Page 41
REMOTE SCROLL DOWN
The Remote Scroll Down input decrements the active setpoint (see Setpoint Select on Page 3-12 for setpoint selection information). This input decrements the active setpoint whether or not the setpoint is displayed.
There are two methods to decrement the active setpoint using Remote Scroll Down. Each closure of this input decrements the active setpoint 1 Engineering Unit. In addition, the active setpoint decrements 1 Engineering Unit every half second while this input is held closed.
NO EFFECT 14 - Vv ° 15 REMOTE SCROLL DOWN J4
Figure 3-21: Remote Scroll Down
ANALOG INPUT (Requires Optional Analog I/O Board)
The Analog Input can be used to replace either one of the three frequency inputs or one of the four internal setpoint inputs. (For a detailed discussion concerning analog input uses, refer to Chapter 8 - Advanced Programming.) Figure 3-22 below illustrates the wiring for the analog input.
Note: The Analog Input can accept either a 0 to 10 VDC or 4 to 20 mA current source. Refer to Chapter 2 - Configuration, for the Analog Input configuration procedure.
SHIELD 1g [a3 INPUT SIGNAL 16 COMMON 17 A Ne 34
Figure 3-22: Analog Input
Page 3-15
REMOTE SCROLL DOWN
The Remote Scroll Down input decrements the active setpoint (see Setpoint Select on Page 3-12 for setpoint selection information). This input decrements the active setpoint whether or not the setpoint is displayed.
There are two methods to decrement the active setpoint using Remote Scroll Down. Each closure of this input decrements the active setpoint 1 Engineering Unit. In addition, the active setpoint decrements 1 Engineering Unit every half second while this input is held closed.
NO EFFECT 14 Vv ° 15 REMOTE SCROLL DOWN J4
Figure 3-21: Remote Scroll Down
ANALOG INPUT (Requires Optional Analog I/O Board)
The Analog Input can be used to replace either one of the three frequency inputs or one of the four internal setpoint inputs. (For a detailed discussion concerning analog input uses, refer to Chapter 8 - Advanced Programming.) Figure 3-22 below illustrates the wiring for the analog input.
Note: The Analog Input can accept either a 0 to 10 VDC or 4 to 20 mA current source. Refer to Chapter 2 - Configuration, for the Analog Input configuration procedure.
SHIELD 1B [a3 INPUT SIGNAL 16 COMMON 17 - Nee 34
Figure 3-22: Analog Input
Page 3-15
Page 42
4) ELECTIVE OUTPUTS
CONTROL OUTPUTS
The M-Drive Contro! Outputs are all open-collector relay drivers (specs listed on Page viii). An external DC power supply is required to provide power to the relays. Free-wheeling diodes are incorporated and need not be added externally.
Figure 3-23 illustrates the wiring for the first three elective outputs. The remaining outputs follow the same pattern.
Diode Protect 8 + EXT. Zero Speed Le) (Ri) pe POWER High Alarm 18 (R3) SUPPLY Low Alarm 11 (3) (58V Max) Common 14 ~ v1
Figure 3-23: Elective Outputs
Page 3-16
4) ELECTIVE OUTPUTS
CONTROL OUTPUTS
The M-Drive Contro! Outputs are all open-collector relay drivers (specs listed on Page viii). An external DC power supply is required to provide power to the relays. Free-wheeling diodes are incorporated and need not be added externally.
Figure 3-23 illustrates the wiring for the first three elective outputs. The remaining outputs follow the same pattern.
Diode Protect 8 + EXT. Zero Speed Le) (Ri) pe POWER High Alarm 18 (R3) SUPPLY Low Alarm 11 (3) (58V Max) Common 14 ~ v1
Figure 3-23: Elective Outputs
Page 3-16
Page 43
ZERO SPEED (J1 Pin 9)
The Zero Speed output may be controlled either by the Ramped Reference, or by both the Ramped Reference and the Feedback. For additional information, refer to CP-74 on Page C-13.
HIGH ALARM (J1 Pin 10)
The High Alarm output is used to indicate when the speed, as identified by the Feedback Input, exceeds a level that is specified by the operator. The High Alarm output is high (inactive) when the feedback is below this level. It is low (active) when the feedback is at or above this level. (See CP-13 on Page C-3.)
LOW ALARM (J1 Pin 11)
The Low Alarm output is used to indicate when the feedback is below a level that is specified by the operator. The Low Alarm output is high (inactive) when the feedback is above this level. It is low (active) when the feedback is at or below the specified level. (See CP-12 on Page C-3.)
RAMPED ERROR (ERROR ALARM 1) (J1 Pin 12) The Ramped Error output is used to indicate when the speed error (Ramped Reference minus feedback) is at or outside a band specified by the operator. This output is high
(inactive) when the error is within the specified band. It is low (active) when the error is at or exceeds the specified band. (See CP-14 on Page C-3.)
SCALED ERROR (ERROR ALARM 2) (J1 Pin 13)
The Scaled Error output operates the same as the Ramped Error, except the speed error is: (Scaled Reference minus feedback). (See CP-15 on Page C-3.)
Page 3-17
ZERO SPEED (J1 Pin 9)
The Zero Speed output may be controlled either by the Ramped Reference, or by both the Ramped Reference and the Feedback. For additional information, refer to CP-74 on Page C-13.
HIGH ALARM (J1 Pin 10)
The High Alarm output is used to indicate when the speed, as identified by the Feedback Input, exceeds a level that is specified by the operator. The High Alarm output is high (inactive) when the feedback is below this level. It is low (active) when the feedback is at or above this level. (See CP-13 on Page C-3.)
LOW ALARM (J1 Pin 11)
The Low Alarm output is used to indicate when the feedback is below a level that is specified by the operator. The Low Alarm output is high (inactive) when the feedback is above this level. It is low (active) when the feedback is at or below the specified level. (See CP-12 on Page C-3.)
RAMPED ERROR (ERROR ALARM 1) (J1 Pin 12) The Ramped Error output is used to indicate when the speed error (Ramped Reference minus feedback) is at or outside a band specified by the operator. This output is high
(inactive) when the error is within the specified band. It is low (active) when the error is at or exceeds the specified band. (See CP-14 on Page C-3.)
SCALED ERROR (ERROR ALARM 2) (J1 Pin 13)
The Scaled Error output operates the same as the Ramped Error, except the speed error is: (Scaled Reference minus feedback). (See CP-15 on Page C-3.)
Page 3-17
Page 44
ANALOG OUTPUT (Requires Optional Analog I/O Board)
The Analog Output can be patched to any of the monitor variables or control parameters of the M-Drive. (For a detailed discussion concerning analog output uses, refer to Chapter 8 - Advanced Programming.) Figure 3-24 below illustrates the wiring for the analog output.
Note: The Analog Output can be configured for either a + 10 VDC or 4 to 20 mA level. Refer to Chapter 2 - Configuration, for the analog output configuration procedure.
| 7 SHIELD Ji 17 COMMON t 18 SIGNAL OUTPUT nd J4
Figure 3-24: Analog Output
Page 3-18
ANALOG OUTPUT (Requires Optional Analog I/O Board)
The Analog Output can be patched to any of the monitor variables or control parameters of the M-Drive. (For a detailed discussion concerning analog output uses, refer to Chapter 8 - Advanced Programming.) Figure 3-24 below illustrates the wiring for the analog output.
Note: The Analog Output can be configured for either a + 10 VDC or 4 to 20 mA level. Refer to Chapter 2 - Configuration, for the analog output configuration procedure.
| 7 SHIELD Ji 17 COMMON t 18 SIGNAL OUTPUT nd J4
Figure 3-24: Analog Output
Page 3-18
Page 45
5) SERIAL COMMUNICATIONS
The Serial Communications interface on the M-Drive complies with EIA Standard RS-422 -A for balanced line transmissions. This interface is provided to permit remote computer variable programming, status or performance monitoring, and remote control. A detailed discussion of the Serial Communications capability is provided in Chapter 7 of this manual.
Figures 3-25 and 3-26 illustrate a multidrop installation of the Serial Communications link., Contrex Micro-Module 100
RS232 to RS422 Converter 3200-1800 or equivalent
RXD TxD B +e +- COM
J1 M-Drive #1 Th r - Leh
¢ Ts | -RXD r Ta | +RXD
3] - TxD
@ re | +TXD A J1 M-Drive #2
7 6 | 5 | ra 3 | 2 |
Figure 3-25: Seria! Communications Connections
Page 3-19
5) SERIAL COMMUNICATIONS
The Serial Communications interface on the M-Drive complies with EIA Standard
RS-422 -A for balanced line transmissions. This interface is provided to permit remote computer variable programming, status or performance monitoring, and remote control. A detailed discussion of the Serial Communications capability is provided in Chapter 7 of this manual.
Figures 3-25 and 3-26 illustrate a multidrop installation of the Serial Communications link.
Contrex Micro-Module 100
RS232 to RS422 Converter 3200-1800 or equivalent
RXD TXD B +- +- COM hh
J1
La
- RXD + RXD - TXD + TXD
M-Drive #1
7 6 | ls | Pa 3 | 2 |
M-Drive #2
Figure 3-25: Serial Communications Connections
Page 3-19
Page 46
tt may be necessary to terminate the communication line at the furthest receiving ends only. A 100 ohm, 1/2 Watt resistor is usually adequate for this purpose. For more information, refer to EIA Standard RS-422-A.
Shield at one end of cable only.
| M-Drive | | M-Drive | | M-Drive | RS232 TO HOST RS422 | CONVERTER | u-Drive | | M-Drive | | M-Drive | Figure 3-27: Correct M-Drive Multidrop Installation | M-Drive | | M-Drive | Me ve HOST CONVERTER 4 ><
| M-Drive | | M-Drive | | w-Drive |
Figure 3-28 Incorrect Installation
Page 3-20 tt may be necessary to terminate the communication line at the furthest receiving ends only. A 100 ohm, 1/2 Watt resistor is usually adequate for this purpose. For more information, refer to EIA Standard RS-422-A.
Shield at one end of cable only.
| M-Drive | | M-Drive | | M-Drive | RS232 TO HOST RS422 | CONVERTER | u-Drive | | M-Drive | | M-Drive | Figure 3-27: Correct M-Drive Multidrop Installation | M-Drive | | M-Drive | M- ve HOST CONVERTER 4 >< | M-Drive | | M-Drive | | woDrive | Figure 3-28 Incorrect Installation Page 3-20
Page 47
CALIBRATION 4
INTRODUCTION
This chapter contains the information required to calibrate the current limit and analog input/output of the M-Drive. Prior to using these procedures, the M-Drive must be properly configured and installed in accordance with Chapters 2 and 3 of this Manual.
CURRENT LIMIT
The current limit level on the M-Drive is adjustable from approximately 4 to 15 amps. To limit the load current to the desired limit, follow the procedure below:
1. Place a DC plus AC RMS ammeter in series (or clamp on) with one of the motor armature lines (A1 or A2).
2. Turn the current fimit potentiometer at the rear of the M-Drive fully clockwise. This potentiometer is located below the J1 connector.
3. With the M-Drive in the RUN state, gradually increase the load until the AC ammeter reaches the desired limit level.
4. Turn the current limit potentiometer counterclockwise until the M-Drive begins to current limit. This is exhibited by the following conditions: a) A slight reduction in motor RPM 6) The front panel "Limit Alarm" LED illuminates c) CP-52 indicates a value of 7.
5. Increase the motor load gradually. The load current should not increase and the motor RPMs should decrease.
The rate at which the M-Drive reduces motor RPMs in response to added load in current limit is adjustable. This value is defaulted at the factory and should not require field adjustment. However, if a different value is desired, adjust CP-60 until the desired response is achieved.
Note: The current limit is not operable when the M-Drive is in Direct Scaling Mode
(CP-61 = 0). For additional information concerning Direct Scaling Mode, refer to Chapter 8 (Advanced Programming).
Page 4-1
CALIBRATION 4
INTRODUCTION
This chapter contains the information required to calibrate the current limit and analog input/output of the M-Drive. Prior to using these procedures, the M-Drive must be properly configured and installed in accordance with Chapters 2 and 3 of this Manual.
CURRENT LIMIT
The current limit level on the M-Drive is adjustable from approximately 4 to 15 amps. To limit the load current to the desired limit, follow the procedure below:
1. Place a DC plus AC RMS ammeter in series (or clamp on) with one of the motor armature lines (A1 or A2).
2. Turn the current limit potentiometer at the rear of the M-Drive fully clockwise. This potentiometer is located below the J1 connector.
3. | With the M-Drive in the RUN state, gradually increase the load until the AC ammeter reaches the desired limit level.
4. Turn the current limit potentiometer counterclockwise until the M-Drive begins to current limit. This is exhibited by the following conditions: a) A slight reduction in motor RPM b) The front panel "Limit Alarm" LED illuminates C) CP-52 indicates a value of 7.
5. Increase the motor load gradually. The load current should not increase and the motor RPMs should decrease.
The rate at which the M-Drive reduces motor RPMs in response to added load in current limit is adjustable. This value is defaulted at the factory and should not require field adjustment. However, if a different value is desired, adjust CP-60 until the desired response is achieved.
Note: The current limit is not operable when the M-Drive is in Direct Scaling Mode
(CP-61 = 0). For additional information concerning Direct Scaling Mode, refer to Chapter 8 (Advanced Programming).
Page 4-1
Page 48
ANALOG INPUT (Requires Optional Analog 1/O Board)
The analog input is factory calibrated for zero and span levels at 0-10 VDC. If it is necessary to field calibrate the analog input, follow these procedures: Zero Adjust
1. Enter CP-85 by pressing: Code Select, 8, 5, and "Enter"
2. Place either zero volts (short) or 4 mA on the analog input depending on the analog input configuration (determined during Chapter 2 procedures).
3. Press the "." (decimal point) key. The display should now read between 0 and 20. This step zero adjusts the analog input. Span Adjust 1. Enter CP-86 by pressing: Code Select, 8, 6, and “Enter’.
2. Place either +10 VDC or 20 mA on the analog input depending on the analog input configuration (determined during Chapter 2 procedures).
3. Press the "." (decimal point) key. The display should now display a value from 3600 to 4000 for a 10 VDC input. This step span adjusts the analog input.
For a comprehensive discussion of the functional use of the analog input for replacing frequency inputs and setpoints, refer to Chapter 8, Advanced Programming.
Page 4-2
ANALOG INPUT (Requires Optional Analog 1/O Board)
The analog input is factory calibrated for zero and span levels at 0-10 VDC. If it is necessary to field calibrate the analog input, follow these procedures: Zero Adjust
1. Enter CP-85 by pressing: Code Select, 8, 5, and "Enter"
2. Place either zero volts (short) or 4 mA on the analog input depending on the analog input configuration (determined during Chapter 2 procedures).
3. Press the "." (decimal point) key. The display should now read between 0 and 20. This step zero adjusts the analog input. Span Adjust 1. Enter CP-86 by pressing: Code Select, 8, 6, and “Enter’.
2. Place either +10 VDC or 20 mA on the analog input depending on the analog input configuration (determined during Chapter 2 procedures).
3. Press the "." (decimal point) key. The display should now display a value from 3600 to 4000 for a 10 VDC input. This step span adjusts the analog input.
For a comprehensive discussion of the functional use of the analog input for replacing frequency inputs and setpoints, refer to Chapter 8, Advanced Programming.
Page 4-2
Page 49
ANALOG OUTPUT (Requires Optional Analog I/O Board)
Zero Adjust
The Analog Output is factory calibrated for zero and span levels at + 10 VDC. ff it is necessary to field calibrate the analog output, follow these procedures:
1. Place a DC voltmeter or ammeter on J4 pins 17 and 18. (Use a DC voltmeter if the analog output is configured for + 10 VDC, or use an ammeter if the analog output is configured for 4 to 20 mA.)
2. Enter CP-82 by pressing: Code Select, 8, 2, and “Enter". 3. Enter new values for CP-82 until the output on the meter reads zero or 4 mA. (See NOTE below.) Enter values from 0 to 2048 (a value of 1024 is nominal).
Larger values will increase the analog output level. The analog output is now zero adjusted.
Note: Two methods are available for entering new values into the M-Drive: 1) Press the digit keys until the new number is displayed, then press “Enter. 2) Press the scroll keys until the new number is displayed.
Span Adjust 1. Enter CP-83 by pressing: Code Select, 8, 3, and Enter. 2., Enter new values for CP-83 until the meter reads 10 volts or 20 mA. Enter values from 2048 to 4096. Larger values will increase the analog output level. The analog output is now span adjusted.
A comprehensive discussion of the functional use of the analog output is available in Chapter 8, Advanced Programming.
Page 43
ANALOG OUTPUT (Requires Optional Analog I/O Board)
Zero Adjust
The Analog Output is factory calibrated for zero and span levels at + 10 VDC. ff itis necessary to field calibrate the analog output, follow these procedures:
1. Place a DC voltmeter or ammeter on J4 pins 17 and 18. (Use a DC voltmeter if the analog output is configured for + 10 VDC, or use an ammeter if the analog output is configured for 4 to 20 mA.)
2. Enter CP-82 by pressing: Code Select, 8, 2, and “Enter". 3. Enter new values for CP-82 until the output on the meter reads zero or 4 mA. (See NOTE below.) Enter values from 0 to 2048 (a value of 1024 is nominal).
Larger values will increase the analog output level. The analog output is now zero adjusted.
Note: Two methods are available for entering new values into the M-Drive: 1) Press the digit keys until the new number is displayed, then press “Enter”. 2) Press the scroll keys until the new number is displayed.
Span Adjust 1. Enter CP-83 by pressing: Code Select, 8, 3, and Enter. 2. Enter new values for CP-83 until the meter reads 10 volts or 20 mA. Enter values from 2048 to 4096. Larger values will increase the analog output level. The analog output is now span adjusted.
A comprehensive discussion of the functional use of the analog output is available in Chapter 8, Advanced Programming.
Page 4-3
Page 50
NOTES NOTES
Page 4-4 Page 4-4