For the Cutler-Hammer D26MB and Eaton D26MB

Page 91

Control Relays & Timers Machine Tool Relays

49-91

July 2008

D26 Series, Type M, DC Multipole with Convertible Contacts

Complete DC Relays When Ordering Specify ■ Catalog Number and Magnet Coil Suffix letter. ■ Example: For a 4-pole relay having 4NO contacts, order Catalog Number

D26MRD40, with a 120V DC coil, order D26MRD40A1. Table 49-147. Complete DC Relays Number of Contacts

Type of Contacts Open Type NO

NC

Catalog Number

2

2 1 0

0 1 2

D26MRD20 D26MRD11 D26MRD02

D26MRD202 D26MRD112 D26MRD022

3

3 2 1 0

0 1 2 3

D26MRD30 D26MRD21 D26MRD12 D26MRD03

D26MRD302 D26MRD212 D26MRD122 D26MRD032

4

4 3 2 1 0

0 1 2 3 4

D26MRD40 D26MRD31 D26MRD22 D26MRD13 D26MRD04

D26MRD402 D26MRD312 D26MRD222 D26MRD132 D26MRD042

6

6 5 4 3 2 1 0

0 1 2 3 4 5 6

D26MRD60 D26MRD51 D26MRD42 D26MRD33 D26MRD24 D26MRD15 D26MRD06

D26MRD602 D26MRD512 D26MRD422 D26MRD332 D26MRD242 D26MRD152 D26MRD062

7

7 6 5 4 3 2 1 0

0 1 2 3 4 5 6 7

D26MRD70 D26MRD61 D26MRD52 D26MRD43 D26MRD34 D26MRD25 D26MRD16 D26MRD07, - - - - - - - 10 – 11

The 6 and 7 contact relays (without Mechanical Latch only) listed above can be provided with four additional NO non-convertible contacts. Add Suffix Number 4 to above listed Catalog Number plus Magnet Coil Suffix. Example: For an 11 contact relay, order D26MRD704A1.

Relay Only

Relay with Mechanical Latch Price U.S. $

Catalog Number

Price U.S. $

Relay has additional factory wired normally closed coil clearing contact (see diagram).

49

Table 49-148. Magnet Coil Selection Volts DC

Suffix Number

Volts DC

Suffix Number

12 24 48

R1 T1 W1

120 240

A1 B1

Components . . . . . . . . . . . . . . Pages 49-88, 49-89 Discount Symbol . . . . . . . . . . . 1CD1 CA08102001E

For more information visit: www.eaton.com

Page 92

49-92

Control Relays & Timers Machine Tool Relays July 2008

D26 Series, Type M, DC Multipole with Convertible Contacts

AC and DC Dimensions Table 49-149. AC and DC D26 Relays, Approximate Dimensions in Inches (mm) and Shipping Wts. AC Relay D26

DC Relay D26

Dim. A

Ship. Wt. Lbs. (kg)

AC Relay D26

DC Relay D26

Dim. A

Ship. Wt. Lbs. (kg)

1 – 4 Poles

1 – 3 Poles

2.5 (1.1)

5 – 8 Poles

4 – 7 Poles

1 – 3 Poles with Timer D26 or D87 1 – 2 Poles with Latch 1 – 3 Poles with D26MF

3.3 (1.5)

6.13 (155.7) 5.81 (147.6)

3.5 (1.6)

5 – 8 Poles with Timer D87 5 – 8 Poles with Latch 9 – 12 Poles

4 – 7 Poles with Timer D87 3 – 6 Poles with Latch 8 – 11 Poles

5.25 (133.4) 7.25 (184.2)

2.8 (1.3)

1 – 4 Poles with Timer D26 or D87 1 – 4 Poles with Latch 1 – 4 Poles with D26MF

4.00 (101.6) 6.00 (152.4)

2.8 (1.3)

D26MAS1

A

3.5 (88.9)

7.31 (185.7) 7.00 (177.8)

3.5 (1.6)

3.8 (1.7) 3.0 (1.4)

0.44 (11.2)

1 Slot #10 Screw

3.13 (79.5)

2 Holes #10 Screw

0.75 (19.1) 2.38 (60.5) Max.

D26MAS2

0.44 (11.2)

Figure 49-126. Approximate Relay Dimensions in Inches (mm) Table 49-150. Approximate Mounting Channel Dimensions in Inches (mm)

49

Catalog Number

A Dim.

B Dim.

D26MC16 D26MC12 D26MC8 D26MC4

40 (1016) 30 (762) 20 (508) 10 (254)

37.5 (952.5) 27.5 (698.5) 17.5 (444.5) 7.5 (190.5)

Note: Channel mounts through keyholes with #10 screws (two each end and one every fourth relay). Relays mount with screws captive in channel. All screws must be tightened firmly.

A 0.69 (17.5)

B 2.5 (63.5)

2.38 (60.5)

1.06 (26.9)

0.38 (9.7)

Type M 3.63 (92.2)

Relay D26

1.25 (31.8)

2.5 (63.5)

1.38 (35.1)

Figure 49-127. Approximate Mounting Channel Dimensions in Inches (mm)

For more information visit: www.eaton.com

CA08102001E

Page 93

Control Relays & Timers Timing Relays

49-93

July 2008

TMR5 Series

TMR5 Series

Technical Data and Specifications Table 49-151. TMR5 Time Delay Relays, Technical Data

TMR5 Time Delay Relays

Description

Specifications

Voltage Tolerance: AC Operation DC Operation

+10/-15% of nominal at 50/60 Hz +10/-15% of nominal

Load Burden

2 VA

Setting Accuracy: Maximum Setting (Adjustable) Minimum Setting (Adjustable) Fixed Time Delay: < 2 Seconds 0.1 – 2 Seconds

+5%, -0% +0%, -50% +1% ±5%

Repeat Accuracy (constant voltage and temperature): > 2 Seconds Delay 0.1 – 2 Seconds Delay

±0.1% ±2%

The TMR5 Series Time Delay Relays are designed for a broad range of OEM applications. The TMR5 Series offers non-programmable plug-in style timers with a variety of functions available. Each unit offers a single function and single input voltage, and operates over a defined time delay range. Units with fixed time delays are also available. Eaton also offers customization capabilities for these timers, remote adjustments, special pin configurations, and more. Contact us to discuss your specific application and design of a custom timer.

Reset Time: On Delay/Interval/Repeat Cycle Off Delay/Single Shot/Watchdog

0.1 Seconds 0.04 Seconds

Start-Up Time (time from when power is applied until unit is timing): 120 and 240V Units 12, 24 and 48V Units

0.05 Seconds 0.08 Seconds

Features

Life: Mechanical Full Load

Product Description

■ Single timing range for each unit

Maintain Function Time (time unit contin- 0.01 Seconds ues to time after power is removed) Temperature: 12 – 120V Input Voltage 240V Input Voltage

-18° to 150°F (-28° to 65°C) -18° to 122°F (-28° to 50°C)

Insulation Voltage

2,000V

Output Contacts

DPDT 10A @ 240V AC / 30V DC, 1/2 hp @ 120/240V AC (NO contacts) 1/3 hp @ 120/240V AC (NC contacts) B300 and R300; AC-15 and DC-13 10,000,000 operations 100,000 operations

■ Ranges available from 0.02 sec to

24 hours ■ Wide variety of functions available ■ Plugs in to standard 8- or 11-Pin

49 socket ■ 10A DPDT output contacts ■ Can be easily customized to meet your needs

Standards and Certifications with Eaton socket

CA08102001E

For more information visit: www.eaton.com

Page 94

Control Relays & Timers Timing Relays

49-94

July 2008

TMR5 Series

Catalog Numbering System

Product Selection

Table 49-152. Catalog Numbering System, TMR5 Time Delay Relays

When Ordering Specify ■ Catalog Number of Timing Relay

TMR5 N 05 120 Family Type TMR5 Operational Mode

Input Voltage 120 = 120V AC/DC 12 = 12V AC/DC 24 = 24V AC/DC 240 = 240V AC/DC

8-Pin Octal Sockets N = ON Delay T = Interval ON L = Flasher R = Repeat Cycle (OFF Time First Followed by ON Time and Repeating) Y = Repeat Cycle (On Time First Followed by OFF Time and Repeating)

Timing Range 04 = 0.05 – 5 sec 05 = 0.1 – 10 sec 08 = 0.6 – 60 sec 12 = 3 – 300 sec 15 = 0.3 – 30 min 16 = 0.6 – 60 min 20 = 4.8 min – 8 hr 22 = 6 sec – 10 min 23 = 14.4 min – 24 hr

11-Pin Octal Sockets F C W

P G D

= OFF Delay, Control Switch Trigger = Single Shot, Control Switch Trigger = Watchdog, Control Switch Trigger (Retriggerable Single Shot) = OFF Delay, Power Trigger = Single Shot, Power Trigger = Watchdog, Power Trigger (Regriggerable Single Shot)

Input Voltage

Socket

Timing Range

Catalog Number

8-Pin

0.1 – 10 sec 0.6 – 60 sec 0.1 – 10 sec 0.6 – 60 sec

TMR5N05120 TMR5N08120 TMR5N0524 TMR5N0824

Price U.S. $

ON Delay 120V AC/DC 120V AC/DC 24V AC/DC 24V AC/DC

OFF Delay, Control Switch Trigger 120V AC/DC 120V AC/DC 24V AC/DC 24V AC/DC

11-Pin

0.1 – 10 sec 0.6 – 60 sec 0.1 – 10 sec 0.6 – 60 sec

TMR5F05120 TMR5F08120 TMR5F0524 TMR5F0824

8-Pin

0.1 – 10 sec 0.6 – 60 sec 0.1 – 10 sec 0.6 – 60 sec

TMR5T05120 TMR5T08120 TMR5T0524 TMR5T0824

Interval ON 120V AC/DC 120V AC/DC 24V AC/DC 24V AC/DC

Single Shot, Control Switch Trigger 120V AC/DC 120V AC/DC 24V AC/DC 24V AC/DC

11-Pin

0.1 – 10 sec 0.6 – 60 sec 0.1 – 10 sec 0.6 – 60 sec

TMR5C05120 TMR5C08120 TMR5C0524 TMR5C0824

Repeat Cycle (OFF Time First Followed by ON Time and Repeating) 120V AC/DC 120V AC/DC 24V AC/DC 24V AC/DC

8-Pin

0.1 – 10 sec 0.6 – 60 sec 0.1 – 10 sec 0.6 – 60 sec

TMR5R05120 TMR5R08120 TMR5R0524 TMR5R0824

Repeat Cycle (ON Time First Followed by OFF Time and Repeating)

For more information on each operational mode, see Pages 49-95 and

49-96. Indicates DUAL knob unit. All dual knob units can have independently

49

Table 49-153. Product Selection, TMR5 Time Delay Relays selectable and adjustable ON and OFF times. If different ON and OFF times are desired, add two codes for time ranges in the part number. The first code listed indicates the first timing range of the unit (OFF time for R, ON time for Y) and the second code indicates the second timing range (ON time for R, OFF Time for Y). Any time range can be created as a custom unit. Contact Eaton for details. Fixed Time Delay settings are available for orders of 50 pieces or more. Contact EatonCare for additional information at 877-ETN-CARE (386-2273).

120V AC/DC 120V AC/DC 24V AC/DC 24V AC/DC

8-Pin

0.1 – 10 sec 0.6 – 60 sec 0.1 – 10 sec 0.6 – 60 sec

TMR5Y05120 TMR5Y08120 TMR5Y0524 TMR5Y0824

All configurations from Catalog Numbering System are available.

Accessories Table 49-154. Accessories for Use with TMR5 Time Delay Relays Description

Standard Pack

Catalog Number

8-Pin Socket 11-Pin Socket Hold Down Spring

10 10 10

D3PA2 D3PA3-A2 D65CHDS

Price U.S. $

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.eaton.com

CA08102001E

Page 95

Control Relays & Timers Timing Relays

49-95

July 2008

TMR5 Series

Operation Function

Operation

Timing Chart

ON-Delay Delay on Operate Delay on Make

Upon application of input voltage, the preset time begins. At the end of the preset time, the relay is energized. Input voltage must be removed and reapplied to reset the time delay and de-energize the relay.

Reset Input Power (Voltage)

On Off On

Output (Load)

Delay Off Reset

Interval ON Interval

Upon application of input voltage, the relay is energized and the preset time begins. At the end of the preset time, the relay is de-energized. Input voltage must be removed and reapplied to reset the time delay.

On Input Power (Voltage) Off On Output (Load)

Delay Off

OFF-Delay Delay on Release Delay on De-energization Delay on Drop-Out

Upon application of input voltage, the time delay relay is ready to accept trigger signals. Upon application of the trigger signal, the relay is energized. Upon release of the trigger signal, the preset time begins. At the end of the preset time, the relay is de-energized. Any application of the trigger signal during the preset time will keep the relay energized and reset the time delay.

Input Power (Voltage)

On Off Closed

Trigger Signal

Output (Load)

Open On Delay

Delay

Delay

Off

Single Shot One Shot Momentary Interval

Upon application of input voltage, the time delay relay is ready to accept trigger signals. Upon application of the trigger signal, the relay is energized and the preset time begins. During the preset time, the trigger signal is ignored. The time delay relay is reset by applying the trigger signal when the relay is not energized.

Input Power (Voltage)

On

Closed Trigger Signal

Open On

Output (Load)

Delay Off

Figure 49-128. Operational Figures (1 of 2)

CA08102001E

49

Off

For more information visit: www.eaton.com

Delay

Page 96

49-96

Control Relays & Timers Timing Relays July 2008

TMR5 Series

Function

Operation

Timing Chart

Watchdog Retriggerable Single Shot

Upon application of input voltage, the time delay relay is ready to accept trigger signals. Upon application of the trigger signal, the relay is energized and the preset time begins. At the end of the preset time, the relay is de-energized unless the trigger signal is closed and opened prior to time out (before preset time elapses). Continuous cycling of the trigger signal at a rate faster than the preset time will cause the relay to remain energized.

Input Power (Voltage) Trigger Signal Relay Output (Load)

On Off Closed Open On Delay

Delay

Off Reset

Flasher

Upon application of input voltage, the preset time (T1) begins. At the end of the preset time, the relay is energized and remains in that condition for the preset time (T1). At the end of this time, the relay is de-energized and the sequence repeats until input voltage is removed.

On Input Power (Voltage) Off Output (Load)

On Off

T1 T1

T1 T1

Action Continues Until Power Is Removed Reset Repeat Cycle OFF/ON Delay

Upon application of input voltage, a preset delay begins (OFF). At the end of the preset delay, the relay is energized and remains in that condition for a second, independently adjustable preset time (ON). At the end of this time, the relay is de-energized and the sequence repeats until input voltage is removed.

On Input Power (Voltage) Off Output (Load)

On Off

Off On Off On Action Continues Until Power Is Removed Reset

Repeat Cycle ON/OFF Delay

Upon application of input voltage, the relay is energized and a preset delay begins (ON). At the end of the preset delay, the relay is de-energized and remains in that condition for a second, independently adjustable preset time (OFF). At the end of this time, the relay is energized and the sequence repeats until input voltage is removed.

On Input Power (Voltage) Off Output (Load)

On Off

On Off On Off Action Continues Until Power Is Removed

49 Figure 49-128. Operational Figures (2 of 2)

For more information visit: www.eaton.com

CA08102001E

Page 97

Control Relays & Timers Timing Relays

49-97

July 2008

TMR5 Series

Wiring Diagrams

+

Control Switch 4 5 3 2

6

4

7

3 2

1 8 (DC)+ L1

6 7

5

4

8 9 10

(DC)+ L1

Input Voltage

6 7

−

8 9 10

1 11 (DC)+ L1

(DC)− L2

(DC)− L2

Input Voltage * Should Be Same Voltage as Input Voltage

Input Voltage

Figure 49-129. Wiring for 8-Pin Units

5

3 2

1 11

−(DC) L2

Power Trigger *

Figure 49-130. Wiring for 11-Pin Control Switch Trigger Units

Figure 49-131. Wiring for 11-Pin Power Trigger Units

Dimensions Dual Knob Only

2.4 (60)

2.9 (74)

1.7 (43)

3.5 (89)

49

Figure 49-132. TMR5 Approximate Dimensions in Inches (mm) 6-32 x 0.312 Combination Head Screw and Pressure Clamping Plate (8 Places)

6-32 x 0.312 Combination Head Screw and Pressure Clamp (11 Places)

Two 0.165 (4.2) Dia. Slots

2.14 (54.3) 2.03 (51.4)

1.30 (32.9) 1.60 (40.5) Max.

Two 0.17 (4.3) Dia. Holes

2.05 (52.07) Max.

2.06 (52.3)

0.82 (20.8) 0.58 (14.7) 0.97 (24.6) Max. Tolerances: ± 0.010 ± (0.25) Unless Otherwise Shown

2.33 (59.1) 0.97 Max. (24.6) Tolerances: ± 0.010 ± (0.25) Unless Otherwise Shown

D3PA2

D3PA3

Figure 49-133. D3PA2 and D3PA3 Sockets, Approximate Dimensions in Inches (mm)

CA08102001E

0.125 – 0.156 (3.17 – 3.96))

For more information visit: www.eaton.com

0.15 (3.6) 0.58 (14.7) 0.77 (19.6)

Page 98

49-98

Control Relays & Timers Timing Relays July 2008

TR Series

TR Series

Technical Data and Specifications Table 49-155. Contact Ratings Item

Specification

Contact Configuration

2 Form C, DPDT (Delayed Output)

Allowable Voltage/Current

240V AC, 30V DC/10A

Max. Permissible Operating Frequency

1800 cycles per hour

Rated Load, Resistive Inductive Horsepower Rating

10A, 240V AC / 30V DC 7A, 240V AC / 30V DC 1/6 hp 120V AC, 1/3 hp 240V AC

Life, Electrical Mechanical

500,000 operations min. (resistive) 50,000,000 operations minimum

Table 49-156. General Specifications TR Timing Relays

Product Description The upgraded TR Series Timing Relays are designed to meet most timing requirements by offering more flexibility in range of input voltage, timing range and functionality. Use a rotary switch to choose from 20 selectable time ranges from 0.1 second to 600 hours. We offer both a power triggered and signal triggered model, each with expanded operation modes. There is a green LED to indicate when power is ON and an orange LED when output is ON.

Features ■ 20 time ranges and 10 timing

49 functions ■ Time delays from 0.1 sec to 600 hrs. ■ Space-saving, compact package ■ High repeat accuracy of ± 0.2% ■ LED indication ■ Standard 8- or 11-Pin and 11-blade termination ■ 2 Form C DPDT delayed output contacts ■ 10A Contact Rating

Standards and Certifications TUV

Item

Specification

Operation System Time Range Pollution Degree Overvoltage Category Rated Operational Voltage 240AC 24AC 12DC

Solid-State CMOS Circuit 0.1 sec to 600 hours 2 (IE60664-1) III (IE60664-1)

Voltage Tolerance 240AC 24AC 12DC Input OFF Voltage Ambient Operating Temperature Reset Time Repeat Error Voltage Error Temperature Error Setting Error Insulation Resistance Dielectric Strength Between power and output terminals Between contacts of different poles Between contacts of same pole Vibration Resistance Shock Resistance Operating extremes Damage limits, TRNP, TRFP TRNB, TRFB Power Consumption (Approx.) 240AC 120V AC / 60 Hz 240V AC / 60 Hz 24AC (AC/DC) 12DC Dimensions TRNP, TRFP TRNB, TRFB Weight

100 – 240V AC (50/60 Hz) 24V AC (50/60 Hz)/24V DC 12V DC 85 – 264V AC (50/60 Hz) 20.4 – 26.4V AC (50/60 Hz)/21.6 – 26.4V DC 10.8 – 13.2V DC Rated Voltage x 10% Minimum -4 – 149°F (-20 – 65°C) 100 mS maximum ± 0.2%, ± 20 mS ± 0.2%, ± 20 mS ± 0.5%, ± 20 mS ± 10% maximum 100M ohm minimum (500V DC) 2000V AC, 1 minute 2000V AC, 1 minute 1000V AC, 1 minute 10 – 55 Hz amplitude 0.5 mm; 2 hrs in each of 3 axes 10G 40G (3x in each of 3 axes) 10G (3x in each of 3 axes)

6.5 VA TRNP, TRNB/6.6 VA TRFP, TRFB 11.6 VA TRNP, TRNB/12.1 VA TRFP, TRFB 3.4 VA – 1.7W TRNP, TRNB/3.5 VA – 1.7W TRFP, TRFB 1.6W 1.58H x 1.42W x 3.07D in. (40H x 36W x 77.9D mm) 1.58H x 1.42W x 2.95D in. (40H x 36W x 74.9D mm) TRNP, 87g; TRFP, 89g; TRNB, TRFB, 85g

For the value of the error against a preset time, whichever value is larger should apply.

For more information visit: www.eaton.com

CA08102001E

Page 99

Control Relays & Timers Timing Relays

49-99

July 2008

TR Series

Catalog Numbering System

Product Selection

Table 49-157. Catalog Numbering System

When Ordering Specify ■ Catalog Number of Timing Relay

TR N P 240 AC Family Type TR Operational Mode N = Power Triggered A = ON Delay B = Interval C = Cycle (OFF first) D = Cycle (ON first) F = Signal Triggered A = ON Delay B = Cycle (OFF first) C = Cycle (ON first) D = Signal ON/OFF Delay E = OFF Delay F = One-Shot

Input Voltage 24AD = 24V AC (50/60 Hz)/24V DC 240AC = 100 – 240V AC (50/60 Hz) Model Type P = Pin/Octal B = Blade Style

Table 49-158. TR Plug-In Timing Relays Coil Voltage

Octal

Blade

Catalog Number

Price U.S. $

Catalog Number

Price U.S. $

Power Triggered 24V AC/DC

TRNP24AD

TRNB24AD

100 – 240V AC

TRNP240AC

TRNB240AC

24V AC/DC

TRFP24AD

TRFB24AD

100 – 240V AC

TRFP240AC

TRFB240AC

Signal Triggered

49

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 CA08102001E

For more information visit: www.eaton.com

Page 100

49-100

Control Relays & Timers Timing Relays July 2008

TR Series

Operation TRNP, TRNB A: ON-Delay 1 (Power Start) Set timer for desired delay, apply power to coil. Contacts transfer after preset time has elapsed, and remain in transferred position until timer is reset. Reset occurs with removal of power. Item Terminal No. Operation ( ) 2-7 Power (1 2) A-B (1) 1-4, 5-8 Delayed (2) 1-7, 3-9 (NC) Contact (1) 1-3, 6-8 ( ) (2) 4-7, 6-9 NO Indicator

PWR

B: Interval (Power Start) Set timer for desired delay, apply power to coil. Contacts transfer immediately, and return to original position after preset time has elapsed. Reset occurs with removal of power. Item Terminal No. Operation ( ) 2-7 Power (1 2) A-B (1) 1-4, 5-8 Delayed (2) 1-7, 3-9 (NC) Contact (1) 1-3, 6-8 ( ) (2) 4-7, 6-9 NO Indicator

OUT

OUT

Set Time

Set Time

T

C: Cycle 1 (Power Start, OFF First) Set timer for desired delay, apply power to coil. First transfer of contacts occurs after preset delay has elapsed, after the next elapse of preset delay contacts return to original position. The timer now cycles between on and off as long as power is applied (Duty Ratio 1:1). Operation Item Terminal No. ( ) 2-7 Power (1 2) A-B (1) 1-4, 5-8 Delayed (2) 1-7, 3-9 (NC) Contact (1) 1-3, 6-8 ( ) (2) 4-7, 6-9 NO Indicator

PWR

T

D: Cycle 3 (Power Start, ON First) Functions in same manner as Mode C, with the exception that first transfer of contacts occurs as soon as power is applied. The ratio is 1:1. Time On = Time Off. Item

Operation

Terminal No.

2-7 Power (1 2) A-B (1) 1-4, 5-8 Delayed (2) 1-7, 3-9 (NC) Contact (1) 1-3, 6-8 ( ) (2) 4-7, 6-9 NO ( )

Indicator

OUT Set Time

PWR

PWR OUT

T

Set Time

T

T

T

Note: T=Set Time, Ta=Shorter Than Set Time, (1):TRNP, (2): TRNB, (A): TRFP, (B): TRFB Internal Connections 4

5

3

6

2

7 1

49

(˜/-) TRNP

2

3

4

5

6

7

8

A

8

(˜/+)

1

9 B

(˜/+)

(˜/-) TRNB

Figure 49-134. Operational Figures (1 of 2)

For more information visit: www.eaton.com

CA08102001E