Page 128

Graphic presentation and maneuvering

VU-meter Object for creating a graphic VU meter on the display.

Parameter

Description

Analog signal

The address of the signal.

Scale division

State the interval between the scale numbers to be drawn.

Scale ticks

State the interval between the scale ticks displayed.

Minimum value

The minimum value the signal can have.

Maximum value

The maximum value the signal can have.

Offset and Gain

Used to scale register value. See the section General parameters.

Frame

Select if a frame shall be drawn around the object.

BG

Select background color for the object.

Scale

Select the color of the scale in the object.

Needle

Select the color of the needle in the object.

117

Page 129

Graphic presentation and maneuvering

6.3 Maneuvering Graphic Blocks Not valid for E710. Move between the maneuverable objects with the arrow keys. Objects selected are highlighted with a blinking frame.

Selecting maneuverable objects The arrow keys are used to jump between maneuverable objects in the terminal during run-time. The choice of object is according to the following principle: The cursor’s position is assumed to be the center of a cross. Press the right arrow and the first object found in area A according to the diagram below is selected. Should the system not find an object in the narrow field on the right, it searches in area a. The down arrow searches in areas B and b, the left arrow searches in areas C and c and the up arrow searches in areas D and d. . c

D d A

C b

Cursor position

B a

Digital objects Digital objects, text, symbol and filled objects, switch status when [ENTER] is pressed. If the INC and DEC functions have been linked to function keys, the signal linked to the object with these keys is set and reset respectively.

118

Page 130

Graphic presentation and maneuvering

Analog objects ASCII objects Mark the object and enter the required text. Finish writing with [ENTER].

Message objects Place the cursor on the object and press [ENTER]. An option list is now shown with all the maneuverable states. Move stepwise to the required state and press [ENTER] and the analog signal linked to the object is forcibly set.

Multichoice objects Place the cursor on the object and press [ENTER]. An option list is now shown with all the maneuverable states. Move stepwise to the required state and press [ENTER] and the analog signal linked to ththe object is forcibly set.

Numerical objects To maneuver numerical objects write in the value and press [ENTER]. If a value too high or too low is entered the max and min value for the object is shown. This information will also be shown if you press [ENTER] when the object is maneuverable.

Numerical table objects When the table object is marked press [ENTER] to select the first item in the table. Use the arrow keys to move the cursor between the items in the table. Change the value in the marked item and press [ENTER].

Potentiometer objects The object is maneuvered with the arrow keys by placing the cursor on the object and pressing [ENTER]. The value can now be increased/decreased with the number that corresponds to the setting ”Scale Ticks” in the object. End maneuvering with [ENTER]. The object can also be maneuvered with the Increment and Decrement functions on the condition that they are linked to the function keys, see the Function keys section.

119

Page 131

Graphic presentation and maneuvering

Bar object The min/max indicators for bar objects can be set at the current value by pressing [ENTER]. The max/min indicators are reset when you touch the bar.

Trend objects Not valid in E50, E100, E200 and E300. Trend curves can show historic data in the run-time mode. Mark the required trend object and press [ENTER]. A dialog square is now shown and the date for the data to be presented can be chosen. ”History” is shown at the bottom of the square. Press [ENTER] again to return to real-time display. Trend data is stored in the files whose names are stated when the trend object is defined.

120

Page 132

Graphic presentation and maneuvering

Other objects Digital clock The digital clock can be altered by marking the object and giving the required time. Finish with [ENTER]. Note! If you use the clock in the PLC system and you want to change it, this must be done in run-time mode.

Jump object Mark the object and press [ENTER].

TCP/IP Command promt TCP/IP Commands can be written on the highlighted row. Previous commands can be called up by pressing the arrow keys [Up] and [Down].

6.4 Using the touch screen This section is only valid for E710. E710 does not have a built-in keyboard. All maneuvering takes place using the touch screen. Because of its sensitivity, you should only press one point on the screen at any given time. Otherwise, the terminal will interpret the midpoint of two points pressed.

Digital objects Digital objects, text, symbol and filled object change status when you touch them.

Analog objects ASCII objects When you touch the object an alphanumeric keyboard will be shown on the screen. Touch in the required text and end with [ENTER].

Multichoice objects When you touch the object a choice list appears. Select the required object by touching it. 121

Page 133

Graphic presentation and maneuvering

Numerical objects When you touch the object a numeric keyboard appears. Touch the new value and end with [ENTER].

Numerical table objects When you touch the item in the table object a numeric keyboard appears. Touch the new value and end with [ENTER].

Potentiometer objects Touch the button in the object and drag to maneuver the object.

Bar object The max/min indicators are reset when you touch the bar.

Trend objects Trend curves can show historic data in run-time. When you touch the object a dialog box appears where you can choose the time interval and date for presented data. Double arrow Single arrows + ^

Move the trend one window. Move the trend 1/4 window. Zoom up the trend. Zoom down the trend. Return to default settings.

Return to realtime trend by touching the object again.

122

Page 134

Graphic presentation and maneuvering

Other objects Digital clock When you touch the object a numeric keyboard appears. Touch the required time and end with [ENTER]. Note! If you use the clock in the PLC system and you want to change it, this must be done in run-time mode.

Jump object Touch the object to activate the jump.

Alphanumeric keyboard The alphanumeric keyboard appears when you maneuver, e.g. an ASCII object.

Key

Description

A-Z

Used to enter required text.

ESC

Close down the keyboard and return to previous level.

←

Delete one character to the left.

CLR

Delete all characters.

DEL

Delete the character on cursor position.

↵

Confirm the settings and close down the keyboard.

» «

Move the cursor to the right. Move the cursor to the left.

123

Page 135

Graphic presentation and maneuvering Key

Description a-z

Switch between upper case and lower case letters.

0-9

Switch between lower case letters and digits and special characters.

Numeric keyboard The numeric keyboard appears when you maneuver, e.g. a numeric object.

Key

124

Description

0-9

Used to enter required text.

ESC

Close down the keyboard and return to previous level.

←

Delete one character to the left.

CLR

Delete all characters.

DEL

Delete the character at cursor position.

↵

Confirm the settings and close down the keyboard.

» «

Move the cursor to the right. Move the cursor to the left.

Page 136

Graphic presentation and maneuvering

Choice list Choice lists will also appear on the screen. In the choice list you use the arrows to show the uppermost or lowermost choice respectively. [CANCEL] is used to close down the list without making a selection.

125

Page 137

Graphic presentation and maneuvering

126