Page 101
Control Relays & Timers Timing Relays
49-101
July 2008
TR Series
TRFP, TRFB A: ON-Delay 2 (Signal Start) When a preset time has elapsed after the start input turned on while power is on, the NO output contact goes on. Operation Item Terminal No. (A) 2-10 Power (B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 Delayed (B) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO) Indicator
PWR
B: Cycle 2 (Signal Start, OFF First) When the start input turns on while power is on, the output oscillates at a preset cycle (Duty Ratio 1:1), starting while the NO contact off. Item Terminal No. Operation (A) 2-10 Power (B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 Delayed (B) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO) Indicator
OUT
OUT
Set Time
T
Ta
C: Cycle 4 (Signal Start, ON First) When the start input turns on while power is on the NO contact goes on. The output oscillates at a preset cycle (Duty Ratio 1:1).
Item Terminal No. ( ) 2-10 Power (A B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 ( B Delayed ) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO) Indicator
Operation
PWR
Set Time
Indicator T
T
T
T
T
T
T
T Ta
Operation
Item Terminal No. ( ) 2-10 Power (A B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 Delayed (B) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO)
Set Time
T
T
T
T
T
T Ta
T
T
Ta
T
T
Ta
F: One-Shot (Signal Start) When the start input turns on while power is on, the NO output contact goes on. When a preset time has elapsed, the output contact goes off.
Indicator
OUT
Operation
49
PWR OUT
T
Ta
T
Ta
Set Time
T
Note: T=Set Time, Ta=Shorter Than Set Time, (1):TRNP, (2): TRNB, (A): TRFP, (B): TRFB. Internal Connections External Control Start Signal 4 3
5 6 7
2
1 11
External Control Start Signal 1 2 3 8 9
10
(˜/+)
4
5
7
8
A (˜/-)
TRFP
6 9 B
(˜/+)
(˜/-) TRFB
Figure 49-134. Operational Figures (2 of 2)
CA08102001E
T
PWR
Item Terminal No. ( ) 2-10 Power (A B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 Delayed (B) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO)
PWR
Set Time
T
OUT
E: Signal OFF-Delay When power is turned on while the start input is on, the NO output contact goes on. When a preset time has elapsed after the start input turned off, the NO output contact goes off.
Indicator
T
D: Signal ON/OFF-Delay When the start input turns on while power is on, the NO output contact goes on. When a preset time has elapsed while the start input remains on, the output contact goes off. When the start input turns off, the NO contact goes on again. When a preset time has elapsed after the start input turned off, the NO contact goes off. Item Terminal No. Operation ( ) 2-10 Power (A B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 ( B Delayed ) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO)
OUT Set Time
PWR
For more information visit: www.eaton.com
Ta
Page 102
49-102
Control Relays & Timers Timing Relays July 2008
TR Series
Accessories
Dimensions
Table 49-159. Sockets for Use with TR Timers, Standard Pack of 10 Timing Relay
Terminal Style
Catalog Number
TRNP
8-Pin Octal
D3PA2
TRFP
11-Pin Octal
D3PA3
TRNB, TRFB
0.187" solder/QC terminals (Blade style)
D5PA2
Price U.S. $
3.07 (77.9) Pin (P) Type
2.95 (74.9) Blade (B) Type
Figure 49-135. Approximate Dimensions in Inches (mm)
49
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.eaton.com
CA08102001E
Page 103
Control Relays & Timers Timing Relays
49-103
July 2008
D80 Series, Pneumatic Timers
D80 Series, Pneumatic Timers
Technical Data and Specifications Table 49-160. Contact Ratings AC Pilot Duty, Amperes A600
DC Pilot Duty, Amperes B600
120V
240V
480V
600V
120V
240V
600V
40. 15.
20. 10.
10. 6.
8. 5., 0.5, 0.2, 0.02
30. 3.
15. 1.5
8. 1.
6. 0.8, 0.2, 0.1, - 1NO-1NC Make Break
2NO-2NC Make Break
Product Selection Catalog Number D80ND1A
When Ordering Specify ■ Catalog Number of Timer plus Suffix
Letter for solenoid volts and hertz. ■ Catalog Number of Enclosure (if required). Table 49-161. Pneumatic Timers Timed Contacts
■ Adjustable Timing Range:
0.5 to 180 seconds ■ Repeat Accuracy: +10% ■ Minimum Reset Time: 0.05 seconds
#NKCR ■ CSA certified
Catalog Number
D80NE1_ D80JE10_ D80JE11_ D80JE12_
D80ND1_ D80JD10_ D80JD11_ D80JD12_
2NO-2NC
N/A NONE 1NO-1NC 2NO-2NC
D80NE2_ D80JE20_ D80JE21_ D80JE22_
D80ND2_ D80JD20_ D80JD21_ D80JD22_
Price U.S. $
Must be ordered with solenoid assembly. Add Suffix letter from table below. ON or OFF Delay Timers are field convertible from ON to OFF or OFF to ON Delay by rotating the solenoid assembly 180°, timing function is shown on mounting plate. These timers will not accept instantaneous contacts.
Table 49-162. Solenoid Suffix Selection Table Volts/Hertz
Suffix
Volts/Hertz
Suffix
12 – 50/60 24 – 50/60 120/60 – 110/50 208 – 220/60
R T A E
240/60 – 220/50 380/50 480/60 – 440/50 600/60 – 550/50
B L C D
49
Consult Customer Support Center for availability.
Table 49-163. Solenoids – Can Be Used for Replacement or to Convert Above Items for Different Volts/Hertz Applications Volts/Hertz
Catalog Number
12 – 50/60 24 – 50/60 120/60 – 110/50 208 – 220/60
D80AMR D80AMT D80AMA D80AME
Standards and Certifications ■ UL listed, File #E1230, Guide
Catalog Number N/A None 1NO-1NC 2NO-2NC
Product Description
Design Characteristics
ON Delay, Time Delay After OFF Delay, Time Delay Energizing Timer Coil. After De-energizing Timer Convertible to OFF Delay Coil. Convertible to ON Delay
1NO-1NC
Catalog Number D80JD12A
Type D80 Timers are supplied only as complete devices with Switch Block(s) and Solenoid assembled. The Solenoids and Switch Blocks listed in Tables 49-163 and 49-164 can be used for replacement or conversion of D80 Timers.
Instantaneous Contacts
Price U.S. $
Volts/Hertz
Catalog Number
240/60 – 220/50 380/50 480/60 – 440/50 600/60 – 550/50
D80AMB D80AML D80AMC D80AMD
Price U.S. $
Table 49-164. Switch Blocks – Can Be Used for Either Timed or Instantaneous Contacts Circuit
Type of Contacts
Catalog Number
SPDT DPDT
1NO-1NC 2NO-2NC
D80AS1 D80AS2
Price U.S. $
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 CA08102001E
For more information visit: www.eaton.com
Page 104
49-104
Control Relays & Timers Phase Monitoring Relays July 2008
D65 Series, Product Family Overview
Contents Description
Page
Phase Monitoring Relays, D65 Series Product Family Overview . . . . . . . . . . . . . . 49-104 Phase Reversal. . . . . . . . . . . 49-106 Phase Loss and Reversal . . . . . . . . . . . . . . . 49-108 Phase Loss, Reversal and Undervoltage. . . . . . . . . . . 49-110 Phase Loss, Reversal, Unbalance and Under/ Overvoltage . . . . . . . . . . . . 49-112
Product Family Overview
Standards and Certifications
The D65 Series Phase Monitoring Relays provide protection against premature equipment failure caused by voltage faults on three-phase systems. All D65 phase monitoring relays are compatible with most Wye or Delta systems. In Wye systems, a connection to neutral is not required. Phase Monitoring relays protect against single-phasing regardless of any regenerative voltages.
D65VMC, D65PLR and D65PAR Series pending
D65VMLP Series
D65VMLS Series
Product Family Selection Table 49-165. D65 Product Family Selection Catalog Number
Mounting Style
Phase Loss
Phase Reversal
Phase Unbalance
Undervoltage
Overvoltage
Time Delay on Undervoltage
D65VMC
Plug-In
D65PLR
Plug-In
✓
✓
D65PAR
Plug-In
✓
✓
D65VMLP
Plug-In
✓
✓
✓
✓ (adj.)
✓ (fixed)
0.1 – 20 sec
D65VMLS
Surface
✓
✓
✓
✓ (adj.)
✓ (fixed)
0.1 – 20 sec
✓ ✓ (adj.)
50 mS fixed
In addition to the above approvals, all Plug-In Products are also UL Listed when used with the appropriate Eaton socket.
49
For more information visit: www.eaton.com
CA08102001E
Page 105
Control Relays & Timers Phase Monitoring Relays
49-105
July 2008
D65 Series, Product Family Overview
Application Description
Typical Connections
Protection
Line Side Monitoring
Depending on the unit selected, it will protect three-phase equipment against:
With the relay connected before the motor starter, the motor can be started in the reverse direction. However, the motor is unprotected against phase failures between the relay and the motor.
■ Phase Loss, total loss of one or more of the three phases. Also known as “single phasing”. Typically caused by a blown fuse, broken wire or worn contact. This condition would result in a motor drawing locked rotor current during start-up. In addition, a three-phase motor will continue to run after losing a phase, resulting in possible motor burn-out. ■ Phase Reversal, reversing any two of the three phases will cause a three-phase motor to run in the opposite direction. This may cause damage to driven machinery or injury to personnel. The condition usually occurs as a result of mistakes made during routine maintenance or when modifications are made to the circuit. ■ Phase Unbalance, unbalance of a three-phase system occurs when single-phase loads are connected such that one or two of the lines (phases) carry more or less of the load. This could cause motors to run at temperatures above published ratings. ■ Undervoltage, when voltage in all three lines of a three-phase system drop simultaneously. ■ Overvoltage, when voltage in all three lines of a three-phase system increase simultaneously.
L1 Stop
L2 O/L M
M M
L1
3 Phase Motor
M
L2
M
L3
Input Fuses 2A Max.
Phase Monitor Relay
Figure 49-136. Line Side Monitoring
Load Side Monitoring With the relay connected directly to the motor, the total feed lines are monitored. This connection should not be used with reversing motors. L1
L2
Start
O/L
Stop M
L1
Phase Monitor Relay M
L2 L3
3 Phase Motor
M M
Input Fuses 2A Max. Phase Monitor Relay
Figure 49-137. Load Side Monitoring
CA08102001E
Phase Monitor Relay
Start
For more information visit: www.eaton.com
49
Page 106
49-106
Control Relays & Timers Phase Monitoring Relays July 2008
D65 Series, Phase Reversal
Phase Reversal
Product Selection Table 49-166. Product Selection, D65VMC Series Mounting Style
Nominal Voltage 50/60 Hz
Catalog Number
Plug-in
120V
D65VMC120
Plug-in
208 – 480V
D65VMC480
Price U.S. $
Requires a 600V rated socket when used on system voltages greater than 300V.
Accessories Table 49-167. Accessories, D65VMC Series D65VMC Series Phase Reversal
Product Description The D65VMC Series Monitoring Relays provide protection against phase reversal in a compact plug-in design. One version will work on any threephase system from 208V to 480V (a separate 120V-only version is also available). These devices are designed to be compatible with most Wye or Delta systems. In Wye systems, a connection to a neutral is not required. The relay is energized and the LED on when the sequence is correct. Any fault will de-energize the relay and turn off the LED. Re-energization is automatic upon correction of the fault condition.
Description
Standard Pack
Catalog Number
8-Pin Socket Hold Down Spring
10 10
D3PA2 D65CHDS
Technical Data and Specifications Table 49-168. Technical Data, D65VMC Series, Phase Reversal Description
Specifications
Phase Reversal Output Contacts Life Response Times: Operate Release Load (Burden) Temperature Transient Protection Mounting
Unit trips if sequence of the three phases is anything other than A-B-C 10A SPDT @ 240V AC, 1/3 hp @ 240V AC (NO), 1/6 hp @ 240V AC (NC) Full Load, 100,000 operations
Indicator LED
Features
Price U.S. $
Reset
50 mS 50 mS 3 VA -20° to 150°F (-28° to 65°C) 10,000 volts for 20 microseconds Uses an 8-pin octal socket. Requires a 600V rated socket when used on system voltages greater than 300V Red LED on when all conditions are normal, and off when a fault condition has occurred Automatic upon correction of fault
■ Protects against phase reversal ■ One version works on 208 – 480V
49 three-phase systems ■ LED indicates both normal and fault conditions ■ Compact plug-in case utilizing industry-standard 8-pin octal socket ■ 10A SPDT output contacts
Standards and Certifications When used with appropriate Eaton socket.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com
CA08102001E
Page 107
Control Relays & Timers Phase Monitoring Relays
49-107
July 2008
D65 Series, Phase Reversal
Schematic ØA ØB
4
ØC
5
3
6
2
7 1
8
Figure 49-138. Wiring for 8-Pin Socket
Dimensions
2.4 (60)
1.7 (43)
2.9 (74)
3.0 (76)
Figure 49-139. D65VMC Series, Approximate Dimensions in Inches (mm)
49
CA08102001E
For more information visit: www.eaton.com
Page 108
49-108
Control Relays & Timers Phase Monitoring Relays July 2008
D65 Series, Phase Loss and Reversal
Phase Loss and Reversal
Product Selection Table 49-169. Product Selection, D65PLR Series Mounting Style
Nominal Voltage 50/60 Hz
Catalog Number
Plug-in
120V
D65PLR120
Plug-in
208V
D65PLR208
Plug-in
240V
D65PLR240
Plug-in
400V
D65PLR400
Plug-in
480V
D65PLR480
Price U.S. $
Requires a 600V rated socket when using on system voltages greater than 300V.
D65PLR Series Phase Loss and Reversal
Accessories Table 49-170. Accessories, D65PLR Series
Product Description The D65PLR Series Monitoring Relays provide protection against phase loss and phase reversal in a compact plugin design. These devices are designed to be compatible with most Wye or Delta systems. In Wye systems, a connection to a neutral is not required. Phase monitoring relays protect against single-phasing regardless of any regenerative voltages.
Standard Pack
Catalog Number
8-Pin Socket Hold Down Spring
10 10
D3PA2 D65CHDS
Price U.S. $
Technical Data and Specifications Table 49-171. Technical Data, D65PLR Series, Phase Loss and Reversal Description
Specifications Unit trips on loss of any Phase A, B or C Unit trips if sequence of the three phases is anything other than A-B-C 10A SPDT @ 240V AC, 1/3 hp @ 240V AC (NO), 1/6 hp @ 240V AC (NC) Full Load, 100,000 operations
Features
Phase Loss Phase Reversal Output Contacts Life Response Times: Operate Release Load (Burden) Temperature Transient Protection Mounting
■ Protects against phase loss and
Indicator LED
The relay is energized and the LED on when all three phases are present and in the correct sequence. Any fault will instantaneously de-energize the relay and turn off the LED. Re-energization is automatic upon correction of the fault condition.
49
Description phase reversal ■ LED indicates both normal and fault conditions ■ Compact plug-in case utilizing industry-standard 8-pin octal socket ■ 10A SPDT output contacts
Reset
50 mS 50 mS 3 VA -20° to 150°F (-28° to 65°C) 10,000 volts for 20 microseconds Uses an 8-pin octal socket. Requires a 600V rated socket when used on system voltages greater than 300V Red LED on when all conditions are normal, and off when a fault condition has occurred Automatic upon correction of fault
Standards and Certifications When used with appropriate Eaton socket.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com
CA08102001E
Page 109
Control Relays & Timers Phase Monitoring Relays
49-109
July 2008
D65 Series, Phase Loss and Reversal
Schematic ØA ØB
4
ØC
5
3
6
2
7 1
8
Figure 49-140. Wiring for 8-Pin Socket
Dimensions
2.4 (60)
1.7 (43)
2.9 (74)
3.0 (76)
Figure 49-141. D65PLR Series, Approximate Dimensions in Inches (mm)
49
CA08102001E
For more information visit: www.eaton.com
Page 110
49-110
Control Relays & Timers Phase Monitoring Relays July 2008
D65 Series, Phase Loss, Reversal and Undervoltage
Phase Loss, Reversal and Undervoltage
Product Selection Table 49-172. Product Selection, D65PAR Series Mounting Style
Nominal Voltage 60 Hz
Undervoltage Range
Catalog Number
Plug-in Plug-in
120V
90 – 115V
D65PAR120
208V
156 – 198V
D65PAR208
Plug-in
240V
180 – 230V
D65PAR240
Plug-in
400V
300 – 380V
D65PAR400
Plug-in
480V
360 – 460V
D65PAR480
Price U.S. $
Requires a 600V rated socket when using on system voltages greater than 300V.
D65PAR Series Phase Loss, Reversal and Undervoltage
Product Description The D65PAR Series Monitoring Relays provide protection against phase loss, phase reversal and undervoltage in a compact plug-in design. These devices are designed to be compatible with most Wye or Delta systems. In Wye systems, a connection to a neutral is not required. Phase monitoring relays protect against single-phasing regardless of any regenerative voltages. The relay is energized and the LED on when all three phases are present in the correct sequence at a voltage level above the undervoltage setting. The undervoltage drop-out can be set at 75 – 95% of operating voltage. Any fault will instantaneously de-energize the relay and turn off the LED. Re-energization is automatic upon correction of the fault condition.
49
Accessories Table 49-173. Accessories, D65PAR Series Description
Standard Pack
Catalog Number
8-Pin Socket Hold Down Spring
10 10
D3PA2 D65CHDS
Price U.S. $
Technical Data and Specifications Table 49-174. Technical Data, D65PAR Series, Phase Loss, Reversal and Undervoltage Description
Specifications
Phase Loss Phase Reversal Undervoltage
Unit trips on loss of any Phase A, B or C Unit trips if sequence of the three phases is anything other than A-B-C Adjustable over a range per product selection table. Unit trips when the average of all three lines is less than the adjusted set point. 10A SPDT @ 240V AC, 1/3 hp @ 240V AC (NO), 1/6 hp @ 240V AC (NC) Full Load, 100,000 operations
Output Contacts Life Response Times: Operate Release Load (Burden) Temperature Transient Protection Mounting
Features
Indicator LED
■ Protects against phase loss, phase
Reset
50 mS 50 mS 3 VA -20° to 150°F (-28° to 65°C) 10,000 volts for 20 microseconds Uses an 8-pin octal socket. Requires a 600V rated socket when used on system voltages greater than 300V Red LED on when all conditions are normal, and off when a fault condition has occurred Automatic upon correction of fault reversal and undervoltage ■ Undervoltage setting is adjustable from 75 – 95% of nominal ■ LED indicates both normal and fault conditions ■ Compact plug-in case utilizing industry-standard 8-pin octal socket ■ 10A SPDT output contacts
Standards and Certifications When used with appropriate Eaton socket.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com