Page 272
LEDs
20 LEDs The chapter is not valid for E50 and E100. The terminal has LEDs built in, that are connected to registers defined under LED in the Functions menu. The content of the register determines the color and any blinking of the LED according to the following table. Register value(Hex)
Register value(Dec)
Blinking frequency(Hz)
Color
00
0
-
None
01
1
-
Green
02
2
-
Red
11
17
5
Green
12
18
5
Red
21
33
2.5
Green
22
34
2.5
Red
31
49
1.2
Green
32
50
1.2
Red
41
65
0.6
Green
42
66
0.6
Red
261
Page 273
LEDs
262
Page 274
Function keys
21 Function keys This section describes how to use the function keys. A function key is linked to a signal by writing in its address after each key or by selecting a function from the choice list. The signal linked to a function key is activated according to the function linked to the key when it was defined. Note! It is only possible to affect two signals linked to fuction keys at the same time. I.e. if more than two function keys are pressed at the same time it is only the two presst first that are affected.
The terminal has different numbers of function keys depending on the type of terminal.
F1
F5
F2
F6
F3
F7 F8
F4
F1
F9
F3
F2
F10
F11
F12
F13
F4
F14
F15
F5
F16
263
Page 275
Function keys
F1
F1
264
F2
F2
F3
F3
F4
F5
F4
F5
F6
F7
F8
Page 276
Function keys
F1
F5
F2
F6
F3
F7
F4
F8
F9
F10
F11
F12
F13
F14
F15
F16
265
Page 277
Function keys
F1
F5
F2
F6
F3
F7
F4
F8
F9
F10
F1
F1
266
F11
F2
F2
F3
F13
F14
F15
F3
F4
F5
F6
F4
F5
F6
F12
F7
←
F16
F8
F7
F8
↵
Page 278
Function keys
21.1 Definitions There are two ways of defining the function keys; globally or locally. Global function keys are defined and used in the whole application, that is they apply in all the blocks. Local function keys are defined and used in a single block. A global definition is always available in the run-time mode assuming that the block shown on the display does not have a local definition for the function key in question. Local definitions have a higher priority than global ones. Global function keys are defined under Function keys in the Functions menu. Local function keys are defined in the blockheader of current block under F-keys.
267
Page 279
Function keys
Function
268
Description
IO
The signal activated with the function key.
Event
How the key affect the current digital signal. Momentary means that the signal is set as long as the key is active. Toggle means that the signal is set and reset respectively when the key is activated. Set means that the signal is set when the key is activated and remain set. Reset means that the signal is reset when the key is activated and remain reset. Grouped means that all signals linked to a function key with current group number is reset. The group number is entered under Value. A group can contain max 8 function keys. Set Analog means that the analog signal linked to the function key gets the value entered under Value. Inc Analog means that the analog signal linked to the function key shall increase the value with the value entered under Valure. Dec Analog means that the analog signal linked to the function key shall decrease the value with the value entered under Value.
Set analog object to
Sets selected analog object to entered value.
Increment analog object with or set digital object
Increases the value of an maneuverable analog object with entered value or sets a selected digital object.
Decrement analog object with or reset digital object
Decreases the value of an maneuverable analog object with entered value or sets a selected digital object.
Set digital object momentarily
Sets selected digital object as long as the key is pressed.
Jump to block
Jumps to the block with number nnn.
Security level
Function keys can be defined with a security level. The security level means that the operator must log in with a password for the same or a higher security level to be able to use the function key.
Fxx
The function key linked to one of the functions.
Page 280
Function keys Other functions for Function keys Function
Description
Load recipe
Load recipe from the memory of the terminal.
Save recipe
Save recipe into the memory of the terminal.
Delete recipe
Erase recipe from the memory of the terminal.
Login to specified security level
Logging in.
Logout
Logging out.
Change login password
Change password.
Scroll one page up
Scrolling the pages in text blocks and in the alarm list.
Scroll one page down
Scrolling the pages in text blocks and in the alarm list.
Zoom up text size
Increase the text size in the alarm list.
Zoom down text size
Reduce the text size in the alarm list.
Save recipe on memory card
Save recipe on the memory card defined as backup.
Load recipe from mem- Load recipe from the memory card defined as backup. ory card Erase recipe on memory card
Erase recipe from the memory card defined as backup.
Save project on memory card
Save project on the memory card defined as backup.
Load project from memory card
Load project from the memory card defined as backup.
Erase project on memory card
Erase project from the memory card defined as backup.
Acknowledge alarm
Acknowledges alarms in the alarm list.
Show alarm list
Shows the alarm list (block 990).
Jump to info block connected to the alarm
Jump to a block connected to the alarm. See the chapter Alarm handling.
List alarm groups
Select from which alarm group alarms will be shown in the alarm list. Not valid in E100 and E200.
Return to previous block
Show the previous block, works for nine levels. When returning to block 0 you can’t jump to the previous block using this function. If login in run-time is done on a higher security level than current level this function can’t be used for block jump.
269
Page 281
Function keys Function
Description
Show info about analog object
Shows the min. and max. values for analog objects in the Textblock in the run-time mode.
Show diagnostics page
Shows the information page. See the chapter Terminal functions.
21.2 Jump to block with the function keys This function makes it possible to use the function keys for jumping to blocks without using the Display signal. When the key is defined, locally or globally, you select Jump to block in the list of options. Changing block via function keys is the easiest way to change block. The method do not occupy any digital signal in the controller system.
270