Page 31
M-DRIVE WIRING DRAWING M-DRIVE WIRING DRAWING
Figure 3-3 below illustrates the control installation wiring for the M-Drive. It is divided into Figure 3-3 below illustrates the control installation wiring for the M-Drive. It is divided into Required Inputs and Outputs, Elective Inputs and Outputs and Serial Communications. Required Inputs and Outputs, Elective Inputs and Outputs and Serial Communications. a : 2 M-Drive Motor 3 M-Drive Motor a oe Fl+ as) L1 s Fit Field 2 Ll, - - L5 T Field é Neutral L2 ~_ - __1 $6] 32 g2 (> 1_F2 =n © ° Neutral L2, _ - - - __ 6] 32 J2 2 LE2=__| Chassis Gnd, rs \ 7 | r3| 22 Armature 3 Chassis Gnd + i 3 a2 | Armature 3 - 4 Pe on ra ; g +12V (58 mA Max) a 3 3 +12V (58 mA_Max) aN 2 33 Drive Output 3 i = ive ut pu ze Feedback q ty Drive Output 8 3 = Feedback q ru g 4 & co), 3 R-Stop rato ° R-Stop rete i a A == n 3 RON Leo 3 Po STOP ite iG Y F-STOP uo op riz Z eee = ce wee eee el -- ene eee eel lL ~--+--+----4-- - eee eee ee eee og Ext. Ref. EHR 3 # Ext. Ref EA 2 5 ¥ req. np. Breas Tap: = z 3 ®-¢ Zero Speed . £ _ ° = ayy 9 @-¢ Zero Speed . 3 ® ow Alarm | Offset Freq. 8 rt @-4 Dev Alarm 1 § offset Freq. HA 8 12 & Dev Alarm 1 2 Input up rr3 4 @ - Dev Alarm 2 3 iP 9 i3 Dev Alarm 2 ¥ 1g sat - 9 1g sae - 8, - - a Spare No a a Spare > a (7) Closed/ $ 5 a Closed/ g 5 n Open Loop 6 » Open Loop 6 ay} 2 a vai? (Common) Analog 2., 54 Li fcenmon) Analog 5 mesa a J4 18 (Signal) output & Reypaa wr T v4 18 (Signal) Output o hovpout + 5 (Optional) g Lockout ¢ 5 (optional) | > Primary/, - 31V 2 2 Primary/ L - 310 Q 3 Sec Mode 6 a 2 3 Sec Mode ° el ele a om QQ 3 4 4129 8 cq Ramp, 7 Tt +12V 5 A Disable 2 ry 3 aD + TXD 1 Disable t 8 Z Da + TxD 2 Primary 2° 3 $ > Ae § Primary 2 _ 5 3 -_ ae 5 SetPt Sel 1° Jl v7) + RXD 5 SetPt Sel 1 JL 4 + ~BXD. 2 Secondary 3 a 3 _ - =e 8 Secondary 3 qn 5 - 5S SetPt Sel 40 ~ i 6 Com (opr) = SetPt Sel 40 * 2 $ Com (OPT) =, 3 $ TI 7 ci Local/ } T2 z Local/ i2 Local/ ry Computer o ae & Computer > & Rmt Scroll ee i374 Rat Scroll ee 8 UP, 14 + Rmt Scroll oe en nt Scroll oe fis] DN ae Analog (signal) Te Analog (gmat), f 16 Input (common) 17 | Input (common )} 17 h (Optional) = (Optional) Figure 3-3: M-Drive General Wiring Drawing Figure 3-3: M-Drive General Wiring Drawing
Page 3-5 Page 3-5
Page 32
M-DRIVE CONNECTOR LOCATIONS M-DRIVE CONNECTOR LOCATIONS
Figure 3-4 below illustrates the location and numbering of the wiring connectors as viewed Figure 3-4 below illustrates the location and numbering of the wiring connectors as viewed from the rear of the M-Drive. from the rear of the M-Drive.
1 1 1 1
2 2 2 2
3 3 3 3
4 4 4 4
5 5 5 5
6 6 6 6
7 7 7 7
8 J3 8 8 J3 8
9 9 9 9
10 10 10 10
11 11 11 11
12 12 12 12
13 13 13 13
14 14 14 14
15 15 15 15
16 16 16 16 g1 g1
1 1
2 2
3 3
4 4
5 5
6 6
1 7 1 7
2 8 2 8
3 J4 9 3 J4 9
4 10 4 10
5 11 5 11
6 12 6 12
7 13 7 13
14 14
J2 15 J2 15
16 16
17 17
18 18
Figure 3-4: Wiring Connector Locations Figure 3-4: Wiring Connector Locations
Page 3-6 Page 3-6
Page 33
1) REQUIRED INPUTS
INPUT POWER
The M-Drive operates on either 115 VAC or 230 VAC. The lowest 3 pin connections on J2 are allocated for the power connection.
Ll 5 NEUTRAL OR L2 6 CHASSIS GND 7
J2
Figure 3-5: Input Power
FEEDBACK INPUT Feedback Input is a pulse train input used by the M-Drive to ascertain motor speed. The specific Feedback Input connections to the M-Drive are identical whether the sensor is a Magnetic Pickup, Encoder, Hall Effect Quad Sensor or Proximity Sensor. The Feedback input connections are illustrated below:
+12V *(OPT) _ I
SIGNAL . 5
COMMON $
SHIELD 7 fy 33
Figure 3-6: Feedback Input Connections
* Amplified or 3-wire sensors will contain their own source supply voltage or use the M-Drive + 12VDC if their current draw does not exceed 50 milliamps total.
Page 3-7
1) REQUIRED INPUTS
INPUT POWER
The M-Drive operates on either 115 VAC or 230 VAC. The lowest 3 pin connections on J2 are allocated for the power connection.
Ll 5 NEUTRAL OR L2 6 CHASSIS GND 7
J2
Figure 3-5: Input Power
FEEDBACK INPUT Feedback Input is a pulse train input used by the M-Drive to ascertain motor speed. The specific Feedback Input connections to the M-Drive are identical whether the sensor is a Magnetic Pickup, Encoder, Hall Effect Quad Sensor or Proximity Sensor. The Feedback input connections are illustrated below:
+12V *(OPT) _ I
SIGNAL . 5
COMMON é
SHIELD 7 fy 33
Figure 3-6: Feedback Input Connections
* Amplified or 3-wire sensors will contain their own source supply voltage or use the M-Drive + 12VDC if their current draw does not exceed 50 milliamps total.
Page 3-7
Page 34
RUN
RUN is a momentary input which when closed allows the M-Drive to run normally. As a momentary input, the RUN state is internally latched and need not be maintained by the operator device.
12
J3
Figure 3-7: Run Input
R-STOP R-STOP is a momentary input which when opened commands the M-Drive to ramp to zero speed at the specified deceleration rate. As a momentary input, the R-STOP state is internally latched and need not be maintained by the operator device.
R-STOP
|, LL
12
J3
Figure 3-8: R-Stop Input
Page 3-8
RUN
RUN is a momentary input which when closed allows the M-Drive to run normally. As a momentary input, the RUN state is internally latched and need not be maintained by the operator device.
12
J3
Figure 3-7: Run Input
R-STOP R-STOP is a momentary input which when opened commands the M-Drive to ramp to zero speed at the specified deceleration rate. As a momentary input, the R-STOP state is internally latched and need not be maintained by the operator device.
R-STOP
|, LL
12
J3
Figure 3-8: R-Stop Input
Page 3-8
Page 35
F-STOP
F-STOP is a momentary input which when opened commands the M-Drive to come to zero speed immediately, ignoring the specified deceleration rate. As a momentary input, the F-STOP state is internally latched and need not be maintained by the operator device.
F-STOP
14 roy fe 15
5
33 Figure 3-9: F-Stop Input
Note: Both the R-STOP and F-STOP inputs must be closed prior to entering the RUN state. If only one of the Stop inputs is used, the other needs to be wire shorted for proper M-Drive operation.
2) REQUIRED OUTPUT: . MOTOR CONNECTIONS
Connect the armature leads to J2 pins 3 and 4. Reversal of the armature leads reverses the direction of motor rotation.
Connect the field leads to J2 pins 1 and 2. Permanent magnet (PM) motors do not require field connections. Figure 3-10 below illustrates the motor connections.
iit I |+ 2 {7 F2 Fl 2 F2 ( Fl OR 3 - 3 ~- - + | | A2 - + Al A2 Al 4 + | a + I 32 4-WIRE 32 3-WIRE
Figure 3-10: Motor Connections
Page 3-9
F-STOP
F-STOP is a momentary input which when opened commands the M-Drive to come to zero speed immediately, ignoring the specified deceleration rate. As a momentary input, the F-STOP state is internally latched and need not be maintained by the operator device.
F-STOP
14 . fos
15
33 Figure 3-9: F-Stop Input
5
Note: Both the R-STOP and F-STOP inputs must be closed prior to entering the RUN state. If only one of the Stop inputs is used, the other needs to be wire shorted for proper M-Drive operation.
2) REQUIRED OUTPUT:
. MOTOR CONNECTIONS
Connect the armature leads to J2 pins 3 and 4. Reversal of the armature leads reverses the direction of motor rotation.
Connect the field leads to J2 pins 1 and 2. Permanent magnet (PM) motors do not require field connections. Figure 3-10 below illustrates the motor connections.
i oit I |+ 2 7 F2 TYYY) Fl 2 F2 ( Fl OR 3 - 3 ~- - + | A2, + Al A2 Al 4 + | a + 1
J2 4-WIRE J2 3-WIRE
Figure 3-10: Motor Connections
Page 3-9
Page 36
3) ELECTIVE INPUTS
EXTERNAL REFERENCE FREQUENCY INPUT
The External Reference Frequency Input is a frequency input that acts as the lead signal when the M-Drive is in Follower Format. This signal is proportioned by the ratio setpoint to control the speed of the Follower M-Drive.
If this input is used, install per Figure 3-11.
+12V *(OPT) I
SIGNAL . 2
COMMON . 3
SHIELD a vy J3
Figure 3-11: External Reference Frequency Input
JOG
JOG is a maintained input which when closed drives the motor at the selected jog speed. As a maintained input, the jog state is only valid for the duration of the time the Operator device is held closed.
| io
J3
Figure 3-12: Jog Input
Page 3-10
3) ELECTIVE INPUTS
EXTERNAL REFERENCE FREQUENCY INPUT
The External Reference Frequency Input is a frequency input that acts as the lead signal when the M-Drive is in Follower Format. This signal is proportioned by the ratio setpoint to control the speed of the Follower M-Drive.
If this input is used, install per Figure 3-11.
+12V *(OPT) I
SIGNAL . 2
COMMON . 3
SHIELD a vy J3
Figure 3-11: External Reference Frequency Input
JOG
JOG is a maintained input which when closed drives the motor at the selected jog speed. As a maintained input, the jog state is only valid for the duration of the time the operator device is held closed.
| io
J3
Figure 3-12: Jog Input
Page 3-10
Page 37
CLOSED/OPEN LOOP
The Closed/Open loop input determines the basic manner in which the control algorithm operates. In the Closed Loop position, the control algorithm adjusts the Drive output to reduce the error (setpoint minus feedback) to zero. In the Open Loop position, the contro! algorithm adjusts the drive output in response to setpoint input only and ignores the feedback or error.
Normal operation of the M-Drive occurs in the Closed Loop position. The Open Loop position is used to calibrate the drive during the scaling operation or to monitor non-linearities in the system control loop.
CLOSED LOOP
5 ~ x4 OPEN LOOP J4
Figure 3-13: Closed/Open Loop Input
PRIMARY/SECONDARY MODE (MASTER/FOLLOWER)
The Primary/Secondary input selects the scaling format used by the control algorithm. The Primary and Secondary modes are user programmable (as described in Chapter 8), but are defaulted to Master and Follower, respectively, as shipped from the factory. A detailed discussion of the scaling modes can be found in the Programming chapters of this manual.
PRIMARY (MASTER)
Om 2
_ ak
SECONDARY (FOLLOWER ) a4
Figure 3-14: Primary/Secondary Input
Page 3-11
CLOSED/OPEN LOOP
The Closed/Open loop input determines the basic manner in which the control algorithm operates. In the Ciosed Loop position, the control algorithm adjusts the Drive output to reduce the error (setpoint minus feedback) to zero. In the Open Loop position, the contro! algorithm adjusts the drive output in response to setpoint input only and ignores the feedback or error.
Normal operation of the M-Drive occurs in the Closed Loop position. The Open Loop position is used to calibrate the drive during the scaling operation or to monitor non-linearities in the system control loop.
CLOSED LOOP
5 ~ 9 OPEN LOOP J4
Figure 3-13: Closed/Open Loop Input
PRIMARY/SECONDARY MODE (MASTER/FOLLOWER)
The Primary/Secondary input selects the scaling format used by the control algorithm. The Primary and Secondary modes are user programmable (as described in Chapter 8), but are defaulted to Master and Follower, respectively, as shipped from the factory. A detailed discussion of the scaling modes can be found in the Programming chapters of this manual.
PRIMARY (MASTER)
Om 2
_ ay
SECONDARY ( FOLLOWER ) a4
Figure 3-14: Primary/Secondary Input
Page 3-11
Page 38
SETPOINT SELECT PRIMARY SETPOINT SELECT (SETPOINT #1 OR SETPOINT #2)
The Primary Setpoint Select input selects the setpoint source when in the Primary scaling made. In the open position, the setpoint is selected from the Control Parameter 1 entered by the operator. In the closed position, the setpoint is selected from the Control Parameter 2 entered by the operator. A more detailed discussion of the selectable setpoint feature is available in the Advanced Programming chapter of this manual.
CONTROL PARAMETER 1 sy a4 o- CONTROL PARAMETER 2*
Figure 3-15: Primary Setpoint Select
SECONDARY SETPOINT SELECT (SETPOINT #3 OR SETPOINT #4)
The Secondary Setpoint Select input selects the setpoint source when in the secondary scaling mode. In the open position, the setpoint is selected from the Control Parameter 3 entered by the operator. In the closed position, the setpoint is selected from the Control Parameter 4 entered by the operator. A more detailed discussion of the selectable setpoint feature is available in the Advanced Programming chapter of this manual.
CONTROL PARAMETER 3, ~ 1¢
“al
°
CONTROL PARAMETER 4* ry J4
Figure 3-16: Secondary Setpoint Select
Page 3-12
SETPOINT SELECT PRIMARY SETPOINT SELECT (SETPOINT #1 OR SETPOINT #2)
The Primary Setpoint Select input selects the setpoint source when in the Primary scaling made. In the open position, the setpoint is selected from the Control Parameter 1 entered by the operator. In the closed position, the setpoint is selected from the Control Parameter 2 entered by the operator. A more detailed discussion of the selectable setpoint feature is available in the Advanced Programming chapter of this manual.
CONTROL PARAMETER 1 sy a4 o- CONTROL PARAMETER 2*
Figure 3-15: Primary Setpoint Select
SECONDARY SETPOINT SELECT (SETPOINT #3 OR SETPOINT #4)
The Secondary Setpoint Select input selects the setpoint source when in the secondary scaling mode. In the open position, the setpoint is selected from the Control Parameter 3 entered by the operator. In the closed position, the setpoint is selected from the Control Parameter 4 entered by the operator. A more detailed discussion of the selectable setpoint feature is available in the Advanced Programming chapter of this manual.
CONTROL PARAMETER 3, ~ 1¢
“al
°
CONTROL PARAMETER 4* ry J4
Figure 3-16: Secondary Setpoint Select
Page 3-12
Page 39
RAMP DISABLE
The Ramp Disable input is used to inhibit acceleration or deceleration. Acceleration ramp and deceleration ramp are locked in place until the Ramp Disable input is released.
The only exception to the Ramp Disable function is the F-Stop state. If an F-Stop is called for, the speed drive output is immediately reduced to zero, ignoring the Ramp Disable input.
ACTIVE “NN 7 8 ©. HOLD Pe J4
Figure 3-17: Ramp Disable
KEYPAD LOCKOUT
The Keypad Lockout input is used to disable the front operator keypad from making setpoint and other parameter changes. The specific setpoints “locked out" during a Keypad Lockout condition are determined by the Setpoint Mask value (CP-79). See Page C-14 for information concerning Setpoint Mask.
All functions associated with monitoring or viewing of variables remain enabled during Keypad Lockout.
ENABLE ee o - 2 FL LOCKOUT J4
Figure 3-18: Keypad Lockout
Page 3-13
RAMP DISABLE
The Ramp Disabie input is used to inhibit acceleration or deceleration. Acceleration ramp and deceleration ramp are locked in place until the Ramp Disable input is released.
The only exception to the Ramp Disable function is the F-Stop state. If an F-Stop is called for, the speed drive output is immediately reduced to zero, ignoring the Ramp Disable input.
ACTIVE
NN
5 8 OE iy
J4
Figure 3-17: Ramp Disable
KEYPAD LOCKOUT
The Keypad Lockout input is used to disable the front operator keypad from making setpoint and other parameter changes. The specific setpoints “locked out" during a Keypad Lockout condition are determined by the Setpoint Mask value (CP-79). See Page C-14 for information concerning Setpoint Mask.
All functions associated with monitoring or viewing of variables remain enabled during Keypad Lockout.
ENABLE “NN T o - 2 ry LOCKOUT J4
Figure 3-18: Keypad Lockout
Page 3-13
Page 40
LOCAL/COMPUTER
The Local/Computer input is used to enable the serial communi- cations interface to change control variables or selected control commands. in either position, the serial communications is active to monitor variables, but only in the closed position can the serial communications change the control and command variables. More detail on the communications interface is available in Chapter 8 of this manual.
SN 7 mY
LOCAL oO COMPUTER
J4
Figure 3-19: Local/Computer Input
REMOTE SCROLL UP
The Remote Scroll Up input increments the active setpoint (see Setpoint Select on Page 3-12 for setpoint selection information). This input increments the active setpoint whether or not the setpoint is displayed.
There are two methods to increment the active setpoint using Remote Scroll Up. Each closure of this input increments the active setpoint 1 Engineering Unit. in addition, the active setpoint increments 1 Engineering Unit every half second while this input is held closed.
NO EFFECT
™~ 13 ° 14 =
REMOTE SCROLL UP J4
Figure 3-20: Remote Scroll Up
Page 3-14
LOCAL/COMPUTER
The Local/Computer input is used to enable the serial communi- cations interface to change control variables or selected control commands. in either position, the serial communications is active to monitor variables, but only in the closed position can the serial communications change the control and command variables. More detail on the communications interface is available in Chapter 8 of this manual.
SN 7 mY
LOCAL oO COMPUTER
J4
Figure 3-19: Local/Computer Input
REMOTE SCROLL UP
The Remote Scroll Up input increments the active setpoint (see Setpoint Select on Page 3-12 for setpoint selection information). This input increments the active setpoint whether or not the setpoint is displayed.
There are two methods to increment the active setpoint using Remote Scroll Up. Each closure of this input increments the active setpoint 1 Engineering Unit. in addition, the active setpoint increments 1 Engineering Unit every half second while this input is held closed.
NO EFFECT
™~ 13 ° 14 =
REMOTE SCROLL UP J4
Figure 3-20: Remote Scroll Up
Page 3-14