Page 71

Digital Input

KL1501, KL1512

Bus Terminal

Digital input | Counter Pulses often need to be captured in technical control applications. If the pulse length is the order of magnitude of the control cycle time or less, the controller cannot record these signals correctly any more. Pre-processing is then required. The “counter terminals” can count the number of pulses and deliver reliable values to the controller, even though the controller cannot capture the pulse at that speed. The counter is adapted to the individual requirements, such as forwards/backwards counter or Gate/Latch-controlled, by parameterisation. With a counter depth of 16- or 32-bit an overflow, even at high frequencies, can easily be managed by the controller. The KL1501 is optimised for particularly fast signals. On this basis, other input voltages and special pre-processing are available with special varieties of terminals. The KL1512 is developed for price-sensitive areas of application and has certain limitations in relation to speed, bit width and functionality.

Up/down counter,

Up/down counter,

24 V DC, 100 kHz, 32 bit

24 V DC, 1 kHz, 16 bit

Technical data

KL1501 | KS1501

KL1512 | KS1512

Input filter

–

0.2 ms

Number of inputs

2

1

5

1

5

2

6

2

6

3

7

3

7

4

8

4

8 opt. Out

The up/down counter counts binary pulses, and transmits the counter state, in an electrically isolated form, to the higher-level automation device. In the KL1501 Bus Terminal it is possible to choose the (32-bit) counting direction (forwards/backwards) using the forwards/ backwards input, and the gate connection can be used to trigger the counter.

530

In the KL1512 digital input terminal it is possible to choose forwards or backwards counter (16-bit) direction. It is particularly suitable for simple counting tasks.

Nominal voltage

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

“0“ signal voltage

-3…+5 V

-3…+5 V

“1“ signal voltage

15…30 V

15…30 V

Current consum. pow.cont.

–

–

Current consumpt. K-bus typ. 50 mA typ. 50 mA

Counting frequency max. 100 kHz (2 kHz for max. 1 kHz switching up and down) Max. output current

0.5 A typ. (short-circuit-proof)

– per channel

BECKHOFF New Automation Technology

Counter depth

32 bits

Special features

2 additional outputs

16 bits –

Operating temperature

0…+55 °C

0…+55 °C

Approvals

CE, UL, Ex

CE, Ex

Weight approx. 50 g approx. 55 g

Further information www.beckhoff.com/KL1501 www.beckhoff.com/KL1512

Special terminals

KL1501-0010

Distinguishing features special terminal see

605

We reserve the right to make technical changes.

Page 72

KL1904

Digital Input

Digital input | TwinSAFE

For further information on TwinSAFE and the TwinSAFE products see page 828

4-channel digital input terminal, TwinSAFE, 24 V DC

Technical data

KL1904

Connection technology

2-wire

Safety standard

IEC 61508 SIL 3 and DIN EN ISO 13849-1:2008 PLe

Number of inputs

4

1

5

2

6

3

7

4

8

Bus Terminal

The KL1904 safety Bus Terminal is a digital input terminal for sensors with potential-free 24 V DC contacts and comprises four fail-safe inputs. The KL1904 meets the requirements of IEC 61508 SIL 3 and DIN EN ISO 13849-1:2008 PLe.

531

The KL1904 Safety Bus Terminal has four fail-safe inputs.

Protocol

TwinSAFE/FSoE

Nominal voltage

24 V DC (-15 %/+20 %)

Current consumption

– power contacts Current consumpt. K-bus

48 mA

Response time typ. 4 ms (read input/write to K-bus)

Fault response time

≤ watchdog time (parameterisable)

Permiss. degree

2 of contamination

We reserve the right to make technical changes.

Climate class EN60721-3-3

3K3

Installation position horizontal

Special features

4 safe inputs

Operating temperature

0…+55 °C

Approvals

CE, UL, Ex, TÜV Süd

Weight approx. 50 g

Protection class

IP 20

Further information www.beckhoff.com/KL1904

BECKHOFF New Automation Technology

Page 73

Digital Output

KL2408

Bus Terminal

Digital output | 24 V DC, positive switching

532

Many actuators are driven or controlled with 24 V DC. The Bus Terminals of the “positive switching” category switch all output channels to 24 V DC, so all connected actuators are hard-wired to ground (0 V). The output of a Bus Terminal can be considered as a functional 24 V DC relay contact. The output circuit offers further functions such as short-circuitcurrent limitation, short-circuit switch-off and the rapid depletion of inductive energy from the coil. The most common output circuit delivers a maximum continuous current of 0.5 A. Special output terminals are available for higher currents. Any type of load (ohmic, capacitive, inductive) can be connected to an output terminal. As lamp and capacitive loads are critical due to their high starting currents, they are limited by the output circuits of the Bus Terminals. This ensures that the upstream circuit-breaker is not triggered. Inductive loads are problematic at switch-off, as high induction voltages develop if the current is interrupted too fast. An integrated freewheeling diode prevents this voltage peak. However, the current is reduced so slowly that it leads to faults in many technical control applications.

For example, a valve remains open for many milliseconds. The Bus Terminals represent a compromise between prevention of overvoltage and rapid switchoff. They suppress the induction voltage to about 24 V DC and realise switch-off times which approximately correspond to the switch-on time of the coil. In the case of short-circuit, the output circuit limits the current and prevents the activation of the upstream circuit-breaker. The Bus Terminal maintains this current until important self-heating and finally switches off. After the circuit has cooled, it switches back on. The output signal is driven in time until the output of the controller is switched off or the short-circuit is rectified. The clock frequency depends on the ambient temperature and the load of the other terminal channels. The overload protection of the output is also realised by thermal switch-off. The total current specified should be observed. If a total current is not given, it is not limited.

8-channel digital output terminal, 24 V DC, 1-wire

Technical data

KL2408 | KS2408

Connection technology

1-wire

Load type ohmic, inductive, lamp load

Max. output current

0.5 A (short-circuit-proof) per channel

Number of outputs

8

+60 °C -20 °C

1

5

2

6

3

7

4

8

The KL2408 digital output terminal has 8 outputs, each one is assigned a terminal point. This way, a high packing density can be achieved for actuators with common ground potential.

Nominal voltage

24 V DC (-15 %/+20 %)

Current consumption typ. 60 mA + load power contacts

BECKHOFF New Automation Technology

Current consumpt. K-bus typ. 18 mA

Breaking energy

< 150 mJ/channel

Reverse voltage protection yes

Short circuit current

<2A

Operating temperature

-20…+60 °C

Approvals

CE, UL, Ex, GL

Weight approx. 70 g

Further information www.beckhoff.com/KL2408

We reserve the right to make technical changes.

Page 74

KL2xxx, KL1859

Digital Output

16-channel digital

8-channel digital input +

4-channel digital

8-channel digital output terminal,

8-channel digital output, output terminal, output terminal,

24 V DC, 1-wire

24 V DC, 1-wire

24 V DC, 2-wire

24 V DC, 2-wire

KL2809

KL1859

KL2404 |

KL2424 |

KS2404

KS2424

KL2808

2-wire

0.5 A (short-circuit-proof)

0.5 A (short-

2.0 A (short-

0.5 A (short-circuit-proof)

per channel circuit-proof)

circuit-proof)

per channel per channel per channel

16

8 outputs + 8 inputs

4

8

+60 °C

1

9

1

9

2

10

2

10

3

11

3

11

4

12

4

12

5

13

5

13

6

14

6

14

7

15

7

15

8

16

8

16

1

2

6

3

7

4

The KL2809 HD (High Density) Bus Terminal has 16 digital outputs and is suitable for applications in which a very high packing density is required.

The KL1859 digital Bus Terminal combines eight digital inputs and eight digital outputs in one device. – – –

5

1

9

2

10

3

11

4

12

5

13

6

14

7

15

8

16

8

The KL2404 and KL2424 digital input terminals are suitable for the connection of four 2-wire actuators.

number of inputs: 8 input filter: 3.0 ms type 1/3

The KL2808 High Density Bus Terminal contains eight outputs and eight ground connection points for the connection of 2-wire actuators and thus allows a very high packing density.

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

typ. 35 mA + load typ. 15 mA + load typ. 30 mA + load typ. 15 mA + load typ. 35 mA typ. 25 mA typ. 9 mA

< 150 mJ/channel

< 150 mJ/channel

< 150 mJ/channel yes yes yes

<2A

<2A

<2A

0…+55 °C

0…+55 °C

-20…+60 °C

0…+55 °C

CE, Ex

CE, Ex

CE, UL, Ex

CE, Ex approx. 70 g approx. 60 g approx. 70 g approx. 65 g www.beckhoff.com/KL2809 www.beckhoff.com/KL1859 www.beckhoff.com/KL2404 www.beckhoff.com/KL2808

We reserve the right to make technical changes.

typ. 20 mA < 1.7 J/channel

< 150 mJ/channel yes

< 70 A

<2A

BECKHOFF New Automation Technology

Bus Terminal

-20 °C

533

Page 75

Digital Output

KL2xxx

Digital output | 24 V DC, positive switching 4-channel digital

4-channel digital

2-channel digital

2-channel digital output terminal, output terminal, output terminal, output terminal,

24 V DC, 2-/3-wire

24 V DC, 2-/3-wire

24 V DC, 3-wire

24 V DC, 4-wire

Technical data

KL2114 | KS2114

KL2134 | KS2134

KL2442

KL2032

Connection technology

2-/3-wire

3-wire

4-wire

Load type ohmic, inductive, lamp load

Max. output current

0.5 A (short-circuit-proof)

0.5 A (short-circuit-proof)

4.0 A (short-circuit-proof)

0.5 A (short-circuit-proof)

per channel per channel per channel, 8 A for parallel per channel connection Number of outputs

4

4

2

2

+60 °C

+60 °C

-20 °C

-20 °C

Bus Terminal

8A

534

1

5

1

5

1

5

1

5

2

6

2

6

2

6

2

6

3

7

3

7

3

7

3

7

4

8

4

8

4

8

4

8

The KL2114 digital output terminal connects the control signals to the actuators in an electrically isolated manner.

The KL2134 digital output terminal connects the control signals to the actuators in an electrically isolated manner.

The KL2442 is suitable for the connection of actuators with high current requirement of 4 A. For parallel switched outputs, even 8 A is possible.

The KL2032 digital output terminal connects the control signals to the actuators in an electrically isolated manner.

Nominal voltage

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

Current consumption typ. 30 mA + load typ. 30 mA + load typ. 30 mA + load typ. 20 mA + load power contacts Current consumpt. K-bus typ. 9 mA typ. 9 mA typ. 9 mA typ. 5 mA

Breaking energy

< 150 mJ/channel

< 150 mJ/channel no data

< 150 mJ/channel

Reverse voltage protection

– yes yes yes

Short circuit current

<2A

<2A

< 70 A

<2A

Operating temperature

0…+55 °C

-20…+60 °C

0…+55 °C

-20…+60 °C

Approvals

CE, UL, Ex

CE, UL, Ex, GL

CE

CE, UL, Ex, GL

Weight approx. 70 g approx. 70 g approx. 70 g approx. 55 g

Further information www.beckhoff.com/KL2114 www.beckhoff.com/KL2134 www.beckhoff.com/KL2442 www.beckhoff.com/KL2032

Special terminals Distinguishing features

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 76

KL2xxx

Digital Output

2-channel digital

2-channel digital

16-channel digital

16-channel digital output terminal, output terminal, output terminal, output terminal,

24 V DC, 4-wire

24 V DC, 4-wire,

24 V DC, flat-ribbon

24 V DC, with diagnostics cable connection

D-sub connection

KL2212 | KS2212

KL2872

KM2042 flat-ribbon cable

D-sub

KL2012 |

KL2022 |

KS2012

KS2022

2.0 A (short-

0.5 A (short-circuit-proof)

0.5 A (short-circuit-proof)

0.5 A (short-circuit-proof)

circuit-proof)

circuit-proof)

per channel per channel per channel per channel per channel 2

16

16

2

1

5

1

5

2

6

2

6

3

7

3

7

4

8

4

8

The digital output terminals KL2012 and KL2022 connect the control signals to the actuators in an electrically isolated manner.

Bus Terminal

0.5 A (short-

+48 V

Diagnostic possibilities: – short-circuit to 24 V – short-circuit to 0 V – undervoltage

535 +

1

2

–

The KL2872 allows the connection of 16 actuators by direct ribbon cable via a 20-pin contact strip with a 2.54 mm contact spacing. The required 24 V DC voltage supply must be input by the ribbon cable or the terminal points.

The digital output terminal KM2042 allows direct connection of actuators by D-sub connection, which is common in e.g. valve terminals.

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

typ. 15 mA + typ. 20 mA + typ. 15 mA + load typ. 60 mA from the supply

– (no power contacts)

load load typ. 5 mA

(no power contacts) typ. 15 mA typ. 5 mA typ. 5 mA

< 150 mJ/channel

< 150 mJ/channel

< 150 mJ/channel

– yes yes

<2A

<2A

<2A

0…+55 °C

0…+55 °C

0…+55 °C

CE, UL, Ex

CE

CE approx. 55 g approx. 60 g approx. 55 g approx. 90 g www.beckhoff.com/KL2012 www.beckhoff.com/KL2212 www.beckhoff.com/KL2872 www.beckhoff.com/KM2042

< 150 mJ/

< 1.7 J/channel channel – <2A

< 70 A

0…+55 °C CE, UL, Ex

CE, UL, Ex, GL

KL2872-0010 negative switching

We reserve the right to make technical changes.

538

BECKHOFF New Automation Technology

Page 77

Digital Output

KM200x

Digital output | 24 V DC, terminal modules 16-channel digital

32-channel digital

64-channel digital output, 24 V DC, output, 24 V DC, output, 24 V DC, plug connector plug connector plug connector

Technical data

KM2002

KM2004

KM2008

Connection technology plug

Load type ohmic, inductive, lamp load

Max. output current

0.5 A (short-circuit-

0.5 A (short-circuit-proof)

0.5 A (short-circuit-proof)

proof) per channel per channel per channel

16 (2 x 8)

32 (4 x 8)

64 (8 x 8)

Bus Terminal

Number of outputs

536

Like the standard Bus Terminals, the terminal modules are integrated in the I/O system. Plug connectors with spring connections enable plug-in wiring and are optionally available with 1 or 3 pins. LEDs integrated in the plug indicate the signal state for each channel directly at the wire. Ordering information: KM200x -0000 without plugs -0001 1-pin plug (without status LED) -0002 1-pin plug (with status LED) -0004 3-pin plug (with status LED) Nominal voltage

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

Current consumption

– (no power contacts)

– (no power contacts)

– (no power contacts)

power contacts Current consumpt. K-bus typ. 5 mA typ. 5 mA typ. 5 mA

Breaking energy

< 150 mJ/channel

< 150 mJ/channel

< 150 mJ/channel

Reverse voltage protection yes yes yes

Short circuit current

<2A

<2A

<2A

Operating temperature

0…+55 °C

0…+55 °C

0…+55 °C

Approvals

CE

CE

CE

Weight approx. 90 g with 1-pin approx. 90 g with 1-pin connector, approx. 310 g with 1-pin connector, connector, approx. 110 g approx. 110 g with 3-pin connector approx. 390 g with 3-pin connector www.beckhoff.com/KM2004 www.beckhoff.com/KM2008 with 3-pin connector Further information www.beckhoff.com/ KM2002

Special terminals

KM2002-000x

KM2004-000x

KM2008-000x

Distinguishing features different connectors different connectors different connectors

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 78

KL2904, KL2124

Digital Output

Digital output | TwinSAFE; 5 V DC, positive switching 4-channel digital

4-channel digital output terminal, output terminal,

TwinSAFE, 24 V DC

5 V DC, 2-/3-wire

Technical data

KL2904

KL2124 | KS2124

Connection technology

2-wire

2-/3-wire

Safety standard

IEC 61508 SIL 3 and DIN EN ISO 13849-1:2008 PLe

–

Max. output current

0.5 A/20 mA min. (per channel)

±20 mA (short-circuit-proof) per channel,

Number of outputs

4

4

1

5

2

6

7

3

7

8

4

8

1

5

2

6

3

4

+5 V

Bus Terminal

8 mA signal current

537

The KL2904 Safety Bus Terminal has four outputs.

The positive-switching KL2124 output terminal offers four outputs and additionally provides 5 V DC and ground (0 V) for each channel.

For further information on TwinSAFE and the TwinSAFE products see page 828

Nominal voltage

24 V DC (-15 %/+20 %)

5 V DC

Current consumption load-dependent typ. 16 mA + load

Current consumpt. K-bus

250 mA typ. 14 mA

Protocol

TwinSAFE/FSoE

–

Fault response time

≤ watchdog time (parameterisable)

–

Installation position horizontal variable – power contacts

Special features

4 safe outputs

Operating temperature

0…+55 °C

0…+55 °C

Approvals

CE, UL, Ex, TÜV Süd

CE, Ex

Weight approx. 100 g approx. 70 g

Further information www.beckhoff.com/KL2904 www.beckhoff.com/KL2124

We reserve the right to make technical changes.

BECKHOFF New Automation Technology

Page 79

Digital Output

KL2xxx

Digital output | 24 V DC, negative switching 8-channel digital

16-channel digital

4-channel digital

16-channel digital output terminal, output terminal, output terminal, output terminal,

24 V DC, 1-wire

24 V DC, 1-wire

24 V DC, 2-/3-wire

24 V DC, flat-ribbon cable connection

Technical data

KL2488 | KS2488

Connection technology

1-wire

Load type ohmic, inductive, lamp load

Max. output current

0.5 A (short-circuit-proof) per channel 8

Number of outputs

Bus Terminal

1

KL2889

KL2184 | KS2184

KL2872-0010

2-/3-wire flat-ribbon cable

0.5 A (short-circuit-proof)

0.5 A (short-circuit-proof)

0.5 A (short-circuit-proof)

per channel per channel per channel

16

4

16

5

2

6

3

7

538 4

1

9

2

10

3

11

4

12

5

13

6

14

7

15

8

16

8

The KL2488 digital output terminal is suitable for the connection of eight negative switching actuators using 1-wire connection technology.

The KL2889 HD (High Density) Bus Terminal offers terminal points for 16 negative switching actuators using 1-wire connection technology and thus a very high packing density.

1

5

2

6

3

7

4

8

+

The KL2184 digital output terminal offers four outputs and additionally provides 24 V DC and ground (0 V) for each channel.

1

2

–

A 20-pin plug connector with 2.54 mm contact spacing enables the secure connection of plug connectors using insulation displacement contact, as is usual for ribbon cables and special round cables. The required 24 V DC voltage supply must be input by the ribbon cable or the terminal points 1 and 2.

Nominal voltage

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

24 V DC (-15 %/+20 %)

Current consumption typ. 60 mA + load typ. 35 mA + load typ. 30 mA + load typ. 60 mA from the supply

Current consumpt. K-bus typ. 18 mA typ. 45 mA typ. 9 mA typ. 5 mA

Breaking energy

< 100 mJ/channel

< 100 mJ/channel

< 100 mJ/channel

< 100 mJ/channel

Reverse voltage protection yes yes yes yes

Short circuit current

<7A

<7A

<7A

<7A

Operating temperature

0…+55 °C

0…+55 °C

0…+55 °C

0…+55 °C

Approvals

CE, UL, Ex

CE, Ex

CE, UL, Ex

CE

Weight approx. 70 g approx. 70 g approx. 70 g approx. 55 g

Further information www.beckhoff.com/KL2488 www.beckhoff.com/KL2889 www.beckhoff.com/KL2184 www.beckhoff.com/KL2872 power contacts

(no power contacts)

BECKHOFF New Automation Technology

We reserve the right to make technical changes.

Page 80

KL2784, KL2794

Digital Output

The KL2784 and KL2794 digital output terminals each provide four switches, which can be used like a relay contact for AC/DC voltages. The KL2784 uses a power contact as a common potential. In the KL2794, the power contacts are passed directly to the circuit without connection. The electronic switch in the Bus Terminal is implemented by efficient Mosfet transistors with a low switch-on resistance. The electronics are virtually wear-free. The switch itself is not short-circuit-proof, but can conduct a high current with its high pulse current capability long enough, until the circuit-breaker switches off. It behaves like a robust relay contact. Inductive loads can be switched directly, without further safety measures. The circuit switches relatively slowly and prevents high peak voltages. No break sparks are created in the terminal and thus no electromagnetic interference pulse.

4-channel digital

4-channel digital output terminal, output terminal,

24 V AC/DC,

24 V AC/DC, solid state solid state relay relay, potential-free

Technical data

KL2784 | KS2784

KL2794 | KS2794

Connection technology

2-wire

Load type

AC/DC loads

Max. output current

2A

2A

Number of outputs

4 x make contacts

4 x make contacts

1

5

1

5

2

6

2

6

3

7

3

7

4

8

4

8

Bus Terminal

Digital output | 24 V AC/DC, solid state relays

539

4 electronic switches on the power contact

4 potential-free electronic switches

Nominal voltage

0…24 V AC/DC

0…24 V AC/DC

Switching on speed typ. 1.8 ms, max. 5 ms typ. 1.8 ms, max. 5 ms

Switching off speed typ. 30 ms, max. 50 ms typ. 30 ms, max. 50 ms

Current consumption only load

– power contacts Current consumpt. K-bus

80 mA

80 mA

Breaking energy no data no data

Short circuit current

90 A

90 A

Surge voltage protection

> 39 V

> 39 V

Peak current

5 A (100 ms),

5 A (100 ms),

< 50 A (10 ms)

< 50 A (10 ms)

Closing resistor typ. 0.03 Ω typ. 0.03 Ω

Special features alternative for relay contacts alternative for relay contacts, potential-free

We reserve the right to make technical changes.

Operating temperature

0…+55 °C

0…+55 °C

Approvals

CE, Ex

CE, Ex

Weight approx. 70 g approx. 70 g

Further information www.beckhoff.com/KL2784 www.beckhoff.com/KL2794

BECKHOFF New Automation Technology