2. Motor Does Not Stop 2.1 Check MV-53 (RUN/STOP STATE) If MV-53 = 128, then 2.2 If MV-53 = 64, then 2.2 If MV-53 = 32, then J3 pin 13 is (at least momentarily) shorted to common If MV-53 = 1, then J3 pin 16 is shorted to common
2.2 Measure voltage of J2-Pin 4 with respect to J2-Pin 3. If voltage = zero Verify motor armature wiring. If voltage not = zero Consult MV-54 and Page C-9 to determine if Ramp is disabled. If true, J4-Pin 7 is shorted to common. If false, call factory.
3. Motor Does Not Run 3.1 Check MV-53 If MV-53 = 128, then J3 Pin 14 is not shorted to common If MV-53 = 64, then J3 Pin 11 is (at least momentarily) not shorted to common If MV-53 = 32, then check fuses on Power Drive Board * If MV-53 = 1, then check fuses on Power Drive Board
4. Motor Runs at Wrong Speed 4.1 Determine M-Drive control format
If Master, then 4.2 If Follower, then 4.3 If Offset, then 4.4 If Jog, then 4.5 If Direct, then 4.6 4.2 Master Control Format
Check MV-53 lf MV-53 not = 32, then 9.1 Check MV-50 (Active Format)
Hf MV-50 not = 1, then 9.2 Check Setpoint if setpoint incorrect, then enter correct setpoint and exit Trouble-shooting outline. Check MV-45 (Scaled Reference)
If MV-45 incorrect, then 9.3
IF MV-45 correct, then 4.7
In addition to the logic fuse on the rear of the M-Drive, there are two power fuses located on the M-Drive Power Drive Board. These are used to protect the power drive portion of the M-Drive. Remove the rear plate and pull out the Power Drive Board to replace these fuses (Fenner Part No 6441-0315).
Page 9-7
2. Motor Does Not Stop 2.1 Check MV-53 (RUN/STOP STATE) If MV-53 = 128, then 2.2 If MV-53 = 64, then 2.2 If MV-53 = 32, then J3 pin 13 is (at least momentarily) shorted to common If MV-53 = 1, then J3 pin 16 is shorted to common
2.2 Measure vottage of J2-Pin 4 with respect to J2-Pin 3. If voltage = zero Verify motor armature wiring. If voltage not = zero Consult MV-54 and Page C-9 to determine if Ramp is disabled. If true, J4-Pin 7 is shorted to common. If false, call factory.
3. Motor Does Not Run 3.1 Check MV-53 If MV-53 = 128, then J3 Pin 14 is not shorted to common If MV-53 = 64, then J3 Pin 11 is (at least momentarily) not shorted to common If MV-53 = 32, then check fuses on Power Drive Board * If MV-53 = 1, then check fuses on Power Drive Board
4. Motor Runs at Wrong Speed 4.1 Determine M-Drive control format
If Master, then 4.2 If Follower, then 4.3 If Offset, then 4.4 If Jog, then 4.5 If Direct, then 4.6 4.2 Master Control Format
Check MV-53 lf MV-53 not = 32, then 9.1 Check MV-50 (Active Format)
lf MV-50 not = 1, then 9.2 Check Setpoint
If setpoint incorrect, then enter correct setpoint and exit Trouble-shooting outline. Check MV-45 (Scaled Reference)
lf MV-45 incorrect, then 9.3
IF MV-45 correct, then 4.7
In addition to the logic fuse on the rear of the M-Drive, there are two power fuses located on the M-Drive Power Drive Board. These are used to protect the power drive portion of the M-Drive. Remove the rear plate and pull out the Power Drive Board to replace these fuses (Fenner Part No 6441-0315).
Page 9-7
Page 112
4.3 Follower Control Format
Check MV-53 If MV-53 not = 32, then 9.1 Check MV-50 If MV-50 not = 2, then 9.2 Check Setpoint If setpoint incorrect, then enter correct setpoint and exit Trouble-shooting outline. Check MV-45 (Scaled Reference) If MV-45 incorrect, then 9.3 IF MV-45 correct, then 4.7 4.4 Offset Control Format Check MV-53 If MV-53 not = 32, then 9.1 Check MV-50 If MV-50 not = 3, then 9.2 Check Setpoint If setpoint incorrect, then enter correct setpoint and exit Trouble-shooting outline. Check MV-45 (Scaled Reference) If MV-45 incorrect, then 9.3 If MV-45 correct, then 4.7
4.5 Jog Control Format Check MV-53 lf MV-53 not = 1, then 9.1 Check CP-5 (Jog Setpoint) lf CP-5 incorrect, then enter correct setpoint and exit Trouble-shooting outline.
Check MV-45 (Scaled Reference) If MV-45 incorrect, then 9.3 IF MV-45 correct, then 4.7
4.6 Direct Control Format
Check MV-53 lf MV-53 not = 32, then 9.1 Check MV-50 lf MV-56 not = 0, then 9.2
Check CP-6 (Direct Setpoint) If CP-6 incorrect, then enter correct setpoint and exit Trouble-shooting outline. If CP-6 correct, then 4.12
4.7 Check MV-46 (Ramped Reference) If MV-46 correct, then 48 if MV-46 incorrect, then consult Table 9-1 to determine if Ramp is disabled, else Ramp is in Progress. Page 9-8
4.3 Follower Control Format
Check MV-53 If MV-53 not = 32, then 9.1 Check MV-50 If MV-50 not = 2, then 9.2 Check Setpoint If setpoint incorrect, then enter correct setpoint and exit Trouble-shooting outline. Check MV-45 (Scaled Reference) If MV-45 incorrect, then 9.3 IF MV-45 correct, then 4.7 4.4 Offset Control Format Check MV-53 If MV-53 not = 32, then 9.1 Check MV-50 If MV-50 not = 3, then 9.2 Check Setpoint If setpoint incorrect, then enter correct setpoint and exit Trouble-shooting outline. Check MV-45 (Scaled Reference) If MV-45 incorrect, then 9.3 If MV-45 correct, then 4.7
4.5 Jog Control Format Check MV-53 lf MV-53 not = 1, then 9.1 Check CP-5 (Jog Setpoint) lf CP-5 incorrect, then enter correct setpoint and exit Trouble-shooting outline.
Check MV-45 (Scaled Reference) If MV-45 incorrect, then 9.3 IF MV-45 correct, then 4.7
4.6 Direct Control Format
Check MV-53 lf MV-53 not = 32, then 9.1 Check MV-50 lf MV-56 not = 0, then 9.2
Check CP-6 (Direct Setpoint) If CP-6 incorrect, then enter correct setpoint and exit Trouble-shooting outline. If CP-6 correct, then 4.12
4.7 Check MV-46 (Ramped Reference) If MV-46 correct, then 48 if MV-46 incorrect, then consult Table 9-1 to determine if Ramp is disabled, else Ramp is in Progress. Page 9-8
Page 113
4.8 Consult Table 8-1 for Open/Closed Loop status if Closed Loop, then If Open Loop, then J4-Pin 6 is shorted to common
4.9 Check MV-68 (Trim Authority) Most systems should be able to operate with trim authorities as low as 20%. If this is not true, either the system (drive) is nonlinear, under powered, or improperly scaled. If CP-68 < 20, then set CP-68 to 20 or higher If CP-68 > 20, then
4.10 Check CP-65 (Reset) This value should be the smallest reset possible consistent with stable operation. 2000 - 4000 is reasonable.
4.12 Check Motor Armature and field connections 5. Motor Runs at Correct Speed but does not Run Fast Enough
5.1 Check CP-11 (Maximum RPM) 5.2 Verify current limit calibrations IAW Page 4-1.
6. Motor Runs at Correct Speed but does not Run Slow Enough 6.1 Check CP-10 (Minimum RPM)
7. Motor Runs Unstable 7.1 Enter 100 at CP-68, and tune the M-Drive IAW Page 5-12.
4.9
4.10
Page 9-9
4.8 Consult Table 8-1 for Open/Closed Loop status if Closed Loop, then 48 If Open Loop, then J4-Pin 6 is shorted to common
4.9 Check MV-68 (Trim Authority) Most systems should be able to operate with trim authorities as low as 20%. If this is not true, either the system (drive) is nonlinear, under powered, or improperly scaled. if CP-68 < 20, then set CP-68 to 20 or higher If CP-68 > 20, then 4.10
4.10 Check CP-65 (Reset) This value should be the smallest reset possible consistent with stable operation. 2000 - 4000 is reasonable.
4.12 Check Motor Armature and field connections
5. Motor Runs at Correct Speed but does not Run Fast Enough 5.1 Check CP-11 (Maximum RPM) 5.2 Verify current limit calibrations IAW Page 4-1.
6. Motor Runs at Correct Speed but does not Run Slow Enough 6.1 Check CP-10 (Minimum RPM)
7. Motor Runs Unstable 7.1 Enter 100 at CP-68, and tune the M-Drive IAW Page 5-12.
Page 9-9
Page 114
8. Tach Reads Incorrectly
8.1 Check MV-54 and Table 9-1 to insure M-Drive is operating Closed Loop.
8.2 Check MV-44 If MV-44 is not near zero, then motor is not running at the correct speed 8.3 Verify MV-45 is correct using the appropriate formula from 9.3 2 3 8.4 Check MV-45 and Table 7-1 to determine if M-Drive is in Primary or Secondary Mode. If Primary Mode, Check MV-63. if M-Drive in Primary Mode and MV-63=1, then calculate tach indication: MV-40 = (CP-22 * MV-43 * 60)/(CP-34 * CP-31)
If M-Drive in Primary Mode and MV-63=2, then calculate tach indication:
MV-40 = (CP-22 * MV-43 * GP-33 * GP-30) (MV-41 * CP-34 * CP-31)
If Secondary Mode, Check MV-64. If M-Drive in Secondary Mode and MV-64=1, then calculate tach indication: MV-40 = (CP-23 * MV-43 * 60)/(CP-37 * CP-31)
If M-Drive in Secondary Mode and MV-64=2, then calculate tach indication: MV-40 = (CP-23 * MV-43 * CP-36 * CP-30) (MV-41 * CP-37 * CP-31)
Page 9-10
8. Tach Reads Incorrectly 8.1 Check MV-54 and Table 9-1 to insure M-Drive is operating Closed Loop. 8.2 Check MV-44 If MV-44 is not near zero, then motor is not running at the correct speed 8.3 Verify MV-45 is correct using the appropriate formula from 9.3 2 3 8.4 Check MV-45 and Table 7-1 to determine if M-Drive is in Primary or Secondary Mode. If Primary Mode, Check MV-63. if M-Drive in Primary Mode and MV-63=1, then calculate tach indication: MV-40 = (CP-22 * MV-43 * 60)/(CP-34 * CP-31)
If M-Drive in Primary Mode and MV-63=2, then calculate tach indication:
MV-40 = (CP-22 * MV-43 * GP-33 * GP-30) (MV-41 * CP-34 * CP-31)
If Secondary Mode, Check MV-64. If M-Drive in Secondary Mode and MV-64=1, then calculate tach indication: MV-40 = (CP-23 * MV-43 * 60)/(CP-37 * CP-31)
If M-Drive in Secondary Mode and MV-64=2, then calculate tach indication: MV-40 = (CP-23 * MV-43 * CP-36 * CP-30) (MV-41 * CP-37 * CP-31)
Page 9-10
Page 115
9. System Checks 9.1 RUN/STOP LOGIC If MV-53 = 128, then J3-Pin 14 is not shorted to common.
If MV-53 = 64, then J3-Pin 11 was not (at least temporarily) shorted to common.
If MV-53 = 32, then J3-Pin 13 was (at least temporarily) shorted to common. IF MV-53 = 1, then J3-Pin 16 is shorted to common.
9.2 Format Consult MV-54 and Table 7-1 to verify Primary/Secondary mode. If Primary Mode, enter proper format into CP-61. lf Secondary Mode, enter proper format in CP-62.
9.3 Scaled Reference
Determine Mode and Format, then calculate MV-45 per the correct equation.
MODE FORMAT EQUATION
PRI 0 MV-45=0 PRI 1 MV-45 = (SP*CP34*CP31)/(CP20 *60) PRI 2 MV-45= (SP*MV41*CP34*CP31) (CP20*CP33*CP-30) 3 MV-45 = (SP*MV41*CP34*CP31) (CP20*CP33*CP-30) +
PRI
(MV42*CP34*CP31)/(CP35*CP32) + (CP75 - CP76).
SEC 0 MV-45=0
SEC 1 MV-45 = (SP*CP37*CP31)/(CP21 *60)
SEC 2 MV-45= (SP*MV41*CP37*CP31) (CP21*CP36*CP-30)
SEC 3 MV-45= (SP*MV41*CP37*CP31)
(CP21*CP36*CP-30) + (MV42*CP37*CP31)/(CP38*CP32) + (CP77 - CP78).
10. Brown Out Watch Dog (- - -1, ---2 or, 3 displayed)
A display reading of ---1, --2 or --3 indicates an M-Drive environment problem; i.e., electrical noise severe enough to disrupt the microprocessor or a temporary interruption of AC power requirements. Generally, --1 indicates an AC power problem, ---2 indicates noise, and, -3 indicates noise has disrupted the parameter RAM. If a ---2 or --3 appears, the programming Control Parameters should be verified and a Clear 7 procedure performed (see Page 9-13).
Page 9-11
9. System Checks 9.1 RUN/STOP LOGIC. If MV-53 = 128, then J3-Pin 14 is not shorted to common. If MV-53 = 64, then J3-Pin 11 was not (at least temporarily) shorted to common. If MV-53 = 32, then J3-Pin 13 was (at least temporarily) shorted to common. IF MV-53 = 1, then J3-Pin 16 is shorted to common.
9.2 Format Consult MV-54 and Table 7-1 to verify Primary/Secondary mode. If Primary Mode, enter proper format into CP-61. lf Secondary Mode, enter proper format in CP-62.
9.3 Scaled Reference Determine Mode and Format, then calculate MV-45 per the correct equation.
MODE FORMAT EQUATION
PRI 0 MV-45=0 PRI 1 MV-45 = (SP*CP34*CP31)/(CP20 *60) PRI 2 MV-45= (SP*MV41*CP34*CP31) (CP20*CP33*CP-30) 3 MV-45= (SP*MV41*CP34*CP31) (CP20*CP33*CP-30) +
PRI
(MV42*CP34*CP31)/(CP35*CP32) + (CP75 - CP76).
SEC 0 MV-45=0
SEC 1 MV-45 = (SP*CP37*CP31)/(CP21 *60)
SEC 2 MV-45= (SP*MV41*CP37*CP31) (CP21*CP36*CP-30)
SEC 3 MV-45= (SP*MV41*CP37*CP31)
(CP21*CP36*CP-30) + (MV42*CP37*CP31)/(CP38*CP32) + (CP77 - CP78).
10. Brown Out Watch Dog (--1, --2 or, 3 displayed)
A display reading of --1, --2 or, -3 indicates an M-Drive environment problem; ie., electrical noise severe enough to disrupt the microprocessor or a temporary interruption of AC power requirements. Generally, ---1 indicates an AC power problem, ---2 indicates noise, and, -3 indicates noise has disrupted the parameter RAM. If a ---2 or, -3 appears, the programming Control Parameters should be verified and a Clear 7 procedure performed (see Page $-13).
Page 9-11
Page 116
Part Number___
6441-0200 6441-0315 6340-0021 6310-0226
6310-0224
6310-0227
6310-0228
3200-1680
Call Factory
Page 9-12
SPARE PARTS LIST
Description Fuse 1A Fuse 15A Shunt Jumper
7 Position Terminal Connector (Power Drive Board)
16 Position Terminal Connector (CPU Board)
16 Position Terminal Connector (Drive Board)
18 Position Terminal Connector (CPU Board)
Analog Input/Output Option Board PROM Number
Part Number___
6441-0200 6441-0315 6340-0021 6310-0226
6310-0224
6310-0227
6310-0228
3200-1680 Call Factory
Page 9-12
SPARE PARTS LIST
Description Fuse 1A Fuse 15A Shunt Jumper
7 Position Terminal Connector (Power Drive Board)
16 Position Terminal Connector (CPU Board)
16 Position Terminal Connector (Drive Board)
18 Position Terminal Connector (CPU Board)
Analog Input/Output Option Board PROM Number
Page 117
EPROM LOCATION EPROM LOCATION
It is possible that the EPROM may be replaced at the customer's location. Figure 9-1 It is possible that the EPROM may be replaced at the customer's location. Figure 9-1 below illustrates the location of this EPROM. below illustrates the location of this EPROM. (TOP) (TOP) EPROM EPROM Chip Chip Figure 9-1: EPROM Location Figure 9-1: EPROM Location RESTORE SETTINGS RESTORE SETTINGS CAUTION CAUTION This procedure restores the M-Drive to the factory default settings. This procedure restores the M-Drive to the factory default settings. Any User-entered parameters or programming will be erased. Any User-entered parameters or programming will be erased. 1. Remove power from the M-Drive. 1. Remove power from the M-Drive. 2. While pressing "Clear" and "7" on the Operator Keypad, apply power to the 2. bi pressing "Clear" and "7" on the Operator Keypad, apply power to the -Drive. -Drive. Response: The M-Drive restores the factory default settings, and then performs Response: The M-Drive restores the factory default settings, and then performs the Power Up routine described on Page 9-1. the Power Up routine described on Page 9-1.
Page 9-13 Page 9-13
Page 118
NOTES NOTES
Page 9-14 Page 9-14
Page 119
APPENDIX A - FEEDBACK SENSORS A
INTRODUCTION
For the M-Drive to accurately control a motor, the M-Drive must receive a feedback signal reflecting the actual motor speed. This appendix contains information concerning three methods to provide this signal: Ring Kits, Bracket mount sensors, and Encoders or proximity sensors. RING KITS
A ring kit is used to provide a magnetic sensor which detects the actual speed of the motor being controlled. This ring kit is typically comprised of 2 parts: A machined aluminum ring with a specific number of gear teeth and a specific bore diameter, and a magnetic pickup which mounts in the ring.
Ring kits are divided into two groups: Standard Ring Kits, and XP Ring Kits. XP is an abbreviation for Explosion Proof.
STANDARD RING KITS NEMA G-FACE RING MOUNT Best performance is achieved with a SM3N-A magnetic pickup mounted in a C-face ring.
Shielded cable connections to the magnetic pickup are made by soldering and- taping inside the conduit adapter box as shown below.
_ - - 1/2 NPT
SETSCREW
{mati
Figure A-1: SM3N-A Magnetic Pickup Page A-1
APPENDIX A - FEEDBACK SENSORS A
+885 +.983
INTRODUCTION
For the M-Drive to accurately control a motor, the M-Drive must receive a feedback signal reflecting the actual motor speed. This appendix contains information concerning three methods to provide this signal: Ring Kits, Bracket mount sensors, and Encoders or proximity sensors. RING KITS
A ring kit is used to provide a magnetic sensor which detects the actual speed of the motor being controlled. This ring kit is typically comprised of 2 parts: A machined aluminum ring with a specific number of gear teeth and a specific bore diameter, and a magnetic pickup which mounts in the ring.
Ring kits are divided into two groups: Standard Ring Kits, and XP Ring Kits. XP is an abbreviation for Explosion Proof.
STANDARD RING KITS NEMA C-FACE RING MOUNT
Best performance is achieved with a SM3N-A magnetic pickup mounted in a C-face ring. Shielded cable connections to the magnetic pickup are made by soldering and- taping inside the conduit adapter box as shown below.
ee 1/2 NPT
SETSCREW
Figure A-1: SM3N-A Magnetic Pickup Page A-1
-885 +.983
Page 120
XP RING KITS
The 7000-0450 Nema 56C pickup mounting ring used in the XP (explosion proof) kits is 1.280 inches thick and when "sandwiched" between a 56C frame XP motor and a gear box reduces the shaft engagement into the gear box by 1.280 inches.
For this application, a 3 to 5 inch armature shaft which is one inch longer than standard must be specified.
Page A-2, =, 4 1/2" INTERNAL 6500-0038 / PIPE THREAD XP PICKUP \, Qa 7000-0450 3 io
56C MOUNTING RING (1.160 THICK)
30T GEAR
Figure A-2: XP Magnetic Pickup Ring Mounting
XP RING KITS
The 7000-0450 Nema 56C pickup mounting ring used in the XP (explosion proof) kits is 1.280 inches thick and when "sandwiched" between a 56C frame XP motor and a gear box reduces the shaft engagement into the gear box by 1.280 inches.
For this application, a 3 to 5 inch armature shaft which is one inch longer than standard must be specified., = 1/2" INTERNAL 6500-0038 [- PIPE THREAD XP PICKUP \, 7000-0450 = 56C MOUNTING io om RING __ Ss (1.160 THICK) Sa a uw [=] S !
30T GEAR
Figure A-2: XP Magnetic Pickup Ring Mounting Page A-2