Page 118
Graphic presentation and maneuvering
Numeric Objects for entry and presentation of values in numerical form. It is used for example to create entry fields.
Parameter
Description
Analog signal
The address of the signal.
Positions
The number of positions the entered value will take up including comma and minus sign.
Decimals
The number of decimals the value shall be entered with.
Minimum value
The minimum limit for maneuvering.
Maximum value
The maximum limit for maneuvering.
Offset and Gain
Used to scale register value. See the section General parameters.
Font size
Select font size in the object.
Security Level
Select security level for the object.
Adjustment
Select if the input field shall be left aligned or centred.
Frame
Select if a frame shall be drawn around the object.
Maneuverable
Select if the object can be altered from the terminal in the run-time mode.
Zero fill
Select if zeros are to be printed out in empty positions.
BG
Select background color for the object.
Text
Select the color of the text in the object.
107
Page 119
Graphic presentation and maneuvering
Numeric table Not valid for E300. Object for creating a table of analog numeric objects.
Parameter
108
Description
Analog signal
The first signal to be presented in the table. Only 16-bit registers can be used if version 4.0 or higher on the terminal is used.
X-size
State the number of signals to be presented horizontally.
Y-size
State the number of signals to be presented vertically.
Positions
The number of positions you should enter the value with including comma and minus sign.
Decimals
The number of decimals you should enter the value with.
Minimum value
The minimum limit for maneuvering.
Maximum value
The maximum limit for maneuvering.
Offset and Gain
Used to scale register value. See the section General parameters.
Font size
Select the size of the text in the object.
Security level
Select the security level for the object.
Maneuverable
Select whether the object can be altered in the run-time mode.
Page 120
Graphic presentation and maneuvering Parameter
Description
Zero fill
Select if zeros are to be printed out in empty positions.
Direction
Select direction for the object, horizontal or vertical. The signals in the table are calculated after this direction.
Table frame
Select whether the whole table shall be shown with a frame.
Adjustment
Select whether the entry field shall be left aligned or centred.
BG
Select background color for the object.
Text
Select the color of the text in the object.
Item frame
Select if every single item in the table shall be shown with a frame.
Note! Minimum value and maximum value are only active when maneuvering the object.
109
Page 121
Graphic presentation and maneuvering
Slide Objects which make it possible to increase or decrease the value of an analog signal.
Parameter
Description
Analog signal
The address of the analog signal.
Scale division
State the interval between the scale numbers to be drawn.
Scale ticks
State the interval between the scale ticks displayed.
Minimum value
The minimum value the object can have.
Maximum value
The maximum value the object can have.
Offset and Gain
Used to scale register value. See the section General parameters.
Security level
Select security level for the object.
Maneuverable
Select whether the object can be altered from the terminal in the run-time mode.
Direction
Select whether the object shall be presented vertically or to the right.
Frame
Select if a frame shall be drawn around the object.
BG
Select background color for the object.
Scale
Select color of the scale in the object.
Button
Select color of the indication button in the object.
Note! The data type formats BCD float and Float without exponent do not work for slide objects.
110
Page 122
Graphic presentation and maneuvering
S-meter Objects for creating a graphic speedometer on the display.
Parameter
Description
Analog signal
The address of the signal.
Scale division
State the interval between the scale numbers to be drawn.
Scale ticks
State the interval between the scale ticks displayed.
Minimum value
The minimum value the object can display.
Maximum value
The maximum value the object can display.
Angle
State the angle, working area, for the object. 10-360 degrees.
Offset and Gain
Used to scale register value. See the section General parameters.
Frame
Select if a frame shall be drawn around the object.
BG
Select background color for the object.
Scale
Select the color of the scale in the object.
Needle
Select the color of the needle in the object.
111
Page 123
Graphic presentation and maneuvering
TCP/IP Command promt A window in which TCP/IP commands can be entered and sent between terminals and personal computers in a TCP/IP network. In run-time previous commands can be called up with the arrow keys [Up] and [Down].
Parameter
112
Description
No. of columns
The width of the window.
No. of rows
The height of the window.
Font size
Select font size in the object.
Enable accelerator keys
Select whether the function keys F1-F4 should write predefined commands in the window.
Accelerator keys
Enter any command that will be written at the command promt by pressing respective function key.
Frame
Select the type of frame the window will be shown with.
BG
Select background color for the window.
Text
Select the color of the text in the window.
Page 124
Graphic presentation and maneuvering
Commands for the TCP/IP Commad promt Command IPCONFIG
Description Gets network parameters/IP address
PING
Testing if a host is available
ROUTE
Show/Add/Delete routes
ARP
Show/Add/Delete IP/Hardware address
For further information about the TCP/IP network we refer to the chapter Network communication.
113
Page 125
Graphic presentation and maneuvering
Touch key Only valid for E710. See the section Maneuvering Graphic Blocks. The object is a pressure-sensitive surface whose function corresponds to a function key. The object is used to change pictures, control digital signals and so on.
Parameter
Description
Action
The type of signal the object shall affect. Predefined functions are described in the chapter Function keys. Increment, Decrement and Set are not available.
Digital signal
The digital signal affected by the object if I/O is selected under Action.
Block
The block that will be displayed if the object is defined as an jump object if block type is selected under Action.
Security level
Select security level for the object.
Button type
Select required type of button, circular, rectangular or invisible.
IO event
States how the object shall affect the signal. Momentary means that the signal is affected as long as the object is touched. Toggle means that the signal is set to one or zero alternately when the object is affected. On means that the signal is set when the object is affected. Off means that the signal is reset when the object is affected.
BG
Select background color for the object.
An invisible, pressure-sensitive “virtual” surface can be used to define the area for block changes in an overview display of, for example, a machine. Detail images are linked to defined parts of the overview display. When the pressure-sensitive areas are pressed, the detail images appear. 114
Page 126
Graphic presentation and maneuvering
Trend Objects which graphically present collected values from analog signals.
Parameter
Description
Name
State the name of the object. The name must be unique for each object.
Curve
Select the curve you want to edit 1-2 in E300, E600 and 1-6 in E700/E710.
Analog signal
The analog signals the object shall sample and present the values for. Only 16-bit numbers can be used. For valid devices see the driver manual.
Color
Select a color for each curve.
Offset and Gain
Used to scale register value. See the section General parameters.
115
Page 127
Graphic presentation and maneuvering Parameter
Description
Enable
The digital signal which when set starts the collection of data. Data collection ceases if the signal is set to zero. The parameter needs not be stated.
Y Min value reg.
The minimum value on the Y-axis loaded from the stated PLC register.
Y Minimum value
The minimum value on the Y-axis. (If Y Min value reg. is defined this is the minimum value that can be loaded from the register.)
Y Max value reg.
The maximum value on the Y-axis loaded from the stated PLC register.
Y Maximum value
The maximum value on the Y-axis. (If Y Max value reg. is defined this is the maximum value that can be loaded from the register.)
Y Scale
States which side of the Y-axis shall be shown, to the left, right, both or neither.
Y Scale division
The interval between the scale number on the Y-axis.
Y Scale ticks
The interval between the scale ticks displayed.
X Sample interval
States the time interval between the collection of data. Minimum value is 1 second and maximum value is 100 hours.
X Stored samples
States how many values shall be stored. The maximum number of values are 4800. Only valid in E700 and E710.
X Time range
States the time interval to be shown in the trend diagram.
X Time scale division
The interval between the scale number on the X-axis.
X Time scale ticks
The interval between the scale ticks displayed.
Sample full limit
State the number of samples when the samples full signal shall be set. Only valid in E700 and E710.
Sample full signal
Select a signal which will be set when the number of samples reach the value stated in the parameter Sample full limit. Only valid in E700 and E710.
Frame
Select if a frame shall be printed around the object.
BG
Select background color for the object.
Scale
Select the color of the scale in the object.
Erase trend data signal
The digital signal which when set will erase all historic trend data. Not valid in E300.
Grid
Select if grid shall be displayed in the object.
Grid color
Select a suitable color for the grid.
Note! If you copy a block containing a trend object you must change the name of the trend object. Two trend objects may not have the same name.
116