For the Beckhoff KL1184, Beckhoff KL2022 and Beckhoff KL2184
Page 121
Position measurement
KL5001, KL5051
Bus Terminal
Position measurement | SSI encoder interface
580
The KL5001 SSI interface terminal enables the direct connection of an SSI encoder that is powered via the SSI interface. The interface circuit generates a pulse for reading the encoder and makes the incoming data stream available to the controller as a data word in the process image. Various operating modes, transmission frequencies and bit widths can be permanently stored in a control register. A screen can be connected via the KL9195 shield terminal. The KL5051 bidirectional SSI interface terminal enables the connection of digital servo drives. The encoder is powered via the SSI interface, which consists of two logic channels. The first channel us used for the positioning of the drive, while the second channel is used to set releases, to transmit parameter data and to read status information and parameter values. The 5 V DC supply voltage can be generated with the KL9505 power supply terminal and fed into the power contacts.
SSI encoder interface
Bidirectional SSI encoder interface
Technical data
KL5001 | KS5001
KL5051 | KS5051
Technology
SSI encoder interface
Data direction read bidirectional
Number of channels
1 encoder interface
1 encoder interface
Encoder connection binary input: D+, D-, binary input: D+, D-, binary output: Cl+, Cl- binary output: Cl+, Cl+60 °C -20 °C
KL9195 | Shield terminal see page 595 KL9505 | Power supply terminal see page 600
Power supply
1
5
+24 V
2
6
0V
3
7
4
8
24 V DC via power contacts
1
5
+5 V
2
6
0V
3
7
4
8
5 V DC via power contacts (KL9505)
Current consumption typ. 20 mA + load no data
Current consumpt. K-bus typ. 25 mA typ. 75 mA
Signal input difference signal (RS422)
difference signal (RS422)
Signal output difference signal (RS422)
difference signal (RS422)
Encoder supply
24 V DC via power contacts
5 V DC
Data transfer rates variable up to 1 MHz,
1 MHz power contacts
250 kHz default
BECKHOFF New Automation Technology
Special features
– bidirectional
Operating temperature
-20…+60 °C
0…+55 °C
Approvals
CE, UL, Ex
CE, UL, Ex
Weight approx. 60 g approx. 80 g
Further information www.beckhoff.com/KL5001 www.beckhoff.com/KL5051
We reserve the right to make technical changes.
Page 122
KL5121
Position measurement
Position measurement | Incremental encoder interface Incremental encoder interface with programmable outputs
Technical data
KL5121 | KS5121
Technology incremental encoder interface with programmable outputs
Number of channels
1 incremental encoder + 4 outputs
Encoder connection
A, B, latch, gate
1
5
1’
5’
2
6
2’
6’
3
7
3’
7’
4
8
4’
8’
Bus Terminal
The KL5121 can be used to implement a linear path control. The terminal reads an incremental signal supplied by an incremental encoder or a pulse generator and switches the outputs at predefined counter states. The counter states can be transmitted to the terminal by the higher-level automation device in the form of a table. The position is registered with the latch input, which is activated/deactivated by the gate input. Up to four 24 V outputs can be switched. The LEDs indicate the states of the signals at the various inputs and outputs. The KL5121 is particularly suitable for applications that are dependent on a short response time. The K-Bus cycle time, the fieldbus runtime and the processing speed of the controller are of no importance for the fast and accurate processing of positional data, since the Bus Terminal always switches the outputs with a constant time delay, irrespective of the control environment.
581
Power supply
24 V DC (-15 %/+20 %)
Current consumption typ. 30 mA + load power contacts
We reserve the right to make technical changes.
Current consumpt. K-bus typ. 30 mA
Encoder operating voltage
24 V DC
Counter
16 bits, binary
Limit frequency
1 million increments/s (with 4-fold evaluation)
Output voltage
24 V
Output current
0.5 A
Switching times
< 100 µs
Special features electronic camshaft controller
Operating temperature
0…+55 °C
Approvals
CE, UL, Ex
Weight approx. 60 g
Further information www.beckhoff.com/KL5121
BECKHOFF New Automation Technology
Page 123
Position measurement
KL5101
Bus Terminal
Position measurement | Incremental encoder interface
582
The KL5101 Bus Terminal processes differential signals according to the RS422/RS485 standard. This transmission type is particularly resistant to interference and is suitable for high transmission frequencies. The KL5111, KL5151 and KL5152 Bus Terminals have a single-ended input and are simple to wire up. The signal frequencies from less time-critical applications can be processed using these terminals. All incremental encoder terminals use a quadrature decoder. Gate and latch inputs enable pre-processing in the Bus Terminal in order to be able to transfer positional values to the controller exactly upon an external event and thus support the referencing of a drive. The KL5101 and KL5111 make a period duration measurement available with a resolution of 200 ns. Rotary speeds can thus be determined directly, since a calculation of the speed by means of position differences in the controller is in many cases not accurate enough due to jitter. The KL5152 contains two encoders and provides a particularly inexpensive solution for a large number of channels if gate and latch functions are not needed. The LEDs on the Bus Terminals indicate the states of the input signals for better diagnosis.
1-channel incremental encoder interface, 16 bits, differential inputs, RS485
Technical data
KL5101 | KS5101
Technology incremental encoder interface (RS485)
Number of channels
1 incremental encoder + 1 input
Encoder connection
A, A (inv), B, B (inv), zero, zero (inv), difference signal (RS485); status input +60 °C -20 °C
1
5
1’
5’
2
6
2’
6’
3
7
3’
7’
4
8
4’
8’
The KL5101 terminal is an interface for the direct connection of incremental encoders with difference signal (RS485) or with single inputs. A 16 bit counter with a quadrature decoder and a 16 bit latch for the zero pulse can be read, set or enabled. Interval measurement with a resolution of 200 ns is possible. The G2 input allows the counter to be halted (high = stop). The value is read with a rising edge at G1. Power supply
24 V DC (-15 %/+20 %)
Current consum. pow.cont.
– (no power contacts)
Current consumpt. K-bus typ. 60 mA
Encoder operating voltage
5 V DC
Encoder output current
0.5 A
Counter
16 bits, binary
Limit frequency
4 million increments/s (with 4-fold evaluation)
Quadrature decoder
1-, 2-, or 4-fold evaluation
Zero-pulse latch
16 bits
Commands read, set, enable
Special features
–
Operating temperature
-20…+60 °C
Approvals
CE, UL, Ex
Weight approx. 85 g
Further information www.beckhoff.com/KL5101
Special terminals Distinguishing features
BECKHOFF New Automation Technology
We reserve the right to make technical changes.
Page 124
KL5111, KL515x
Position measurement
1-channel incremental encoder interface,
1-channel incremental encoder interface,
2-channel incremental encoder interface,
16 bits, single-ended, 24 V DC
32 bits, single-ended, 24 V DC
32 bits, single-ended, 24 V DC
KL5111 | KS5111
KL5151 | KS5151
KL5152 | KS5152 incremental encoder interface, 24 V DC 1 incremental encoder
2 incremental encoders
A, B, C; 24 V (low: < 3 V, high: > 18 V)
A, B, C, gate/latch, 24 V
A1, B1, A2, B2, 24 V
+60 °C
1
5
1
5
1
5
2
6
2
6
2
6
3
7
3
7
3
7
4
8
4
8
4
8
Bus Terminal
-20 °C
583
The KL5111 Bus Terminal is an interface for the direct connection of 24 V incremental encoders. A 16 bit counter with a quadrature decoder and a 16 bit latch for the zero pulse can be read, set or enabled. The state of the counter is transmitted quickly and securely to the PC, PLC or CNC over the fieldbus. Interval measurement with a resolution of 200 ns is possible.
The KL5151 Bus Terminal is an interface with 24 V inputs for the direct connection of incremental encoders. A 32 bit counter with a quadrature decoder and a 32 bit latch for the zero pulse can be read, set or enabled. The KL5151 inputs can optionally be used as single or two-counter inputs.
The KL5152 Bus Terminal is an interface with 24 V inputs for the direct connection of incremental encoders. Two 32 bit counters with quadrature decoders can be read or set.
24 V DC (-15 %/+20 %)
24 V DC (-15 %/+20 %)
24 V DC (-15 %/+20 %)
–
–
– typ. 40 mA typ. 40 mA typ. 40 mA
24 V DC
24 V DC
24 V DC
–
–
–
16 bits, binary
32 bits, binary
32 bits, binary
1 million increments/s (with 4-fold evaluation)
400,000 increments/s (with 4-fold evaluation)
400,000 increments/s (with 4-fold evaluation)
4-fold evaluation
4-fold evaluation
4-fold evaluation
16 bits
32 bits
– read, set, enable read, set, enable read
–
–
–
0…+55 °C
-20…+60 °C
0…+55 °C
CE, UL, Ex
CE, UL, Ex
CE, UL, Ex approx. 60 g approx. 50 g approx. 50 g www.beckhoff.com/KL5111 www.beckhoff.com/KL5151 www.beckhoff.com/KL5152
KL5111-00xx
KL5151-0021 for special terminals see page
605 incremental encoder 1 x 32 bits A, B, capture input and 1 driver output 24 V, 0.5 A
We reserve the right to make technical changes.
BECKHOFF New Automation Technology
Page 125
Communication
KL6001, KL6031
Communication | Serial interfaces Serial interface RS232,
Serial interface RS232, up to 19,200 baud up to 115.2 kbaud
Technical data
KL6001 | KS6001
KL6031 | KS6031
Technology
RS232
Data transfer rates
1,200…19,200 baud;
4,800…115,200 baud;
default: 9,600 baud, 8 data default: 9,600 baud, 8 data bits, no parity and one stop bit bits, no parity and one stop bit
2 (1/1), TxD and RxD,
2 (1/1), TxD and RxD, full duplex full duplex
Data transfer channels
+60 °C -20 °C
1
5
1
5
2
6
2
6
Bus Terminal
The KL60xx serial interfaces enable the connection of devices with RS232 or RS422/ RS485 interfaces to the control level. The devices connected to the Bus Terminals communicate via the coupler and the network with the automation device. The active communication channel operates independently of the higher-level bus system in full duplex mode at up to 115.2 kbaud. This way, any desired number of serial interfaces can be used in the application without having to consider structural restrictions in the control device. The serial interface can be positioned close to the place of use, this way reducing the necessary cable lengths. The RS232 interface enables high resistance to interference by means of electrically isolated signals, which in the case of the KL6021 is additionally supported by differential signal transmission according to RS422.
3
7
3
7
584
4
8
4
8
The KL6001 and KL6031 serial interfaces allow devices with an RS232 interface to be connected. The interface operates in conformity with the CCITT V.28/DIN 66 259-1 standards. The active communication channel operates independently of the higher-level bus system in full duplex mode at up to 19,200 baud (KL6001) or 115.2 kbaud (KL6031). The RS232 interface guarantees high immunity to interference through electrically isolated signals. Data buffer
128 bytes receive buffer,
1024 bytes receive buffer,
16 bytes transmit buffer
128 bytes transmit buffer
– (no power contacts)
– (no power contacts)
Current consumpt. K-bus typ. 55 mA typ. 55 mA
Cable length max. 15 m max. 15 m
Line impedance
–
–
Special features high interference immunity, high interference immunity, electrically isolated signals electrically isolated signals
Operating temperature
0…+55 °C
-20…+60 °C
Approvals
CE, UL, Ex
CE, UL, Ex
Weight approx. 80 g approx. 80 g
Further information www.beckhoff.com/KL6001 www.beckhoff.com/KL6031
Special terminals
KL6001-0020
Distinguishing features standard format 5 bytes
Current consumption power contacts of user data
BECKHOFF New Automation Technology
We reserve the right to make technical changes.
Page 126
KL60xx
Communication
Serial interface RS422/RS485,
Serial interface RS422/RS485,
Serial interface TTY,
Data exchange terminal up to 19,200 baud up to 115.2 kbaud
20 mA current loop with serial interface
KL6021 | KS6021
KL6041 | KS6041
KL6011 | KS6011
KL6051 | KS6051
TTY
2 x RS422
RS422/RS485 1,200…19,200 baud;
4,800…115,200 baud;
1,200…19,200 baud;
62,500 baud, 32 bits bidirectional default: 9,600 baud, 8 data bits, default: 9,600 baud, 8 data bits, default: 9,600 baud, 8 data bits, data exchange between two KL6051 no parity and one stop bit no parity and one stop bit no parity and one stop bit
TxD and RxD, full/half duplex
TxD and RxD, full/half duplex
2 (1/1), TxD and RxD, full duplex
TxD and RxD, full duplex
+60 °C
1
5
1
5
1
5
1
5
2
6
2
6
2
6
2
6
3
7
3
7
3
7
3
7
Bus Terminal
-20 °C
4
8
4
8
4
8
4
8
585
The KL6021 and KL6041 serial interfaces allow devices with an RS422 or RS485 interface to be connected. The active communication channel operates independently of the higher-level bus system in full or half duplex mode at up to 19,200 baud (KL6021) or 115.2 kbaud (KL6041). The transmission of differential signals conforms to RS422 and guarantees high immunity to interference through electrically isolated signals.
The KL6011 serial interface allows devices with a 20 mA current interface to be connected. The interface operates passively. The current interface (TTY) guarantees high immunity to interference through electrically isolated signals with injected current.
Under the terminal’s default setting, 32 inputs and 32 outputs are transferred between the fieldbus systems. The time to exchange the data is about 5 ms for 32 bits of I/O. The exchange of data with the Bus Coupler is indicated by the run LED. The TxD and RxD LEDs indicate the state of the signal transmission.
128 bytes receive buffer,
1024 bytes receive buffer,
128 bytes receive buffer,
32 bit bidirectional
16 bytes transmit buffer
128 bytes transmit buffer
16 bytes transmit buffer
– (no power contacts)
– (no power contacts)
– (no power contacts)
– (no power contacts)
typ. 65 mA typ. 65 mA typ. 55 mA typ. 65 mA approx. 1,000 m twisted pair approx. 1,000 m twisted pair max. 1,000 m twisted pair approx. 1,000 m twisted pair
120 Ω
120 Ω
–
120 Ω high interference immunity, high interference immunity,
2 x 20 mA bit transfer automatic data exchange electrically isolated signals electrically isolated signals
0…+55 °C
-20…+60 °C
0…+55 °C
0…+55 °C
CE, UL, Ex
CE, UL, Ex
CE, UL, Ex
CE, UL, Ex approx. 60 g approx. 60 g approx. 60 g approx. 60 g www.beckhoff.com/KL6021 www.beckhoff.com/KL6041 www.beckhoff.com/KL6011 www.beckhoff.com/KL6051
KL6021-002x special terminals see
KL6011-0020 605
We reserve the right to make technical changes.
standard format 5 bytes of user data
BECKHOFF New Automation Technology
Page 127
Communication
KL6201, KL6211
Communication | AS-Interface
Bus Terminal
The AS-Interface master terminal is an extended master according to the M3 profile and enables the direct connection of AS-Interface slaves. The AS-compliant interface supports digital and analog slaves with the versions 2.0 and 2.1, safety slaves and slaves with Combined Transaction Type 1 (profile S-7.3 and 7.4). Process data exchange, parameterisation and the diagnosis are fieldbus-independent. Together with the various Bus Couplers, the KL6201 or the KL6211 represents a universal AS-Interface/ fieldbus gateway. Together with the BK3120, the PROFIBUS DP V1 services can be used for communication with the KL6201 or the KL6211. Unlike the KL6201 AS-Interface master terminal, the KL6211 features power contacts. This enables direct connection to the AS-Interface supply via the KL9520 AS-Interface potential feed terminal or the KL9528 power supply terminal.
AS-Interface
AS-Interface master terminal master terminal with power contacts
Technical data
KL6201 | KS6201
Technology
AS-Interface
Cycle time max. 5 ms (31 devices)
Number of channels
1
KL9520, KL9528 | AS-Interface system terminals see page 602
KL6211 | KS6211
1
1
5
2
6
3
7
4
8
Mode
1
5
ASi+
2
6
ASi–
3
7
4
8
Mode
Set
Set
Mode
Mode
Set
Set
586
AS-Interface versions
V 2.0 and V 2.1
V 2.0 and V 2.1
Current consumption
– (no power contacts)
typ. 60 mA + load
Current consumption typ. 55 mA (K-bus), typ. 55 mA (K-bus),
K-bus approx. 60 mA (AS-Interface)
approx. 60 mA (AS-Interface)
Number of slaves
31 for V 2.0, 62 for V 2.1
31 for V 2.0, 62 for V 2.1
Slave types digital and analog digital and analog
AS-Interface address via configuration via configuration assignment or automatic or automatic
Diagnostics power failure, slave failure, power failure, slave failure, parameterisation fault parameterisation fault
2 lines via spring force
2 lines via spring force technology technology
Operating temperature
0…+55 °C
0…+55 °C
Approvals
CE
CE
Weight approx. 55 g approx. 55 g
Further information www.beckhoff.com/KL6201 www.beckhoff.com/KL6211
Special terminals
KL6201-0010
Distinguishing features for special terminals power contacts
Connection see page
BECKHOFF New Automation Technology
607
We reserve the right to make technical changes.
Page 128
KM6551
Communication
Communication | Wireless data exchange Wireless data exchange terminal
Technical data
KM6551
Technology wireless data exchange
Data transfer rates
250 kbit
Number of channels
1 radio connection
Bus Terminal
The KM6551 terminal module is a data exchange unit for radio technology. The KM module is based on the IEEE802.15.4 standard. Data are exchanged or transferred via radio between two stand-alone control units, independent of the higher-level fieldbus. The outdoor range between two KM6551 units can be up to 300 m. The data exchange module has a reverse SMA plug (Straight Medium Adapter) for connection of various radio antennas. The free choice of antenna enables adaptation to the respective environment. Status and data exchange are displayed via LEDs, thereby offering fast and simple diagnostics. A library is available for using the KM6551 module with TwinCAT.
Option 1 | Data exchange peer-to-peer
587 send output data send input data Slave
Master
Option 2 | Data exchange up to max. 7 devices Master
Protocol
IEEE 802.15.4
Current consumption
– (no power contacts)
power contacts
Slave 1
Slave 2
Slave 3
Slave 4
Slave 5
Slave 6
Slave 7
Option 3 | Broadcast up to x devices
Current consumpt. K-bus typ. 135 mA
Frequency band
2.4 GHz
Antenna connection reverse SMA plug (RP-SMA)
Operating temperature
0…+55 °C
Approvals
CE, UL
Weight approx. 85 g
Further information www.beckhoff.com/KM6551
Accessories Master
...
Slave 1
Slave 2
Slave 3
Slave 4
Slave 5
We reserve the right to make technical changes.
Slave x
ZS6200-0400 omni-directional antenna 4 dBi
ZS6100-0900 directional antenna 9 dBi
614
ZS6201-0410 rod antenna 4 dBi
615
ZS6201-0500 rod antenna 5 dBi
615
ZS6100-1800 directional antenna 18 dBi
615
ZK6000-0102-0020 coaxial cable, 50 Ω impedance, 2 m
615
ZK6000-0102-0040 coaxial cable, 50 Ω impedance, 4 m
615
614
BECKHOFF New Automation Technology
Page 129
Communication
KL6xxx
Communication | EnOcean, IO-Link, EIB EnOcean master terminal
EnOcean transmitter and receiver
Serial interface for processing signals from the KL6023 wireless adapter with EnOcean radio technology
Technical data
KL6581
KL6583
KL6021-0023
Technology
EnOcean
Data transfer rates
125 kbaud
–
9,600 baud
Number of channels
1
–
1
EnOcean
1
7
8
KL6583 … KL6583 KL6583
KL6023
A B 1
5
+24 V
2
6
0V
3
7
+24 V
+RxD
Bus Terminal
0V
GND
1
5
2
6
3
7
4
8
2 -RxD 6 max. 500 m
4
+5 V
8 max. 300 m
588
The bidirectional EnOcean technology receives signals from battery-less sensors or transmits data to actuators. With a radio signal range of 30 m, the wiring of buildings can be simplified significantly. The KL6581 EnOcean master terminal is the link between up to eight KL6583 EnOcean transmitter and receiver modules and the application.
The KL6583 EnOcean module enables EnOcean data to be transmitted and received. An antenna is integrated in the device. The KL6583 module is supplied with 24 V and offers a bus connection to the KL6581 EnOcean master terminal. The KL6583 is addressed via an address selection switch. Up to eight KL6583 modules can be connected to a KL6581.
Nominal voltage
24 V DC (-15 %/+20 %)
24 V DC (via KL6581)
–
Current consum. pow.cont.
typ. 20 mA + load typ. 20 mA (24 V DC)
– (no power contacts)
Current consumpt. K-bus typ. 60 mA
– typ. 65 mA
Cable length max. 500 m max. 500 m max. 300 m
Connection
2 x 2-wires directly at the KL6583
2 x 2-wires directly
2 x 2-wires directly
(connection of max. 8 KL6583)
at the KL6581 Bus Terminal at the KL6023 EnOcean module
Data transfer standard
– bidirectional
–
Frequency band
–
868.35 MHz
–
Data transfer range
–
300 m in the free field,
–
The KL6021-0023 serial interface enables connection of a KL6023 wireless adapter. It processes the RS485 signals of the wireless adapter.
30 m within buildings Special features up to 8 KL6583 EnOcean transmitter connection to KL6581 EnOcean master and receiver modules high interference immunity, electrically isolated signals
Operating temperature
0…+55 °C
0…+55 °C
0…+55 °C
Approvals
CE
CE
CE
Weight approx. 85 g approx. 90 g approx. 60 g
Further information www.beckhoff.com/KL6581 www.beckhoff.com/KL6583 www.beckhoff.com/KL6021
BECKHOFF New Automation Technology
We reserve the right to make technical changes.
Page 130
KL6xxx
Communication
EIB Wireless adapter for EnOcean
IO-Link master terminal
EIB Bus Terminal radio technology
KL6023
–
Technical data
KL6224
KL6301 | KS6301
Technology
IO-Link
EIB
Data transfer rates
4.8 kbaud, 38.4 kbaud
9,600 baud and 230.4 kbaud –
Number of channels
4
1
IO
The KL6023 Wireless Adapter receives signals from battery-less sensors with EnOcean technology. These signals are converted by the Wireless Adapter to a RS485 signal and directly processed further by the KL6021-0023 serial Bus Terminal. The system does not limit the number of transmitters per receiver unit. In practice, between 25 and 100 transmitters per receiver are used.
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
1
5
2
6
3
7
4
8
Set
Set
IO +EIB
IO -EIB
IO Shield
589
The IO-Link terminal enables connection of up to four IO-Link devices. A point-to-point connection is used between the terminal and the device. The terminal is parameterised via the master. 2-wire and 3-wire connections are supported. Additional 24 V and 0 V connection points can be realised via the KL918x potential distributor terminal.
The KL6301 EIB Bus Terminal is integrated in an EIB network and can receive/transmit data from/to other EIB devices. The Bus Terminal is commissioned or configured via TwinCAT function blocks. Several KL6301 can be used with a single Bus Coupler or a Bus Terminal Controller. Up to 256 group addresses can be received; sending is only limited by the application.
via KL6021-0023 – – max. 300 m 2 x 2-wires directly at the KL6021-0023 Bus Terminal
Nominal voltage
24 V DC (-15 %/+20 %)
24 V DC (-15 %/+20 %)
unidirectional
Current consumption no data
–
868.35 MHz power contacts
300 m in the free field,
Current consumpt. K-bus typ. 85 mA typ. 55 mA
30 m within buildings
Data transfer standard
– twisted pair (TP)
connection to KL6021-0023
Bus access
–
CSMA/CA serial interface
Special features
–
TwinCAT library available
0…+55 °C
Operating temperature
0…+55 °C
0…+55 °C
CE
Approvals
CE
CE, Ex approx. 55 g
Weight approx. 60 g approx. 85 g www.beckhoff.com/KL6023
Further information www.beckhoff.com/KL6224 www.beckhoff.com/KL6301
For availability status see Beckhoff website at: www.beckhoff.com/KL6224