For the Cutler-Hammer D26MB and Eaton D26MB

Page 101

Control Relays & Timers Timing Relays

49-101

July 2008

TR Series

TRFP, TRFB A: ON-Delay 2 (Signal Start) When a preset time has elapsed after the start input turned on while power is on, the NO output contact goes on. Operation Item Terminal No. (A) 2-10 Power (B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 Delayed (B) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO) Indicator

PWR

B: Cycle 2 (Signal Start, OFF First) When the start input turns on while power is on, the output oscillates at a preset cycle (Duty Ratio 1:1), starting while the NO contact off. Item Terminal No. Operation (A) 2-10 Power (B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 Delayed (B) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO) Indicator

OUT

OUT

Set Time

T

Ta

C: Cycle 4 (Signal Start, ON First) When the start input turns on while power is on the NO contact goes on. The output oscillates at a preset cycle (Duty Ratio 1:1).

Item Terminal No. ( ) 2-10 Power (A B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 ( B Delayed ) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO) Indicator

Operation

PWR

Set Time

Indicator T

T

T

T

T

T

T

T Ta

Operation

Item Terminal No. ( ) 2-10 Power (A B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 Delayed (B) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO)

Set Time

T

T

T

T

T

T Ta

T

T

Ta

T

T

Ta

F: One-Shot (Signal Start) When the start input turns on while power is on, the NO output contact goes on. When a preset time has elapsed, the output contact goes off.

Indicator

OUT

Operation

49

PWR OUT

T

Ta

T

Ta

Set Time

T

Note: T=Set Time, Ta=Shorter Than Set Time, (1):TRNP, (2): TRNB, (A): TRFP, (B): TRFB. Internal Connections External Control Start Signal 4 3

5 6 7

2

1 11

External Control Start Signal 1 2 3 8 9

10

(˜/+)

4

5

7

8

A (˜/-)

TRFP

6 9 B

(˜/+)

(˜/-) TRFB

Figure 49-134. Operational Figures (2 of 2)

CA08102001E

T

PWR

Item Terminal No. ( ) 2-10 Power (A B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 Delayed (B) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO)

PWR

Set Time

T

OUT

E: Signal OFF-Delay When power is turned on while the start input is on, the NO output contact goes on. When a preset time has elapsed after the start input turned off, the NO output contact goes off.

Indicator

T

D: Signal ON/OFF-Delay When the start input turns on while power is on, the NO output contact goes on. When a preset time has elapsed while the start input remains on, the output contact goes off. When the start input turns off, the NO contact goes on again. When a preset time has elapsed after the start input turned off, the NO contact goes off. Item Terminal No. Operation ( ) 2-10 Power (A B) A-B ( ) 5-6 Start (A B) 2-5 (A) 1-4, 8-11 ( B Delayed ) 1-7, 3-9 (NC) Contact (A) 1-3, 9-11 (B) 4-7, 6-9 (NO)

OUT Set Time

PWR

For more information visit: www.eaton.com

Ta

Page 102

49-102

Control Relays & Timers Timing Relays July 2008

TR Series

Accessories

Dimensions

Table 49-159. Sockets for Use with TR Timers, Standard Pack of 10 Timing Relay

Terminal Style

Catalog Number

TRNP

8-Pin Octal

D3PA2

TRFP

11-Pin Octal

D3PA3

TRNB, TRFB

0.187" solder/QC terminals (Blade style)

D5PA2

Price U.S. $

3.07 (77.9) Pin (P) Type

2.95 (74.9) Blade (B) Type

Figure 49-135. Approximate Dimensions in Inches (mm)

49

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.eaton.com

CA08102001E

Page 103

Control Relays & Timers Timing Relays

49-103

July 2008

D80 Series, Pneumatic Timers

D80 Series, Pneumatic Timers

Technical Data and Specifications Table 49-160. Contact Ratings AC Pilot Duty, Amperes A600

DC Pilot Duty, Amperes B600

120V

240V

480V

600V

120V

240V

600V

40. 15.

20. 10.

10. 6.

8. 5., 0.5, 0.2, 0.02

30. 3.

15. 1.5

8. 1.

6. 0.8, 0.2, 0.1, - 1NO-1NC Make Break

2NO-2NC Make Break

Product Selection Catalog Number D80ND1A

When Ordering Specify ■ Catalog Number of Timer plus Suffix

Letter for solenoid volts and hertz. ■ Catalog Number of Enclosure (if required). Table 49-161. Pneumatic Timers Timed Contacts

■ Adjustable Timing Range:

0.5 to 180 seconds ■ Repeat Accuracy: +10% ■ Minimum Reset Time: 0.05 seconds

#NKCR ■ CSA certified

Catalog Number

D80NE1_ D80JE10_ D80JE11_ D80JE12_

D80ND1_ D80JD10_ D80JD11_ D80JD12_

2NO-2NC

N/A NONE 1NO-1NC 2NO-2NC

D80NE2_ D80JE20_ D80JE21_ D80JE22_

D80ND2_ D80JD20_ D80JD21_ D80JD22_

Price U.S. $

Must be ordered with solenoid assembly. Add Suffix letter from table below. ON or OFF Delay Timers are field convertible from ON to OFF or OFF to ON Delay by rotating the solenoid assembly 180°, timing function is shown on mounting plate. These timers will not accept instantaneous contacts.

Table 49-162. Solenoid Suffix Selection Table Volts/Hertz

Suffix

Volts/Hertz

Suffix

12 – 50/60 24 – 50/60 120/60 – 110/50 208 – 220/60

R T A E

240/60 – 220/50 380/50 480/60 – 440/50 600/60 – 550/50

B L C D

49

Consult Customer Support Center for availability.

Table 49-163. Solenoids – Can Be Used for Replacement or to Convert Above Items for Different Volts/Hertz Applications Volts/Hertz

Catalog Number

12 – 50/60 24 – 50/60 120/60 – 110/50 208 – 220/60

D80AMR D80AMT D80AMA D80AME

Standards and Certifications ■ UL listed, File #E1230, Guide

Catalog Number N/A None 1NO-1NC 2NO-2NC

Product Description

Design Characteristics

ON Delay, Time Delay After OFF Delay, Time Delay Energizing Timer Coil. After De-energizing Timer Convertible to OFF Delay Coil. Convertible to ON Delay

1NO-1NC

Catalog Number D80JD12A

Type D80 Timers are supplied only as complete devices with Switch Block(s) and Solenoid assembled. The Solenoids and Switch Blocks listed in Tables 49-163 and 49-164 can be used for replacement or conversion of D80 Timers.

Instantaneous Contacts

Price U.S. $

Volts/Hertz

Catalog Number

240/60 – 220/50 380/50 480/60 – 440/50 600/60 – 550/50

D80AMB D80AML D80AMC D80AMD

Price U.S. $

Table 49-164. Switch Blocks – Can Be Used for Either Timed or Instantaneous Contacts Circuit

Type of Contacts

Catalog Number

SPDT DPDT

1NO-1NC 2NO-2NC

D80AS1 D80AS2

Price U.S. $

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 CA08102001E

For more information visit: www.eaton.com

Page 104

49-104

Control Relays & Timers Phase Monitoring Relays July 2008

D65 Series, Product Family Overview

Contents Description

Page

Phase Monitoring Relays, D65 Series Product Family Overview . . . . . . . . . . . . . . 49-104 Phase Reversal. . . . . . . . . . . 49-106 Phase Loss and Reversal . . . . . . . . . . . . . . . 49-108 Phase Loss, Reversal and Undervoltage. . . . . . . . . . . 49-110 Phase Loss, Reversal, Unbalance and Under/ Overvoltage . . . . . . . . . . . . 49-112

Product Family Overview

Standards and Certifications

The D65 Series Phase Monitoring Relays provide protection against premature equipment failure caused by voltage faults on three-phase systems. All D65 phase monitoring relays are compatible with most Wye or Delta systems. In Wye systems, a connection to neutral is not required. Phase Monitoring relays protect against single-phasing regardless of any regenerative voltages.

D65VMC, D65PLR and D65PAR Series pending

D65VMLP Series

D65VMLS Series

Product Family Selection Table 49-165. D65 Product Family Selection Catalog Number

Mounting Style

Phase Loss

Phase Reversal

Phase Unbalance

Undervoltage

Overvoltage

Time Delay on Undervoltage

D65VMC

Plug-In

D65PLR

Plug-In

✓

✓

D65PAR

Plug-In

✓

✓

D65VMLP

Plug-In

✓

✓

✓

✓ (adj.)

✓ (fixed)

0.1 – 20 sec

D65VMLS

Surface

✓

✓

✓

✓ (adj.)

✓ (fixed)

0.1 – 20 sec

✓ ✓ (adj.)

50 mS fixed

In addition to the above approvals, all Plug-In Products are also UL Listed when used with the appropriate Eaton socket.

49

For more information visit: www.eaton.com

CA08102001E

Page 105

Control Relays & Timers Phase Monitoring Relays

49-105

July 2008

D65 Series, Product Family Overview

Application Description

Typical Connections

Protection

Line Side Monitoring

Depending on the unit selected, it will protect three-phase equipment against:

With the relay connected before the motor starter, the motor can be started in the reverse direction. However, the motor is unprotected against phase failures between the relay and the motor.

■ Phase Loss, total loss of one or more of the three phases. Also known as “single phasing”. Typically caused by a blown fuse, broken wire or worn contact. This condition would result in a motor drawing locked rotor current during start-up. In addition, a three-phase motor will continue to run after losing a phase, resulting in possible motor burn-out. ■ Phase Reversal, reversing any two of the three phases will cause a three-phase motor to run in the opposite direction. This may cause damage to driven machinery or injury to personnel. The condition usually occurs as a result of mistakes made during routine maintenance or when modifications are made to the circuit. ■ Phase Unbalance, unbalance of a three-phase system occurs when single-phase loads are connected such that one or two of the lines (phases) carry more or less of the load. This could cause motors to run at temperatures above published ratings. ■ Undervoltage, when voltage in all three lines of a three-phase system drop simultaneously. ■ Overvoltage, when voltage in all three lines of a three-phase system increase simultaneously.

L1 Stop

L2 O/L M

M M

L1

3 Phase Motor

M

L2

M

L3

Input Fuses 2A Max.

Phase Monitor Relay

Figure 49-136. Line Side Monitoring

Load Side Monitoring With the relay connected directly to the motor, the total feed lines are monitored. This connection should not be used with reversing motors. L1

L2

Start

O/L

Stop M

L1

Phase Monitor Relay M

L2 L3

3 Phase Motor

M M

Input Fuses 2A Max. Phase Monitor Relay

Figure 49-137. Load Side Monitoring

CA08102001E

Phase Monitor Relay

Start

For more information visit: www.eaton.com

49

Page 106

49-106

Control Relays & Timers Phase Monitoring Relays July 2008

D65 Series, Phase Reversal

Phase Reversal

Product Selection Table 49-166. Product Selection, D65VMC Series Mounting Style

Nominal Voltage 50/60 Hz

Catalog Number

Plug-in

120V

D65VMC120

Plug-in

208 – 480V

D65VMC480

Price U.S. $

Requires a 600V rated socket when used on system voltages greater than 300V.

Accessories Table 49-167. Accessories, D65VMC Series D65VMC Series Phase Reversal

Product Description The D65VMC Series Monitoring Relays provide protection against phase reversal in a compact plug-in design. One version will work on any threephase system from 208V to 480V (a separate 120V-only version is also available). These devices are designed to be compatible with most Wye or Delta systems. In Wye systems, a connection to a neutral is not required. The relay is energized and the LED on when the sequence is correct. Any fault will de-energize the relay and turn off the LED. Re-energization is automatic upon correction of the fault condition.

Description

Standard Pack

Catalog Number

8-Pin Socket Hold Down Spring

10 10

D3PA2 D65CHDS

Technical Data and Specifications Table 49-168. Technical Data, D65VMC Series, Phase Reversal Description

Specifications

Phase Reversal Output Contacts Life Response Times: Operate Release Load (Burden) Temperature Transient Protection Mounting

Unit trips if sequence of the three phases is anything other than A-B-C 10A SPDT @ 240V AC, 1/3 hp @ 240V AC (NO), 1/6 hp @ 240V AC (NC) Full Load, 100,000 operations

Indicator LED

Features

Price U.S. $

Reset

50 mS 50 mS 3 VA -20° to 150°F (-28° to 65°C) 10,000 volts for 20 microseconds Uses an 8-pin octal socket. Requires a 600V rated socket when used on system voltages greater than 300V Red LED on when all conditions are normal, and off when a fault condition has occurred Automatic upon correction of fault

■ Protects against phase reversal ■ One version works on 208 – 480V

49 three-phase systems ■ LED indicates both normal and fault conditions ■ Compact plug-in case utilizing industry-standard 8-pin octal socket ■ 10A SPDT output contacts

Standards and Certifications When used with appropriate Eaton socket.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com

CA08102001E

Page 107

Control Relays & Timers Phase Monitoring Relays

49-107

July 2008

D65 Series, Phase Reversal

Schematic ØA ØB

4

ØC

5

3

6

2

7 1

8

Figure 49-138. Wiring for 8-Pin Socket

Dimensions

2.4 (60)

1.7 (43)

2.9 (74)

3.0 (76)

Figure 49-139. D65VMC Series, Approximate Dimensions in Inches (mm)

49

CA08102001E

For more information visit: www.eaton.com

Page 108

49-108

Control Relays & Timers Phase Monitoring Relays July 2008

D65 Series, Phase Loss and Reversal

Phase Loss and Reversal

Product Selection Table 49-169. Product Selection, D65PLR Series Mounting Style

Nominal Voltage 50/60 Hz

Catalog Number

Plug-in

120V

D65PLR120

Plug-in

208V

D65PLR208

Plug-in

240V

D65PLR240

Plug-in

400V

D65PLR400

Plug-in

480V

D65PLR480

Price U.S. $

Requires a 600V rated socket when using on system voltages greater than 300V.

D65PLR Series Phase Loss and Reversal

Accessories Table 49-170. Accessories, D65PLR Series

Product Description The D65PLR Series Monitoring Relays provide protection against phase loss and phase reversal in a compact plugin design. These devices are designed to be compatible with most Wye or Delta systems. In Wye systems, a connection to a neutral is not required. Phase monitoring relays protect against single-phasing regardless of any regenerative voltages.

Standard Pack

Catalog Number

8-Pin Socket Hold Down Spring

10 10

D3PA2 D65CHDS

Price U.S. $

Technical Data and Specifications Table 49-171. Technical Data, D65PLR Series, Phase Loss and Reversal Description

Specifications Unit trips on loss of any Phase A, B or C Unit trips if sequence of the three phases is anything other than A-B-C 10A SPDT @ 240V AC, 1/3 hp @ 240V AC (NO), 1/6 hp @ 240V AC (NC) Full Load, 100,000 operations

Features

Phase Loss Phase Reversal Output Contacts Life Response Times: Operate Release Load (Burden) Temperature Transient Protection Mounting

■ Protects against phase loss and

Indicator LED

The relay is energized and the LED on when all three phases are present and in the correct sequence. Any fault will instantaneously de-energize the relay and turn off the LED. Re-energization is automatic upon correction of the fault condition.

49

Description phase reversal ■ LED indicates both normal and fault conditions ■ Compact plug-in case utilizing industry-standard 8-pin octal socket ■ 10A SPDT output contacts

Reset

50 mS 50 mS 3 VA -20° to 150°F (-28° to 65°C) 10,000 volts for 20 microseconds Uses an 8-pin octal socket. Requires a 600V rated socket when used on system voltages greater than 300V Red LED on when all conditions are normal, and off when a fault condition has occurred Automatic upon correction of fault

Standards and Certifications When used with appropriate Eaton socket.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com

CA08102001E

Page 109

Control Relays & Timers Phase Monitoring Relays

49-109

July 2008

D65 Series, Phase Loss and Reversal

Schematic ØA ØB

4

ØC

5

3

6

2

7 1

8

Figure 49-140. Wiring for 8-Pin Socket

Dimensions

2.4 (60)

1.7 (43)

2.9 (74)

3.0 (76)

Figure 49-141. D65PLR Series, Approximate Dimensions in Inches (mm)

49

CA08102001E

For more information visit: www.eaton.com

Page 110

49-110

Control Relays & Timers Phase Monitoring Relays July 2008

D65 Series, Phase Loss, Reversal and Undervoltage

Phase Loss, Reversal and Undervoltage

Product Selection Table 49-172. Product Selection, D65PAR Series Mounting Style

Nominal Voltage 60 Hz

Undervoltage Range

Catalog Number

Plug-in Plug-in

120V

90 – 115V

D65PAR120

208V

156 – 198V

D65PAR208

Plug-in

240V

180 – 230V

D65PAR240

Plug-in

400V

300 – 380V

D65PAR400

Plug-in

480V

360 – 460V

D65PAR480

Price U.S. $

Requires a 600V rated socket when using on system voltages greater than 300V.

D65PAR Series Phase Loss, Reversal and Undervoltage

Product Description The D65PAR Series Monitoring Relays provide protection against phase loss, phase reversal and undervoltage in a compact plug-in design. These devices are designed to be compatible with most Wye or Delta systems. In Wye systems, a connection to a neutral is not required. Phase monitoring relays protect against single-phasing regardless of any regenerative voltages. The relay is energized and the LED on when all three phases are present in the correct sequence at a voltage level above the undervoltage setting. The undervoltage drop-out can be set at 75 – 95% of operating voltage. Any fault will instantaneously de-energize the relay and turn off the LED. Re-energization is automatic upon correction of the fault condition.

49

Accessories Table 49-173. Accessories, D65PAR Series Description

Standard Pack

Catalog Number

8-Pin Socket Hold Down Spring

10 10

D3PA2 D65CHDS

Price U.S. $

Technical Data and Specifications Table 49-174. Technical Data, D65PAR Series, Phase Loss, Reversal and Undervoltage Description

Specifications

Phase Loss Phase Reversal Undervoltage

Unit trips on loss of any Phase A, B or C Unit trips if sequence of the three phases is anything other than A-B-C Adjustable over a range per product selection table. Unit trips when the average of all three lines is less than the adjusted set point. 10A SPDT @ 240V AC, 1/3 hp @ 240V AC (NO), 1/6 hp @ 240V AC (NC) Full Load, 100,000 operations

Output Contacts Life Response Times: Operate Release Load (Burden) Temperature Transient Protection Mounting

Features

Indicator LED

■ Protects against phase loss, phase

Reset

50 mS 50 mS 3 VA -20° to 150°F (-28° to 65°C) 10,000 volts for 20 microseconds Uses an 8-pin octal socket. Requires a 600V rated socket when used on system voltages greater than 300V Red LED on when all conditions are normal, and off when a fault condition has occurred Automatic upon correction of fault reversal and undervoltage ■ Undervoltage setting is adjustable from 75 – 95% of nominal ■ LED indicates both normal and fault conditions ■ Compact plug-in case utilizing industry-standard 8-pin octal socket ■ 10A SPDT output contacts

Standards and Certifications When used with appropriate Eaton socket.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com