Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 14 of 41

E-terminals Programming manual: 6 Graphic presentation and maneuvering, pages 108 to 117

Pages 108 to 117 of 335, from E-terminals Programming manual

The original document is the PDF (4.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Beijer Electronics AB E200

Page 108

Graphic presentation and maneuvering

Parameter

Description

Register pair count

The number of register pair to be drawn as dots or bars for the curve respective.

Value form

Select whether the diagram shall be a bar graph or linear graph for the curve respective. A bar is drawn for each register pair in the bar graph. The X/Y coordinates are marked in as dots between which a line is drawn in a linear graph.

Curve

Select the color of the curve respective.

X Analog signal

The PLC register which contains the first X-coordinate for the curve respective.

Y Analog signal

The PLC register which contains the first Y-coordinate for the curve respective.

Y Scale division

The interval between the scale number on the Y-axis.

Y Scale ticks

The interval between the scale ticks displayed on the Y-axis.

Y Minimum value

The minimum value of the Y-coordinate.

Y Maximum value

The maximum value of the Y-coordinate.

X Scale division

The interval between the scale number on the X-axis.

X Scale ticks

The interval between the scale ticks displayed on the X-axis.

X Minimum value

The minimum value of the X-coordinate.

X Maximum value

The maximum value of the X-coordinate.

Frame

Select if a frame shall be drawn around the object.

Grid

When selected the grid is drawn in the diagram.

BG

Select background color of the object.

Scale

Select the color of the scale for the object.

Grid color

Select the color of the grid in the diagram.

97

Page 109

Graphic presentation and maneuvering

Digital Clock Time object for presenting a digital clock.

Parameter

Description

Day of the week

Select whether the day of the week will be shown.

Date

Select whether the date will be shown.

Time

Select whether the time will be shown.

Time format

Time can be shown either as AM/PM or a 24-hour clock.

Maneuverable

Select whether the clock can be reset in run-time mode.

Frame

Select if a frame shall be drawn around the object.

Font size

Select font size for the text in the object.

Security level

Select security level for the object. 0 means no security level.

BG

Select background color.

Text

Select the color of the text in the object.

Note! A maneuverable Date/Time object must be defined to set the clock in the terminal during run-time.

98

Page 110

Graphic presentation and maneuvering

Digital fill Objects used for filling framed areas with a selected color.

Note! Filling areas that are too irregular can cause system failure in run-time mode. Filling can, in certain cases, make the screen slow.

Parameter

Description

Digital signal

The address of the digital signal.

Maneuvrable

When selected the object can be forced from the terminal in runtime mode.

Security Level

Select security level for the object.

On

Select the color of the object when the signal is 1.

Off

Select the color of the object when the signal is 0.

99

Page 111

Graphic presentation and maneuvering

Placing an object The program calculates what is to be filled in the specified area. It’s therefore important that the object is correctly placed. Wrong placed fillers may cause errors in the application during run-time. The filled area is limited only by static objects and static parts of dynamic objects. Fill objects can be replaced with Digital Symbol or Multi Symbol to give better performance to the project. Object’s placement x TEXT Good! To give the display better response, frame the text so it does not need to be filled.

100

Object’s placement x

TEXT

Bad! The display will be slow, because the program must make many calculations to fill in the irregular areas between letters.

Page 112

Graphic presentation and maneuvering

Digital symbol Object which is used to switch between two chosen symbols depending on the state of a digital signal.

Parameter

Description

Digital signal

The address of the signal.

Symbol OFF

Select the symbol which is to be shown when the signal is 0.

Symbol ON

Select the symbol which is to be shown when the signal is 1.

Maneuverable

When selected the object can be forced from the terminal in runtime mode.

Security Level

Select security level for the object. 0 means no security level.

101

Page 113

Graphic presentation and maneuvering

Digital text Text object which is used to switch between two entered texts depending on the state of a digital signal. The maximum text length is 30 characters.

Parameter

102

Description

Digital signal

The address of the digital signal.

Text 0

The text which is to be shown when the signal is 0.

Text 1

The text which is to be shown when the signal is 1.

Font size

Select font size.

Security Level

Select security level. 0 means no security level.

Maneuverable

When selected the object can be forced from the terminal in runtime mode.

Adjustment

Select whether the text is to be left aligned or centred.

Frame

Select if a frame shall be drawn around the object.

BG

Select background color of the object.

Text

Select text color in the object.

Page 114

Graphic presentation and maneuvering

Jump Object for jumping to another block. Makes it possible to build up a hierarchy of menus in the application. Jumping back to the previous block is done by pressing the [PREV] key (up to nine levels back). See chapter Function Keys.

Parameter

Description

Jump to block

States the number of the block to which the jump is to be made.

Text

Enter any text that will be displayed.

Positions

The number of positions the text will take up on the display.

Font size

Select font size.

Adjustment

Select whether the text shall be left aligned or centred.

Frame

Select if a frame shall be drawn around the object.

BG

Select background color for the object.

Text

Select the color of the text in the object.

Note! If a jump is generated to a block that does not exist in run-time mode an error message is shown.

103

Page 115

Graphic presentation and maneuvering

Message Message object presenting texts from message libraries.

Parameter

Description

Analog signal

Analog signal controlling which text from chosen message library to be shown.

Library

Select the number of a message library. Defined under Message Library in the Function menu.

Font size

Select font size of the text.

Positions

Number of positions to be displayed. 0=automatic adjustment

Security level

Select security level for the object. 0 means no security level.

Maneuverable range

A range of maximum 64 texts can be maneuverable in run-time mode. State the numbers of the first and the last texts of the range. See the section Maneuvering Graphic Blocks.

Adjustment

Select if the text shall be left aligned or centred.

Frame

Select if the text shall be displayed with a frame.

Note! When using Library index register the number of positions should not be 0 since the automatic length adjustment doesn’t work.

For more detailed information, see the chapter Message library.

104

Page 116

Graphic presentation and maneuvering

Multiple choice Objects that can have several states. The object is linked to a register which can assume a maximum of eight states. Each state can be allocated a text, maximum 30 characters long.

Parameter

Description

Analog signal

The register that decides which text that is to be displayed.

Text 0-7

The texts which are to be shown for each state of the object.

Man 0-7

When selected the object can be maneuvered to this state in runtime mode. See the section Maneuvering Graphic Blocks.

Adjustment

Select whether the text shall be left aligned or centred.

Frame

Select if a frame shall be drawn around the object.

Font size

Select font size in the object.

Security Level

Select security level for the object.

BG

Select background color for the object.

Text

Select the color of the text in the object.

105

Page 117

Graphic presentation and maneuvering

Multisymbol Objects that can show one of a maximum of eight different symbols depending on the value in a data register. The PLC register can also control the symbol’s location on the display.

Parameter

Description

Analog signal

The register that decides which symbol to be displayed. If the register contains the value 1 symbol 1 is displayed etc.

Move X

The value which contains the X-coordinate for the object. Permissible values are 0-239 for E300, 0-239 for E600 and 0-319 for E700/E710.

Move Y

The value which contains the Y-coordinate for the object. Permissible values are 0-63 for E300, 0-127 for E600 and 0-239 for E700/E710.

Symbol 0-7

Select the symbol to be displayed. If the value of the register is 0, then symbol 0, is displayed etc.

Note! Move X and Y only need to be stated if the object is to be moved around on the display with the help of the PLC.

106