Page 81
Digital Output
KL2612, KL2641
Bus Terminal
Digital output | Relay outputs up to 400 V AC
540
The Bus Terminals switch a relay as a function of the bits in the process image. The relays completely isolate the current flow by a mechanical contact; there is no residual current through the open contact. The Bus Terminals are not equipped with a protective circuit, so as not to allow for residual current by parallel switched components. The relay contacts differ in their contact material. Signal contacts also switch small voltages and currents; large current here lead to a change in the contact characteristics. Power contacts can switch large loads. A oxide layer on the power contacts prevents safe contact for small voltages below 1 V DC. Switching on is accompanied by a bouncing. The electrical connection is initially switched on and off briefly, until the contact is securely in its closed location. With an inductive load (coil) this behaviour leads to a spark and to corresponding electromagnetic radiation. Capacitive loads create a short-circuit for a brief period of time. This can – particularly with alternating voltages – lead to such high switch-on currents at switch-on under peak value that the bouncing contact is burned shut. A capacitive load can also be electronic devices, which are typically equipped with a rectifier in the input and a relatively large smoothing capacitor. Electronic ballast is especially critical for fluorescent lamps. The maximum switch-on currents of the devices, which should be observed, are shown in the technical data numerous times. The switch-off of a relay takes place by mechanical opening the contact. An arc burns for a short moment and warms the contact. For an inductive load (coil) a large part of the magnetic energy stored in the coil is additionally released as heat at the contact. This load on the contact determines the service life of the relay and is called the electrical service life. The mechanical service life is defined as the number of switching operations without current flow through the contact.
2-channel relay
1-channel relay output terminal, output terminal,
125 V AC
230 V AC, bistable, manual operation
Technical data
KL2612
KL2641
Load type ohmic ohmic, inductive, lamp load
Max. output current
2A
16 A
Number of outputs
2 x change-over
1 make contact
1
5
2
6
3
7
4
8
The KL2612 Bus Terminal is equipped with potentialfree contacts.
Nominal voltage
125 V AC/30 V DC
1
2
3
4
The KL2641 output terminal has a relay with a single contact, which can be used universally for the switching of mains voltage consumers. The relay can optionally be switched in manual or automatic mode. 230 V AC (max. switching voltage 440 V AC)
Current consum. pow.cont.
– (no power contacts)
typ 65 mA + load
Current consumpt. K-bus typ. 60 mA typ. 5 mA
Switching current
0.5 A AC/2 A DC (ohmic)
16 A AC
Operat. cycles mech. (min.)
1 x 108
1 x 106
Operat. cycles electr. (min.)
5
2 x 10 (1 A/30 V DC)
no data
Lamp test, max. 2 A starting current max. 16 A starting current
Minimum permitted load
10 µA at 10 mV
–
Special features signal relay manual operation;
Operating temperature
0…+55 °C
0…+55 °C
Approvals
CE, UL, GL
CE
Weight approx. 80 g approx. 110 g
Further information www.beckhoff.com/KL2612 www.beckhoff.com/KL2641 electronic ballast bistable relay contact
BECKHOFF New Automation Technology
We reserve the right to make technical changes.
Page 82
KL26xx
Digital Output
2-channel relay
2-channel relay
2-channel relay
1-channel relay output terminal, output terminal, output terminal, output terminal,
230 V AC
230 V AC
230 V AC, 300 V DC
400 V AC, 300 V DC
KL2602 | KS2602
KL2622 | KS2622
KL2652 | KS2652
KL2631 | KS2631
5A
2A
…230 V AC
2 x make contacts
2 x change-over
+60 °C
+60 °C
-20 °C
-20 °C
1
5
1
5
1
5
2
6
2
6
2
6
3
7
3
7
3
4
8
4
8
4
1 x make contacts for power contact
1
5
2
6
7
3
7
8
4
8
…400 V AC
Bus Terminal
2 x make contacts for power contact
541
The KL2602 output terminal has two relays each of which has a single contact. The relay contact is connected to the power contacts, which are suitable for use at up to 230 V AC, and can be generally used for switching devices requiring mains power.
The KL2622 Bus Terminal has potential-free contacts; the power contacts are not looped through.
230 V AC/30 V DC
230 V AC/30 V DC
The KL2652 output terminal has two relays each with a changeover contact, which can be used universally for the switching of mains voltage consumers of 230 V AC or 300 V DC. The KL2652 Bus Terminal is equipped with potential-free contacts.
The KL2631 output terminal has a relay with a single contact, which is connected with the power contacts (usable up to 400 V AC) and can be used universally for the switching of mains voltage consumers. In order to use high voltages of up to 400 V AC, the KL2631 must be supplied via the KL9190 power feed terminal.
230 V AC (max. switching voltage
400 V AC/300 V DC
250 V AC/300 V DC) only load
–
– (no power contacts)
typ. 80 mA typ. 85 mA typ. 90 mA only load typ. 80 mA
5 A AC/DC (ohmic)/2 A AC/DC
5 A AC/DC (ohmic)/2 A AC/DC max. 3 A AC/3 A DC at 30 V DC switching capacity DC: 300 V = 0.15 A;
(inductive)
(inductive)
2 x 107
2 x 107
5 x 106
5
5
6
24 V = 5 A; non-linear; AC:1,500 VA 1 x 107
3 x 10 (5 A/30 V DC)
3 x 10 (5 A/30 V DC)
1 x 10 (1 A/250 V AC)
1.3 x 105 (2 A/250 V AC)
max. 5 A starting current (4 x 58 W)
max. 5 A starting current (4 x 58 W)
max. 6 A starting current no data
10 mA at 5 V DC
10 mA at 5 V DC
100 mA (12 V DC)
no data power relay potential-free contacts reverse switching realisable
400 V contact
-20…+60 °C
-20…+60 °C
0…+55 °C
0…+55 °C
CE, UL, GL
CE, UL, GL
CE
CE, GL approx. 85 g approx. 80 g approx. 55 g approx. 85 g www.beckhoff.com/KL2602 www.beckhoff.com/KL2622 www.beckhoff.com/KL2652 www.beckhoff.com/KL2631
We reserve the right to make technical changes.
BECKHOFF New Automation Technology
Page 83
Digital Output
KM2604, KM2614
Digital output | Relay outputs up to 400 V AC 4-channel relay module,
4-channel relay module,
230 V AC
230 V AC, automatic/ manual operation
KM2604
KM2614
Load type ohmic, inductive, lamp load
Max. output current
16 A
Number of outputs
4 x change-over
4 x change-over
The KM2604 terminal module combines four pluggable power relays in one fieldbus module. The high switching capacity of 16 A at 230 V AC enables direct mains connection of consumers with high current consumption. The relays are positioned at the top and can therefore be exchanged easily.
The KM2614 terminal module combines four pluggable power relays in one fieldbus module. The high switching capacity of 16 A at 230 V AC enables direct mains connection of consumers with high current consumption. The relays are positioned at the top and can therefore be exchanged easily. Each relay can be manually switched to the ON status. A seal indicates the initial manual operation.
Nominal voltage
230 V AC (max. switching voltage 250 V AC/30 V DC)
230 V AC (max. switching voltage 250 V AC/30 V DC)
Current consumption
– (no power contacts)
– (no power contacts) typ. 15 mA
Bus Terminal
Technical data
542 power contacts Current consumpt. K-bus typ. 15 mA
Switching current
16 A AC/12 A DC at 30 V DC
16 A AC/12 A DC at 30 V DC
Operat. cycles mech. (min.)
5 x 106
5 x 106
Operat. cycles electr. (min.)
1 x 106 (1 A/250 V AC)
1 x 106 (1 A/250 V AC)
Lamp test, max. 25 A starting current max. 25 A starting current
Minimum permitted load
5 mA (10 V DC)
5 mA (10 V DC)
Special features
– automatic/manual operation at the relay
Operating temperature
0…+55 °C
0…+55 °C
Approvals
CE
CE
Weight approx. 250 g approx. 250 g
Further information www.beckhoff.com/KM2604 www.beckhoff.com/KM2614 electronic ballast
BECKHOFF New Automation Technology
We reserve the right to make technical changes.
Page 84
KM2642, KM2652
2-channel relay module,
2-channel relay module,
230 V AC, manual/automatic
230 V AC, manual/automatic operation operation
KM2642
KM2652
Digital Output
6A 2 x change-over
Bus Terminal
2 x change-over
543
The digital KM2642 output terminal has two independent relay change-over contacts, which can be used for switching mains current consumers. For each channel a switch enables selection between automatic, manual on, manual off. In automatic mode the logical state of an output bit switches the relay. For manual mode a 24 V supply is required for the Bus Coupler. The output state can be read by the controller.
The digital KM2652 output terminal has two independent relay change-over contacts, which can be used for switching mains current consumers. For each channel a switch enables selection between automatic, manual on, manual off. In automatic mode the logical state of an output bit switches the relay. For manual mode a 24 V supply is required for the Bus Coupler. The state of the output and the switch can be read by the controller.
230 V AC (max. switching voltage 250 V AC)
230 V AC (max. switching voltage 250 V AC)
– (no power contacts)
– (no power contacts)
typ. 130 mA typ. 130 mA
6 A AC/4 A DC at 30 V DC
6 A AC/4 A DC at 30 V DC
1 x 106
1 x 106
1 x 105 (3 A/250 V AC)
1 x 105 (3 A/250 V AC)
max. 10 A starting current max. 10 A starting current
100 mA (12 V DC)
100 mA (12 V DC)
manual/automatic operation manual/automatic operation
0…+55 °C
0…+55 °C
CE
CE approx. 110 g approx. 110 g www.beckhoff.com/KM2642 www.beckhoff.com/KM2652
We reserve the right to make technical changes.
BECKHOFF New Automation Technology
Page 85
Digital Output
KL27xx
Bus Terminal
Digital output | Triac outputs up to 230 V AC
544
In applications with particularly frequent switching operations the service life of a mechanical relay is potentially very short. An electronic switch in the form of triacs and Mosfet transistors is an almost wear-free replacement. A triac is a robust switch and will only be used as a zero crossing switch in the Bus Terminals. Switch-on only occurs in zero crossing voltage and switch-off only in zero crossing current. Inductive loads are therefore switched off without overvoltage. The disadvantage of a Triac is a relatively high voltage drop in switched-on state, which leads to a higher power dissipation compared to a relay contact. An essential protective circuit leads to a leakage current in switched-off state. The output is not safely isolated from the mains. Triacs need a minimum load so that they remain switched-on, and a minimum voltage for error-free zero crossing detection. A solid-state output is realised with Mosfet transistors. This implementation is very similar to the relay contact, but not as resilient. The solid-state output always switches immediately (no zero crossing switching) and has high ohmic isolation in switched-off state. Because switching-off takes some milliseconds, no break spark is created even for inductive loads. Solid-state outputs can also switch signals with low voltages and small currents. When fusing Bus Terminals from the triac/solid-state family it should be noted that electronic switches cannot withstand high short-circuit currents. The fuses which are used should at least be fast-acting (characteristic: F) with low rated/reference current.
BECKHOFF New Automation Technology
Technical data
2-channel triac
2-channel triac output terminal, output terminal,
12…230 V AC
12…230 V AC
KL2712 |
KL2722 |
KS2712
KS2722
KL2732
Connection technology
4-wire
2-wire
Load type ohmic, inductive
Max. output current
2 x 0.01…0.5 A
1x1A
1x1A
Number of outputs
2 x make contacts
2 x make contacts
2 x make contacts
1
5
1
5
12… 230 V AC
2
6
2
6
N
3
7
3
7
PE
4
8
4
8
The KL2712 and KL2722 output terminals use a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a Triac which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear.
The KL2732 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a Triac. As a semiconductor switch, it is not subject to wear.
Nominal voltage
12…230 V AC
12…230 V AC
Current consumption only leakage and load current
– (no power contacts)
power contacts Current consumpt. K-bus typ. 10 mA typ. 10 mA
Switching times
0.1…10 ms, zero crossing
0.1…10 ms, zero crossing
Frequency range
47…63 Hz
47…63 Hz
Surge voltage protection
> 275 V AC
> 275 V AC
Peak current
40 A (16 ms), 1.5 A (30 s)
40 A (16 ms), 3 A (30 s)
Leakage current typ. 0.8 mA, max. 1.5 mA (OFF state)
typ. 0.8 mA, max. 1.5 mA (OFF state)
Switch-off time
T/2
T/2
Maximum residual voltage
1.5 V
1.5 V
Special features reverse motors (blinds)
reverse motors (blinds)
Operating temperature
0…+55 °C
Approvals
CE, UL, GL
Weight approx. 55 g approx. 55 g
Further information www.beckhoff.com/KL2712 www.beckhoff.com/KL2732
Special terminals
KL27x2-0010
Distinguishing features special terminals see page
0…+55 °C CE, Ex, GL
CE, GL
KL2732-0010 605 special terminals see page
605
We reserve the right to make technical changes.
Page 86
KL27xx
Digital Output
4-channel triac
1-channel solid state
2-channel solid state output module load relay up to 230 V AC/DC load relay up to 230 V AC/DC
KL2701 | KS2701
KL2702 | for 4 blind motors
KM2774
KL2702-0020
KS2702 2-/3-/4-wire
1.5 A per channel
3 A steady load
4 x 3 make contacts
1 make contact
0.3 A steady load
1.5 A steady load on each channel on each channel
2 x make contacts
1
5
1
5
2
6
2
6
3
7
3
7
4
8
4
8
Bus Terminal mixed
545
Mixed module 24 V DC/230 V AC for the direct control of blinds applications
The KL2701 output terminal uses an electronic load relay to switch a mains voltage of up to 230 V AC/DC. The switching element is a highpower MOSFET which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear.
The KL2702 output terminal uses an electronic load relay to switch a mains voltage of up to 230 V AC/DC. The switching element is a highpower MOSFET which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear.
80…230 V AC
0…230 V AC/DC
0…230 V AC/DC
– (no power contacts)
only leakage and load current only leakage and load current typ. 30 mA typ. 65 mA typ. 10 mA
0.1…10 ms, zero crossing
1.5…5 ms
1.5…5 ms
50 Hz
DC > 100 Hz
DC > 100 Hz
> 275 V AC
> 400 V AC
> 400 V AC
40 A (16 ms), 3 A (30 s)
5 A (20 s), 50 A (100 ms)
0.5 A (20 s), 1.5 A (100 ms)
typ. 0.8 mA, max. 1.5 mA (OFF state)
<< 1 mA (OFF state)
<< 1 mA (OFF state)
T/2
2…4 ms
2…4 ms
1.5 V
100 mΩ
2.1 Ω
–
–
–
0…+55 °C
0…+55 °C
0…+55 °C
CE
CE
CE, UL, Ex, GL approx. 270 g approx. 55 g approx. 55 g www.beckhoff.com/KM2774 www.beckhoff.com/KL2701 www.beckhoff.com/KL2702
We reserve the right to make technical changes.
CE
BECKHOFF New Automation Technology
Page 87
Digital Output
KL2692
Digital output | Cycle monitoring Cycle monitoring terminal (watchdog)
Technical data
KL2692 | KS2692
Connection technology
2-wire
Max. output current
3A
Number of outputs
2 potential-free relay outputs (normally-open contacts)
Number of inputs
2 digital 24 V inputs
Bus Terminal
The KL2692 Bus Terminal monitors a bit that is toggled by the controller during each cycle. If the toggle signal fails, the terminal switches off two potential-free relays in order to prevent damage to the machine. Failure of the toggle signal may be caused by the PLC cycle stopping, by a fault in the bus cable or connector, or by a fault in a bus device. The cycle monitoring time can be parameterised. The Bus Terminal has an enable input that enables the relay to be switched on if a correct toggle signal is detected.
1
5
2
6
3
7
4
8
546
Nominal voltage
30 V DC
Current consumption
– power contacts Current consumpt. K-bus approx. 165 mA
Switching times parameterisable
Ohmic switching current
5 A AC/DC
Inductive switching
2 A AC/DC current Operat. cycles mech. (min.)
2 x 107
Operat. cycles electr. (min.)
1 x 105 (5 A/30 V DC)
Minimum permitted load
10 mA at 5 V DC
Operating temperature
0…+55 °C
Approvals
CE, UL
Weight approx. 60 g
Further information www.beckhoff.com/KL2692
Special terminals
KL2692-1001
Distinguishing features
2 digital inputs, 2 potential-free relays, end terminal variant
BECKHOFF New Automation Technology
We reserve the right to make technical changes.
Page 88
KL2521
Digital Output
Digital output | Frequency output (pulse train) 1-channel pulse train
1-channel pulse train output terminal, RS422 output terminal, 24 V DC
Technical data
KL2521 | KS2521
KL2521-0024 |
Output pattern pulse direction, encoder simulation
Max. output current
RS422 specification
0.5 A
Number of outputs
1 channel (2 differential
1 channel (2 single-ended outputs A, B)
low side switches A, B)
2 (+T, +Z)
2 (+T, +Z)
KS2521-0024
Number of inputs
1
5
1
5
2
6
2
6
3
7
3
7
4
8
4
8
Bus Terminal
The KL2521-xxxx output terminals provide a parameterisable pulse sequence through both their outputs. The relation between channel A and B is adjustable, e.g. as encoder characteristic. The pulse rate and the frequency are specified by the controller via a 16-bit value. The LEDs are driven in time with the outputs and each displays an active output. The galvanic isolation of the K-bus is realised. The KL2521 has two RS422-compatible differential outputs, which are fed electrically isolated from the K-bus. For the KL2521-0024 both output channels are implemented as potential-free FET switches and must be fed externally. The 100 mA switch output is shortcircuit-proof. The KL2521 series offers different modes of operation: frequency modulation on the individual channels, incremental encoder or pulse/direction signals. A travel distance control can also be parameterised.
547
Nominal voltage
RS422 level
24 V DC (externally supplied)
Current consumption
– (no power contacts)
– (no power contacts)
Current consumption typ. 50 mA, max. 120 mA typ. 50 mA, max. 120 mA
K-bus
(load-dependent)
(load-dependent)
PWM clock frequency
1…500 kHz, 50 kHz default
1…500 kHz, 50 kHz default
A
Duty factor
50 % (±20 %)
50 % (±20 %)
B
Resolution max. 15 bits max. 15 bits
Operating temperature
0…+55 °C
0…+55 °C
Approvals
CE, Ex
CE
Weight approx. 50 g approx. 50 g
Further information www.beckhoff.com/KL2521 www.beckhoff.com/KL2521
Special terminals
KL2521-0010
Distinguishing features with additional outputs power contacts Operation mode Frequency modulation
Pulse/ direction signals Incremental encoder
Clockwise
A B A B
Reverse
(230 V AC/DC, 100 mA) instead of the additional
Frequency pulse patterns
We reserve the right to make technical changes.
inputs of the default variant
BECKHOFF New Automation Technology
Page 89
Digital Output
KL25xx
Digital output | 24/50 V DC, PWM output 2-channel pulse
2-channel pulse
2-channel pulse
2-channel pulse width output terminal, width output terminal, width current terminal, width current terminal,
24 V DC
24 V DC
24 V DC
50 V DC
Technical data
KL2502 | KS2502
KL2512 | KS2512
KL2535 | KS2535
KL2545 | KS2545
Load type ohmic
Max. output current
0.1 A (1 A driver compo- inductive > 1 mH, valves, coils 1.5 A per channel nent) per channel Number of outputs
2
2
2 x 1 A (short-circuit-proof,
2 x 3.5 A (short-circuit-proof, thermal overload-proof for thermal overload-proof for both both channels together)
channels together)
2
2
Enc
1
5
1
5
1
5
A1 2
6
2
6
2
6
Bus Terminal
B1
1
5
1’
5’
2
6
2’
6’
A2
B2
3
7
3
7
3
7
3
7
3’
7’
4
8
4
8
4
8
4
8
4’
8’
A1
A2
B1
B2
548
The KL2502 digital output terminal modulates the pulse width of a binary signal, and outputs it electrically isolated from the K-bus. The mark/space ratio is prescribed by a 16-bit value from the automation unit.
The negative switching KL2512 output terminal enables direct connection of different ohmic loads. The output signal is a pulse-width modulated voltage. The typical load of an LED group or an incandescent lamp is connected between the positive side of the supply voltage and the output of the KL2512.
The KL2535 digital output terminal controls an output current via pulse width control of the supply voltage. It is electrically isolated from the K-bus. The current value (0 to 1 A) is specified by the automation device via a 16-bit value.
The KL2545 digital output terminal controls an output current via pulse width control of the supply voltage. It is electrically isolated from the K-bus. The current value (0 to 3.5 A) is specified by the automation device via a 16-bit value.
Nominal voltage
24 V DC (-15 %/+20 %)
24 V DC (-15 %/+20 %)
24 V DC (-15 %/+20 %)
8…50 V DC
Current consum. pow.cont.
typ. 10 mA + load typ. 10 mA + load only load typ. 30 mA + load
Current consumpt. K-bus typ. 18 mA typ. 18 mA typ. 60 mA typ. 100 mA
PWM clock frequency
1…20 kHz, 250 Hz default
1…20 kHz, 250 Hz default
36 kHz
36 kHz
Duty factor
0…100 %
0…100 %
0…100 %
0…100 %
(current-controlled)
(current-controlled)
Resolution max. 10 bits max. 10 bits max. 12 bits max. 12 bits
Operating temperature
0…+55 °C
0…+55 °C
0…+55 °C
0…+55 °C
Approvals
CE, Ex
CE
CE
CE
Weight approx. 50 g approx. 50 g approx. 55 g approx. 100 g
Further information www.beckhoff.com/KL2502 www.beckhoff.com/KL2512 www.beckhoff.com/KL2535 www.beckhoff.com/KL2545
Special terminals
KL2502-xxxx
Distinguishing features for special terminals
(TON > 750 ns, TOFF > 500 ns)
see page
BECKHOFF New Automation Technology
605
We reserve the right to make technical changes.
Page 90
KL2751, KL2761
Digital Output
Digital output | Universal dimmer up to 230 V AC 1-channel universal dimmer terminal, 230 V AC
Technical data
KL2751 | KS2751
KL2761 | KS2761
Connection technology
4-wire
Load type ohmic, inductive or capacitive (not mixed), lamp load, automatic load detection
Max. output current
1.35 A
Number of outputs
1
2.7 A
1
5
230 V AC
2
6
N
3
7
PE
4
8
Bus Terminal
To dim light efficiently means electronically regulating the current flow through the lighting medium using the phase control principle. The ratio of the switch-on time to the switchoff time determines the output light quantity via the flow of current. Depending on the load connected (ohmic, capacitive, inductive) either the switch-on time (leading edge phase control | load type: L) or the switch-off time (trailing edge phase control | load type: C, R) must be regulated. The load type of an electronic ballast depends on the transformer used and must be taken into account. The KL2751 and KL2761 universal dimmer terminals automatically recognise the connected load and select the corresponding control principle. The short-circuit resistance prevents damage to the fuse, so that no additional maintenance work is necessary when exchanging the lamp.
549
Leading edge phase control i t Voltage u Current i
Trailing edge phase control u i t
We reserve the right to make technical changes.
230 V AC only load power contacts u
Voltage u Current i
Nominal voltage Current consumption Current consumpt. K-bus typ. 65 mA
Short circuit current
10…20 A
Mains voltage
230 V AC (50 Hz)
Rated output
300 VA (W)
600 VA (W)
Rated current max. 1.35 A max. 2.7 A
Control type phase control
Resolution
1%
Leakage current
< 1 mA (OFF state)
Special features dimmers with fieldbus functionality
Operating temperature
0…+55 °C
Approvals
CE
Weight approx. 60 g
Further information www.beckhoff.com/KL2751 www.beckhoff.com/KL2761
Special terminals
KL2751-0011
KL2761-0011
Distinguishing features without power contacts
20…40 A
600 W, 50 Hz (without power contacts)
BECKHOFF New Automation Technology