Page 121
The suggested actions which follow will take you through a “tour” of multiple page types. The first segment of the tour explores the object types available on Data Pages (probably the most commonly used page type). From page 100, press the first soft function key to link to Data Page 3. Press the blue Next key repeatedly, to examine Data Pages 4 through 8. Several of these pages contain active soft function keys or other choices which can be used to simulate how an object works. Press the blue Previous key to retreat back to page 100 when you are done. From page 100, press the second soft function key to enter Menu Page 10. Press the blue Next key to advance to page 11, then use the blue > and < keys, followed by the carriage return ↵ key to select any page listed in the menu. If at any time you wish to start completely over, press the blue Home u key to return to the page assigned to be the Home page. Now that you have done some exploration, use the blue Home key or other pathway to return to page 100. From page 100, use the soft function keys, Previous and Next keys, plus > or < keys as called for to explore the 3 remaining page types: Change Password, Setup and Alarms. In the alarms page section, you can generate and clear alarms by following the text on the screen. To turn off the alarm tone, press the Alarm control button, followed by the Horn soft function key. Remember that you can always press the blue Home u key to return to the Home page.
A-26
Appendix
Page 122
Exploring the ASAMPLE1 Configuration If you have run the ASAMPLE1 simulation, you now may wish to look more closely at the configuration. Begin by opening the ASAMPLE1 configuration with your PanelMate 500 configuration software, as was described earlier in this Appendix. By clicking on File, then selecting Print Report, you can print your choice of Configuration Properties or individual Pages for the ASAMPLE1 simulation. If you print everything available, you will generate nearly 50 pages of information. Instead, we recommend you select and print only a limited selection of pages. In order to make these selections, your print selection screen should look like this (note that “Alarm”, “Page Link Summary” and pages 1, 4, 8, and 26 are selected):
Appendix
A-27
Page 123
Note that the ASAMPLE1 application was constructed WITHOUT using the Virtual Mentor Response Template feature. The following are details in the printouts that you should look for: Selection
Illustrates
Page Linkage
* Shows appearance of all onscreen pages in the Summary application.
(prints 5 sheets)
* Shows how every page is linked to any other pages via: - previous or next keys - any of the 4 soft function keys below the screen - any numbered selections on Menu pages
Page #1
* Shows a Data Page appearance.
(prints 1 sheet)
* Shows static text content and position on display. * Shows definition of soft function key #4, which is used to reset a series of internal scratchpad variables. * Shows position and content of two conditional indicators, including a long text string which “wraps around” on the display. * Shows that the Previous key has no page assignment and the Next key advances the screen to page 2.
Page #4
* Shows a Data Page appearance.
(prints 1 sheet)
* Shows static text content and position on display. * Shows definition of soft function keys 2 and 4, which are used to increment and decrement an internal scratchpad variable. * Shows position and content of a conditional indicator. * Shows location and setup of numeric data object.
A-28
Appendix
Page 124
Page #8
* Shows a Data Page appearance.
(prints 2 sheets)
* Shows static text content and position on display. * Shows definition of soft function keys 2, and 4, which are used to increment and decrement an internal scratchpad variable. * Shows position of Numeric Data Object, plus all of its parameters and references. * Shows Bar Graph Object, plus all of its parameters and references.
Page #26
* Shows a Menu Page appearance.
(prints 1 sheet)
* Shows that the 15 selections available to operators set or clear scratchpad variables as part of the alarm simulation.
Alarm Page
* Shows chart of Discrete alarm assignments, including references to the same scratchpad variables referenced on page #26.
(prints 1 sheet)
* Shows chart of Value alarm assignments, including references to the same scratchpad variables referenced on page #26.
By examining these printouts while using the configuration software to explore pages in the configuration, you can see how pages are constructed and linked together. Remember that because this is a simulation, there are no references on any pages to actual PLC addresses. An actual application would access PLC addresses and make use of PanelMate 500’s data objects and mathematical tools to update operators while permitting numeric entry and control operations.
Appendix
A-29
Page 125
Twelve Helpful Reminders 1. The PanelMate 500 Operator Station design is based on the concept of linking pages to each other. Page changes are possible with screen defined soft function keys, menu selection, logic selection, PLC page change selection, or the use of the navigation keys. 2. The navigation keys link pages using the PREVious and NEXT keys. If you get lost you can always go HOME. To move within a page tab left and right. The tab keys are used in a MENU page to scroll up and down. In a DATA page, they are used to select between multiple numeric entry fields. 3. Only one key on the PanelMate 500 unit may be pressed at a time. 4. The LED and Function Keys act globally -- they are independent of the active page. LEDs are set based on value change. LEDs must be “forced” OFF; put a condition of 1 with a response of black as the last condition. 5. When you create an indicator object with text longer than the assigned display width, the text will automatically scroll. You may wish to buffer the end of the string with blank spaces so that the end of the message does not interfere with the start of the message when it wraps around. 6. The Configuration Software saves files with DOS filename extension .Cxy where C means Configuration and the x indicate LCD or VFD and the y indicates two or four line. A Configuration File must be compiled to the online format .Oxy filename before it is transferred to the online unit. 7. Text prompts are entered in individual objects and stored in the message library. If the same word is used multiple times (such as Stop) the message library will only store one copy. Spelling must be identical (Stop and STOP are different). You cannot add new messages directly into the message library. If you need to make a change on a single page then make the change on the page. If you wish to make a global change, (change StOP to Stop) then make the change in the message library.
A-30
Appendix
Page 126
8. There are internal registers known as ScratchPads that have the syntax [SP,xxx] where xxx is any printable ASCII character (letter or number). You cannot use a space character. Keep names short as they consume memory! ScratchPads are stored internally as signed 32 bit values. (They are integers and therefore cannot contain implicit decimal points.) 9. Many editing windows operate with a grid for information entry. They operate like a spreadsheet -- the right mouse button is used to cut/copy/paste/insert/add/delete rows. To perform an operation on an entire row select it by highlighting the row number at the left side of the grid. 10. When a list of Responses is executed, the first GOTO immediately jumps to the next page and halts execution of the rest of the Response list. (Also, You cannot embed variables inside a GOTO to provide indirection.) 11. When a page is called the following events occur: Entry Response Template is executed (if a GOTO is true the page in not drawn.) Page Objects are drawn Scan Response Template is executed as new values are received, then conditions are evaluated only when a value changes in a reference (either PLC or internal ScratchPad). 12. The Virtual Mentor option permits creation of a System Page which runs in the background. The page can have Entry and Scan tables. (Entry tables can be used to initialize ScratchPad variables). Note that your application should initialize data in either the System Page Entry table or the Startup Page Entry table, since they run as separate processes that are not synchronized. Use one table or the other - not both!
Appendix
A-31
Page 127
A-32
Appendix