consumpt. K-bus typ. 60 mA typ. 60 mA
Load
< 500 Ω
< 500 Ω
Power supply
24 V DC via power contacts (alternative 15 V DC
24 V DC via power contacts (alternative 15 V DC with power supply terminal KL9515)
with power supply terminal KL9515)
Special features
–
–
Operating temperature
0…+55 °C
-20…+60 °C
Approvals
CE, UL, Ex, GL
CE, UL, Ex, GL
Weight approx. 80 g approx. 80 g
Further information www.beckhoff.com/KL4011 www.beckhoff.com/KL4012
Special terminals
KL4012-00xx
Distinguishing features special terminals see page
BECKHOFF New Automation Technology
605
We reserve the right to make technical changes.
Page 118
KL441x, KL41112
Analog Output
4-channel analog
8-channel analog
2-channel analog output terminal, output terminal, output terminal,
0…20 mA, 12 bits
0…20 mA, 12 bits
0…20 mA, 15/16 bits
KL4414 | KS4414
KL4418 | KS4418
KL4112 | KS4112 single-ended single-ended single-ended
~ 4 ms
~ 8 ms
~ 3.5 ms
4
8
2
1
5
1
5
1
5
2
6
2
6
2
6
3
7
3
7
3
7
4
8
4
8
4
8
Bus Terminal
15 bit, configurable to 16 bit
577
The KL4414 analog output terminal generates signals in the range from 0 to 20 mA. It combines four channels, which have a common ground potential in one housing. The output stages are powered by the 24 V DC supply.
The KL4418 analog output terminal generates signals in the range from 0 to 20 mA. It combines eight output channels in one housing and is thus particularly suited to space-saving use in the control cabinet. The 0 V power contact serves as the common ground potential.
The KL4112 analog output terminal generates signals in the range from 0 to 20 mA. It combines two output channels, which have a common ground potential with the 24 V DC supply, in one housing. The output stages are powered by the 24 V DC supply.
< ±0.1 % (relative to end value)
< ±0.2 % (relative to end value)
< ±0.1 % (relative to end value)
typ. 60 mA + load typ. 60 mA + load typ. 50 mA + load typ. 20 mA typ. 20 mA typ. 60 mA
< 350 Ω (short-circuit-proof)
< 150 Ω (short-circuit-proof)
< 500 Ω
24 V DC via power contacts (alternative 15 V DC
24 V DC via power contacts (alternative 15 V DC
24 V DC via power contacts (alternative 15 V DC with power supply terminal KL9515)
with power supply terminal KL9515)
with power supply terminal KL9515)
– high packing density increased resolution
0…+55 °C
0…+55 °C
0…+55 °C
CE, UL, Ex, GL
CE, UL, Ex, GL
CE, UL, Ex approx. 75 g approx. 75 g approx. 80 g www.beckhoff.com/KL4414 www.beckhoff.com/KL4418 www.beckhoff.com/KL4112 KL4112-00xx special terminals see page
We reserve the right to make technical changes.
605
BECKHOFF New Automation Technology
Page 119
Analog Output
KL4021, KL4022
Analog output | 4…20 mA 1-channel analog output terminal,
2-channel analog output terminal,
4…20 mA, 12 bits
4…20 mA, 12 bits
Technical data
KL4021 | KS4021
KL4022 | KS4022
Signal current
4…20 mA
Resolution
12 bits
Technology single-ended single-ended
Conversion time
~ 1.5 ms
~ 1.5 ms
Number of outputs
1
2
+60 °C
Bus Terminal
-20 °C
1
5
1
5
2
6
2
6
3
7
3
7
4
8
4
8
578
The KL4021 analog output terminal generates analog output signals in the range from 4 to 20 mA.
The KL4022 analog output terminal generates signals in the range from 4 to 20 mA. It combines two output channels, which have a common ground potential with the 24 V DC supply, in one housing. The output stages are powered by the 24 V DC supply.
Output error
< ±0.1 % (relative to end value)
< ±0.1 % (relative to end value)
Current consumption typ. 30 mA + load typ. 50 mA + load power contacts Current consumpt. K-bus typ. 60 mA typ. 60 mA
Load
< 500 Ω
< 500 Ω
Power supply
24 V DC via power contacts (alternative 15 V DC
24 V DC via power contacts (alternative 15 V DC with power supply terminal KL9515)
with power supply terminal KL9515)
Special features
–
–
Operating temperature
0…+55 °C
-20…+60 °C
Approvals
CE, UL, Ex, GL
CE, UL, Ex, GL
Weight approx. 80 g approx. 80 g
Further information www.beckhoff.com/KL4021 www.beckhoff.com/KL4022
Special terminals
KL4022-00xx
Distinguishing features special terminals see page
BECKHOFF New Automation Technology
605
We reserve the right to make technical changes.
Page 120
KL4424, KL4428
8-channel analog output terminal,
4…20 mA, 12 bits
4…20 mA, 12 bits
KL4424 | KS4424
KL4428 | KS4428 single-ended single-ended
~ 4 ms
~ 8 ms
4
8
1
5
1
5
2
6
2
6
3
7
3
7
4
8
4
8
Bus Terminal
4-channel analog output terminal,
Analog Output
579
The KL4424 analog output terminal generates signals in the range from 4 to 20 mA. It combines four channels, which have a common ground potential in one housing. The output stages are powered by the 24 V DC supply.
The KL4428 analog output terminal generates signals in the range from 4 to 20 mA. It combines eight output channels in one housing and is thus particularly suited to space-saving use in the control cabinet. The 0 V power contact serves as the common ground potential.
< ±0.1 % (relative to end value)
< ±0.2 % (relative to end value)
typ. 60 mA + load typ. 60 mA + load typ. 20 mA typ. 20 mA
< 350 Ω (short-circuit-proof)
< 150 Ω (short-circuit-proof)
24 V DC via power contacts (alternative 15 V DC
24 V DC via power contacts (alternative 15 V DC with power supply terminal KL9515)
with power supply terminal KL9515)
– increased packing density
0…+55 °C
0…+55 °C
CE, UL, Ex, GL
CE, UL, Ex, GL approx. 75 g approx. 75 g www.beckhoff.com/KL4424 www.beckhoff.com/KL4428
We reserve the right to make technical changes.
BECKHOFF New Automation Technology