E-terminals Programming manual: 5 Programming using MAC Programmer+, pages 82 to 90

Pages 82 to 90 of 335, from E-terminals Programming manual

The original document is the PDF (4.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Beijer Electronics AB E200

Page 82

Programming using MAC Programmer+

Alarm Group Under Alarm Group you can group alarms; for example, by danger level - so that they can be more reality identified and dealt with. See the chapter Alarm handling.

Alarms Under Alarms you define alarm messages and the signal to be connected which will activate the alarm. See the chapter Alarm handling.

Time Channels Under Time Channels you define the time channels used to control events in the process at specified times. See the chapter Time control.

Password Under Password the password is defined for the application’s different access levels. See the chapter Password.

Message library Under Message library you create message tables where values between 0 and 65535 are linked to texts. See the chapter Message library.

71

Page 83

Programming using MAC Programmer+

5.16 The Setup Menu Functions for configuration of the terminal are to be found in the Setup menu.

System signals Setting of the handshaking signals between the terminal and the PLC system.

Current display reg.: Register in the PLC system which contains the number of the block shown on the display in the run-time mode. The register is updated automatically by the terminal on changing block. This register does not affect the choice of text block.

New display reg.: A PLC register that determines which block will be shown on the display.

72

Page 84

Programming using MAC Programmer+

Buzzer signal: Not valid in E50, E100 and E200. A register whose value decides the sound of the buzzer. See the table below. If the value i 0 then the buzzer is silent. The unit in the table is Hz. C

D

E

F

G

A

B

Contra

33

37

41

44

49

55

62

Large

65

73

82

87

98

110

123

Small

131

147

165

175

196

220

247

One

262

294

330

349

392

440

494

Two

523

587

659

698

784

880

988

Three

1046

1174

1318

1397

1568

1760

1975

Four

2093

2348

2636

2794

3136

3520

3950

Five

4186

Backlight signal: Digital signal which determines if the display is to be switched on or off.

Cursor ctrl. block: Not valid for E50, E100 and E200. Start register to a control block in the terminal which writes the current cursor position in the graphic block to the register in the PLC system. Register

Description

0

Current graphic cursor position X (in pixels), 0-239 in E300 and E600 and 0-319 in E700.

1

Current graphic cursor position Y (in pixels), 0-63 in E300, 0-127 in E600 and 0-239 in E700.

2

Status register 0 Normal 1 User trying to move down but there is no object there. 2 User trying to move up but there is no object there. 3 User trying to move left but there is no object there. 4 User trying to move right but there is no object there.

73

Page 85

Programming using MAC Programmer+ Start register to a control block in E710 which writes the current touch position in the graphic block to the register in the PLC system. Register

Description

0

X-coordinate (in pixel), 0-319

1

Y-coordinate (in pixel), 0-239

2

Status register 0 Not pressed 1 Pressed

Recipe ctrl.block: Control block for loading/saving/deleting of recipe files via the PLC system. See the chapter Recipes.

Current recipe reg: State the first of four 16-bit registers where the terminal put the name of the last loaded recipe from the system. The name can be presented in an ASCII object. The function takes four registers (eight characters) independent of the recipe name.

Library index reg: Used for indexing message libraries. In the Message object you state the number of the library from which the texts are loaded. If a index register is defined, the content of the index register are added to the stated number in the object. This make it possible to control from which library the texts are loaded from.

74

Page 86

Programming using MAC Programmer+

Commands One or more of the following commands can be stated on the command line. The commands are separated by a space. E50 only support the commands R and T. Command

Description

BR

Batch Read. Puts the terminal in transparent mode communication when using MELSEC PLC systems.

DGP

Delete the alarm group name from the alarm print out.

DD

Disable Delete alarms in the alarm list. When stated it is not possibble to delete inactive and acknowledged alarms from the alarm list.

NTGL

Only valid for E100. Gives the NUM key toggel function. The NUM key activate/inactivate the function for entering numerical characters in E100.

NTx

Timeout in ms for messages in the No protocol mode.

PDxxxxxxxx

Password xxxxxxxx that protect the transfer menu. Not valid in E100 and E200.

PSxxxxxxxx

Password xxxxxxxx that will give access to all functions in the terminal. Not valid in E100 and E200

RPD

RUN/PROG disable. Turns off the possibility to switch between RUN/ PROG with the keys [BACKSPACE] and [MAIN]. If RPD is used you switch mode via the MAC Programmer+.

Rx

Maximum number of retransmissions. x = number of attempts.

SW

Converts text with Swedish ASCII (7 bits) characters to 8 bits IBM PC extended ASCII on printing.

Tx

Global timeout for x milliseconds.

BFF

Block Form Feed. Puts a form feed after each block at print-out.

BSD

Baud Switching Disable when communicating via transparent mode with FX2N and Q. BSD must be set in the terminal not connected to the PLC system.

AKMx

Aktivates the joystick function, see the section ““Joystick” function”

DIMDx

Data register containing a value between -63 and +63 controlling the display brightness. -63 means that the display is as dark as possible and +63 means that the display is as bright as possible. Normal value is 0.

Index register Index addressing of dynamic objects. For more information see the Index addressing chapter. 75

Page 87

Programming using MAC Programmer+

Country settings Language: Choice of system message language during run-time in the terminal; British English, German, Swedish or American English. The default setting is English menu texts.

Character set: The choice of character set affect the used font table in the terminal and which national characters that will be used. Character set

Font table in graphic based terminals

Swedish

437

German

437

French

850

Spanish

850

Norwegian/Danish

850

Russian

866 Not E100 and E200

Slavic

852 Not E100 and E200

In the text based terminals E50, E100 and E200 special font tables is used and the same font table is used independent of the chosen character set. See appendix for all font tables. Different national characters (see the section The terminals keyboard in the the chapter Terminal functions) are used dependent of the chosen character set. Swedish

German

French

Spanish

Nor/Dan

C1

Å

Ü

È

Ñ

Å

C2

Ä

Ä

É

É

Æ

C3

Ö

Ö

Ê

Ó

Ö

C4

å

ß

è

Á

Ø

C5

ä

ü

é

ñ

å

C6

ö

ä

ê

é

æ

C7

ö

ó

ö

C8

ß

á

ø

When Slavic or Russian are chosen the national characters are not used. 76

Page 88

Programming using MAC Programmer+

Date/Time format Setting of date and time format.

Date format: The default format can be YY-MM-DD, YYMMDD, DD.M.YY, DD/MM/YY or MM/DD/YY where Y=year, M=month and D=day.

Time format: The default format can be HH:MM:SS or HH:MM where H=hour, M=minute and S=second.

Clock used: Select Terminal or controller. Terminal means that the terminal’s built-in clock is used and controller means that the clock in the controller system is used in the terminal.

Clock → Controller: Only valid if the clock in the terminal is used. Mark if the clock in the terminal is to be transferred to the controller system. Note! If the controller system has a real-time clock that is activated and the terminal clock is transferred to the same registers in the controller system is using, the clock in the controller system is superior.

Update interval: State how often the terminal will transfer the clock data to the controller system. The value is entered in seconds and 60 is recommended. A shorter updating interval makes the communication between the terminal and the controller system slower.

Controller register: Enter the first address of the registers that will be used to store date and time in the controller system.

77

Page 89

The text of this page cannot be shown here; see it in the PDF.

Page 90

Programming using MAC Programmer+

Terminal options Screen save time: The time in minutes after the last operation on the display when it will switch off. The default setting is 10 minutes. This function is used to optimize the display’s working life. Also see the section Backlight action in the chapter Alarm handling.

Key delay time: The time interval between pressing the same key before the cursor moves to the next position. Used for input of ASCII characters (A-Z etc.). See the section Alpha/numerical keys in the chapter Terminal functions.

Key beep: States whether the terminal will beep when a key is pressed.

Key repeat: States whether the numerical keys, arrow keys and built-in function keys are to be repeated as long as the key is pressed. Function keys and input of ASCII characters (A-Z etc) can not be repeated.

Background: Select terminal background color in the list of choices by clicking BG.

Foreground: Select terminal text color in the list of choices by clicking FG.

Window: Select the color of the windows shown on the display by clicking Windows.

Trend settings Select to store only samples in trends if the value has change since the last sampling.

Store all samples Select to store all samples in trends even if the value has not change since the last sampling. The parameters are valid for all defined trends.

79