Page 111

Control Relays & Timers Phase Monitoring Relays

49-111

July 2008

D65 Series, Phase Loss, Reversal and Undervoltage

Schematic ØA ØB

4

ØC

5

3

6

2

7 1

8

Figure 49-142. Wiring for 8-Pin Socket

Dimensions

2.4 (60)

1.7 (43)

2.9 (74) 3.5 (89)

Figure 49-143. D65PAR Series, Approximate Dimensions in Inches (mm)

49

CA08102001E

For more information visit: www.eaton.com

Page 112

49-112

Control Relays & Timers Phase Monitoring Relays July 2008

D65 Series, Phase Loss, Reversal, Unbalance and Under/Overvoltage

Phase Loss, Reversal, Unbalance and Under/ Overvoltage

Application Description Protective Functions The D65 Series Relay makes separate trip decisions based on the status of the three-phase voltage inputs. Control power is derived from the threephase voltage inputs. Separate control power is not required. The device will trip in response to any combination of the following conditions: ■ Undervoltage, When voltage in

D65 Series

Product Description

49

The Cutler-Hammer® D65 Phase Monitoring Relay from Eaton’s electrical business protects distribution systems supplying motor feeder or branch circuits against premature equipment failure caused by voltage faults on three-phase systems, wye or delta connected. Phase monitoring relays protect against voltage imbalance and single-phasing regardless of any regenerative voltages. The relay is energized when the phase sequence and all voltages are correct. Any of five abnormal conditions (phase loss, phase reversal, overvoltage, undervoltage or phase imbalance) will de-energize the relay. As standard, re-energization is automatic upon correction of the fault condition. The D65 can also be wired for manual reset.

all three lines of a three-phase system drops simultaneously. Undervoltage drop-out can be set at 80 – 95% of operating voltage. Unit trips when the average of all three lines is less than the adjusted set point for a period longer than the adjustable time delay drop-out (0.1 – 20 seconds). This time delay eliminates nuisance tripping caused by momentary voltage fluctuation. ■ Overvoltage, Fixed at 110% of nominal, unit trips when the average of all three lines is greater than the fixed set point for a period longer than the time delay drop-out. ■ Phase Imbalance, Imbalance of a three-phase system occurs when single-phase loads are connected such that one or two of the lines (phases) carry more or less of the load. This could cause motors to run at temperatures above published ratings. Unit trips when any one of the three lines is more than the adjusted set point below the average of all three lines. The percent phase imbalance is adjustable from 2 – 10% and also has a Disable setting for applications where poor voltage conditions could cause nuisance tripping.

For more information visit: www.eaton.com

■ Phase Loss (Single-Phasing), Total loss of one or more of the three phases. Typically caused by a blown fuse, broken wire or worn contact. This condition would result in a motor drawing locked rotor current during start-up. In addition, a threephase motor will continue to run after losing a phase, resulting in potential motor burn-out. Unit trips on loss of any phase. ■ Phase Reversal, Reversing any two of the three phases will cause a three-phase motor to run in the opposite direction. This may cause damage to machinery or injury to personnel. Unit trips if rotation (sequence) of the three phases is anything other than A-B-C.

Features ■ Universal voltage range of 208 –

480V provides the flexibility to cover a variety of applications. 120V and 600V units also available. ■ Automatic or manual reset after the fault condition is corrected. ■ Multi-color LED indicates normal condition and defines fault type for simpler troubleshooting. ■ D65VMLS can be either mounted directly on 35 mm DIN rail with no additional parts or to a back-panel with two screws. No socket required. D65VMLP will plug into D3PA2 socket and mount on 35 mm DIN rail. ■ Small, compact size. ■ User-adjustable settings include nominal voltage, percent phase imbalance, undervoltage drop-out, time delay on undervoltage and time delay on restart after fault.

CA08102001E

Page 113

Control Relays & Timers Phase Monitoring Relays

49-113

July 2008

D65 Series, Phase Loss, Reversal, Unbalance and Under/Overvoltage

Operation

Technical Data and Specifications

The D65 provides protection against premature equipment failure caused by voltage faults on three-phase systems. The D65 is designed to be compatible with most wye or delta systems. In wye systems, a connection to a neutral is not required. D65 Phase Monitoring Relays protect against unbalanced voltages or single-phasing regardless of any regenerative voltages. The relay is energized when the phase sequence and all voltages are correct. Any one of five fault conditions will de-energize the relay. Re-energization is automatic upon correction of the fault condition. Manual reset is available if a NC switch is wired to the appropriate terminals. A multi-color LED indicates normal condition and also provides specific fault indication to simplify troubleshooting. The percent phase imbalance is adjustable from 2 – 10%, and the undervoltage drop-out can be set at 80 – 95% of operating voltage. The adjustable time delay drop-out on undervoltage (0.1 – 20 sec.) eliminates nuisance tripping caused by momentary voltage fluctuations. Table 49-175. LED Operation LED Status

Indicator

Green Steady

Normal/Relay ON

Table 49-177. D65 Series Specifications Description

Specifications

Nominal Voltages (50 – 60 Hz) Connections Output Contacts for D65VMLS

120V, 208 – 480V, 575V

Output Contacts for D65VMLP Dielectric Operating Temp. Response Time Power Up Restart after Fault Drop-out due to Fault

Mechanical Life Electrical Life Power Consumption Net Weight

Green Flashing

Power-Up/Restart Delay

Red Steady

Unbalance

Red Flashing

Undervoltage/Overvoltage

Hysteresis

Amber Steady

Reversal

Amber Flashing

Loss

Dimensions

Alternating Green/Red

Undervoltage/Overvoltage Trip Pending

Alternating Red/Amber

Nominal Voltage Set Error

3-wire wye or delta SPDT and SPNC (surface mount version only) NO: 10A Resistive @ 240V AC / 30V DC, 1/2 hp @ 240V AC NC: 10A Resistive @ 240V AC / 30V DC, 1/3 hp @ 240V AC SPDT: 10A Resistive @ 240V AC / 30V DC; 1/2 hp @ 120/240V AC 1000V + (2 * Nominal Voltage Rating) between input terminals and case or active circuitry -20° – 150°F (-28° – 65°C) 1 – 300 seconds adjustable 1 – 300 seconds adjustable 100 mS fixed on phase loss and phase reversal; 2 seconds fixed on phase imbalance; 0.1 – 20 sec. adjustable on undervoltage only; inverse time curve for overvoltage 10,000,000 operations 100,000 operations 3 VA 10.3 oz. (292g) D65VMLS 6.4 oz. (181g) D65VMLP 2 – 3%

0.2 (5) Mounting Holes – 2 Places

Standards and Certifications 2.7 2.4 (70) (60)

(Low Voltage + EMC Directive EN60947-5-1) (D65VMLS only) (D65VMLP only)

1.4 (35) 1.8 (45)

4.4 (112) 4.5 (114)

49 When used with accompanying Eaton Socket. (D65VMLP only)

2.4 (60)

UL Listed

Product Selection When Ordering Specify ■ Catalog Number

1.7 (43)

Table 49-176. Phase Monitoring Relay Mounting Style

Operating Voltage, 50/60 Hz

Catalog Number

Surface-Mount (DIN Rail or Panel)

120V 208 – 480V 600V

D65VMLS120 D65VMLS480 D65VMLS600

Plug-In (DIN Rail)

120V 208 – 480V

D65VMLP120 D65VMLP480

8-pin Socket, D3PA2

8-pin IP20 Rated Socket, D3PA6

Price U.S. $

2.9 (74) 3.0 (77)

Figure 49-144. Surface-Mount and Plug-In, Approximate Dimensions in Inches (mm)

Requires a 600V-rated socket when used on system voltages greater than 300V. The D3PA2 socket is rated 10A, 600V. For Dimensions, see Page 49-46. For Dimensions, see Page 49-47. Additional models available. Please visit our website for the latest offering.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1

Page 114

49-114

Control Relays & Timers Phase Monitoring Relays July 2008

D65 Series, Phase Loss, Reversal, Unbalance and Under/Overvoltage

Wiring Diagrams ØA ØB ØC A B C 11 21

ØA ØB ØC

3 2

4 5 1 8

Manual Reset

6 7

12 14 M1M2 22 Manual Reset

Figure 49-145. Surface-Mount and Plug-In Wiring Diagrams

Typical Connections Line Side Monitoring With the relay connected before the motor starter, the motor can be started in the reverse direction. However, the motor is unprotected against phase failures between the relay and the motor.

L1

START

STOP

With the relay connected directly to the motor, the total feed lines are monitored. This connection should not be used with reversing motors.

L2

M

M

Load Side Monitoring

O/L Voltage Monitor Relay

M

L1

3 Phase Motor

M

L2

M

L3

Input Fuses (Recommended) Voltage 2A Max. Monitor Relay Line Side Monitoring L1

START

STOP

O/L

L2

M

L1

49

Voltage Monitor Relay M

L2 L3

3 Phase Motor

M M

Voltage Monitor Relay Load Side Monitoring

Input Fuses (Recommended) 2A Max.

Figure 49-146. Line Side and Load Side Monitoring

For more information visit: www.eaton.com

CA08102001E

Page 115

Control Relays & Timers Current Monitoring Relays

49-115

July 2008

D65C Series, Product Family Overview

Contents Description

Product Family Selection Page

D65C Series Product Family Overview . . . . . . . . . . . . . 49-115 Standard Current Monitors, D65CE Series . . . . . . . . . 49-116 Overcurrent Monitors, D65CH Series . . . . . . . . . 49-118 Undercurrent Monitors, D65CL Series . . . . . . . . . . 49-120

Standard Fixed time delay on both pick-up and drop-out current settings. Table 49-178. D65C Product Family Selection, Standard Function Series

D65CE

Pick-Up Setting

Time Delay

Drop-Out Setting

Page Time Delay

Fixed 100 mS Fixed (-5% Pick-Up) Adjustable (50 – 95% Pick-Up)

Adjustable (Across Monitored Range)

D65CEK

Fixed 100 mS

49-116

Fixed time delay eliminates nuisance tripping due to short current surges or drops.

Overcurrent Adjustable time delay on pick-up and fixed time delay on drop-out current settings. Table 49-179. D65C Product Family Selection, Overcurrent Function Series

D65CH

Pick-Up Setting

Time Delay

Adjustable (Across Monitored Range)

0.1 – 10 sec Adjustable

D65CHK

Current Monitoring Relays

Product Family Overview The D65C Series Current Monitoring Relays monitor AC single-phase currents for over- or undercurrent conditions in three current ranges: 0.1 – 1A, 0.5 – 5A, and 1 – 10A. An external current transformer may be used to extend the range of the product. A separate 24V or 120V AC input (supply) voltage is required to power the unit. All versions are available in a compact plug-in case utilizing industry standard 8- or 11-pin octal sockets.

Drop-Out Setting

49-118

Undercurrent Fixed time delay on pick-up and adjustable time delay on drop-out current settings. Table 49-180. D65C Product Family Selection, Undercurrent Function Series

D65CL

Pick-Up Setting

Time Delay

Fixed (+5% Drop-Out)

Fixed 100 mS Adjustable (Across Monitored Range)

Drop-Out Setting

Page Time Delay 0.1 – 10 sec Adjustable

49-120

Fixed time delay eliminates nuisance tripping due to short current surges or drops.

Typical Installations

49 Without External CT M

With External CT M

L1

L1 M

Motor

M

L2

Motor

L2

Control Voltage

M 3 4

1

5 6

2 8

Current Monitor Relay

Figure 49-147. Typical Installation without External CT

CA08102001E

Fixed 100 mS

Fixed (-5% Pick-Up) Adjustable (50 – 95% Pick-Up)

Fixed time delay eliminates nuisance tripping due to short current surges or drops.

Standards and Certifications When used with accompanying Eaton socket.

Page Time Delay

For more information visit: www.eaton.com

Control Voltage

M 3 4

1

5 6

2 8

Current Monitor Relay

Figure 49-148. Typical Installation with External CT

Page 116

49-116

Control Relays & Timers Current Monitoring Relays July 2008

D65C Series, Standard Current Monitors

Standard Current Monitors Monitored Current

Pick-Up Current

Drop-Out Current

Input Power (Voltage) Relay Output

On Off On Off

Figure 49-149. Standard Current Monitoring

Product Selection Table 49-181. Product Selection, D65C Series, Standard Current Monitors D65C Series Standard Current Monitors

Product Description

49

The D65CE Series Standard Current Monitors are used to detect either an overcurrent or undercurrent condition. The pick-up current setting is user-adjustable within three ranges (0.1 – 1A), (0.5 – 5A), or (1 – 10A). The range can be extended beyond 10A with the use of an external current transformer. Choose between a fixed drop-out current setting at 95% of the selected pick-up setting or an adjustable drop-out setting of 50 – 95% of the selected pick-up setting. The relay will energize when the monitored AC current is above the pick-up setting, and will de-energize when the monitored AC current is below the drop-out setting. The time delay on both pick-up and drop-out is fixed at 100 mS. Adjustable time delays are available with the D65CH and D65CL Series.

Features ■ Monitors AC single-phase currents

Pick-Up Setting

Drop-Out Setting

Input Voltage

Current Range Monitored

Catalog Number

24V AC

0.1 – 1A 0.5 – 5A 1 – 10A

120V AC

0.1 – 1A 0.5 – 5A 1 – 10A 0.1 – 1A 0.5 – 5A 1 – 10A

D65CE1C01T D65CE1C5T D65CE1C10T D65CE1C01A D65CE1C5A D65CE1C10A

Price U.S. $

SPDT, 8-Pin Plug-In Adjustable

Adjustable

Fixed (At 95% of Pick-Up)

Adjustable (From 50- 95% of Pick-Up)

24V AC

D65CEK1C01T D65CEK1C5T D65CEK1C10T

120V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CEK1C01A D65CEK1C5A D65CEK1C10A

24V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CE2C01T D65CE2C5T D65CE2C10T

120V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CE2C01A D65CE2C5A D65CE2C10A

24V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CEK2C01T D65CEK2C5T D65CEK2C10T

120V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CEK2C01A D65CEK2C5A D65CEK2C10A

DPDT, 11-Pin Plug-In Adjustable

Adjustable

Fixed (At 95% of Pick-Up)

Adjustable (From 50- 95% of Pick-Up)

Accessories

■ Three separate current monitoring

Table 49-182. Accessories, D65CE Current Monitors ranges covering 0.1 – 10 amperes ■ External CT can be used to extend ranges ■ Adjustable pick-up setting with either fixed or adjustable drop-out setting ■ LED indicates output relay status ■ Choice of compact 8-pin SPDT or 11pin DPDT plug-in case ■ 10A output contacts

Description

Standard Pack

Catalog Number

8-Pin Socket 11-Pin Socket Hold Down Spring

10 10 10

D3PA2 D3PA3-A2 D65CHDS

Price U.S. $

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com

CA08102001E

Page 117

Control Relays & Timers Current Monitoring Relays

49-117

July 2008

D65C Series, Standard Current Monitors

Technical Data and Specifications

Schematics

Table 49-183. Technical Data, D65C Series, Standard Current Monitors Description

Specifications

Input Voltage Tolerance Load (Burden) Current Settings: Pick-Up Drop-Out

AC Operation: +10/-15% of nominal voltage at 50/60 Hz Less than 5 VA

Monitored Current (L1)

Adjustable throughout current range monitored Fixed at 95% of pick-up setting for D65CE Adjustable from 50 – 95% of pick-up setting for D65CEK -20 to 131°F (-28 to 55°C)

Temperature Response Times: Pick-Up Drop-Out Output Contacts

(L2)

4 5 3

6

2

7 1 8

100 mS 100 mS 10A Resistive @240V AC / 30V DC 1/2 hp @ 240V AC (NO); 1/3 hp @ 240V AC (NC) 10,000,000 operations 100,000 operations Green when input voltage is applied; Red when relay is energized Automatic Requires an 8- or 11-pin socket

Mechanical Life Electrical Life Indicator LED Reset Mounting

Input Voltage

Figure 49-152. Wiring for 8-Pin Socket

Monitored Current

Dimensions 4

5

6 7

3 2

8 9 10

1 11

(L1) 2.4 (60)

(L2)

Figure 49-153. Wiring for 11-Pin Socket D65CEK Only 2.9 (74)

1.7 (43)

3.5 (89)

49 Figure 49-150. D65CE Series, Approximate Dimensions in Inches (mm) 6-32 x 0.312 Combination Head Screw and Pressure Clamping Plate (8 Places)

6-32 x 0.312 Combination Head Screw and Pressure Clamp (11 Places)

Two 0.165 (4.2) Dia. Slots

2.14 (54.3) 2.03 (51.4)

1.30 (32.9) 1.60 (40.5) Max.

Two 0.17 (4.3) Dia. Holes

2.05 (52.07) Max.

2.06 (52.3)

0.82 (20.8) 0.58 (14.7) 0.97 (24.6) Max. Tolerances: ± 0.010 ± (0.25) Unless Otherwise Shown

2.33 (59.1) 0.97 Max. (24.6) Tolerances: ± 0.010 ± (0.25) Unless Otherwise Shown

D3PA2

D3PA3

Figure 49-151. D3PA2 and D3PA3 Sockets, Approximate Dimensions in Inches (mm)

CA08102001E

0.125 – 0.156 (3.17 – 3.96))

For more information visit: www.eaton.com

0.15 (3.6) 0.58 (14.7) 0.77 (19.6)

Page 118

49-118

Control Relays & Timers Current Monitoring Relays July 2008

D65C Series, Overcurrent Monitors

Overcurrent Monitors Monitored Current

Pick-Up Current Drop-Out Current

Input Power (Voltage)

On Off On

Relay Output

Off T

T

Figure 49-154. Overcurrent Monitoring

Product Selection D65C Series Overcurrent Monitors

Product Description

49

The D65C Series Overcurrent Monitoring Relays are used to detect an overcurrent condition. The pick-up current setting is user-adjustable within one of three ranges as shown in product selection table. An external current transformer can be used to extend the range beyond 10A. Users may select a fixed drop-out current setting (95% of the selected pick-up setting) or an adjustable drop-out setting (50 – 95% of the selected pickup setting). The relay will energize when the monitored AC current is above the pick-up setting for a period longer than the adjustable time delay of 0.1 – 10 seconds. This delay prevents nuisance tripping caused by inrush currents. It will de-energize when the monitored AC current is below the drop-out setting.

Table 49-184. Product Selection, D65C Series, Overcurrent Monitors Pick-Up Setting

Drop-Out Setting

Input Voltage

Current Range Monitored

Catalog Number

24V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CH1C1T D65CH1C5T D65CH1C10T

120V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CH1C1A D65CH1C5A D65CH1C10A

24V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CHK1C1T D65CHK1C5T D65CHK1C10T

120V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CHK1C1A D65CHK1C5A D65CHK1C10A

24V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CH2C1T D65CH2C5T D65CH2C10T

120V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CH2C1A D65CH2C5A D65CH2C10A

24V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CHK2C1T D65CHK2C5T D65CHK2C10T

120V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CHK2C1A D65CHK2C5A D65CHK2C10A

SPDT, 8-Pin Plug-In Adjustable

Adjustable

Fixed (At 95% of Pick-Up)

Adjustable (From 50- 95% of Pick-Up)

DPDT, 11-Pin Plug-In Adjustable

Adjustable

Fixed (At 95% of Pick-Up)

Adjustable (From 50- 95% of Pick-Up)

Features ■ Monitors AC single-phase currents for overcurrent conditions ■ Three separate current monitoring ranges covering 0.1 – 10 amperes ■ External CT can be used to extend ranges ■ Adjustable pick-up setting with either fixed or adjustable drop-out setting ■ Adjustable time delay of 0.1 – 10 seconds on pick-up ■ LED indicates output relay status ■ Choice of compact SPDT (8-pin) or DPDT (11-pin) plug-in case ■ 10A output contacts

Price U.S. $

Accessories Table 49-185. Accessories, D65CH Overcurrent Monitors Description

Standard Pack

Catalog Number

8-Pin Socket 11-Pin Socket Hold Down Spring

10 10 10

D3PA2 D3PA3-A2 D65CHDS

Price U.S. $

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com

CA08102001E

Page 119

Control Relays & Timers Current Monitoring Relays

49-119

July 2008

D65C Series, Overcurrent Monitors

Technical Data and Specifications

Schematics

Table 49-186. Technical Data, D65C Series, Overcurrent Monitors Description

Specifications

Input Voltage Tolerance Load (Burden) Current Settings: Pick-Up Drop-Out

AC Operation: +10/-15% of nominal voltage at 50/60 Hz. Less than 5 VA

Monitored Current (L1)

Adjustable throughout current range monitored Fixed at 95% of pick-up setting for D65CH Adjustable from 50 – 95% of pick-up setting for D65CHK -20 to 131°F (-28 to 55°C)

Temperature Response Times: Pick-Up Drop-Out Output Contacts

Reset Mounting

(L2)

4 5 3

6

2

7 1 8

Adjustable 0.1 – 10 seconds Fixed at 100 mS 10A Resistive @240V AC / 30V DC 1/2 hp @ 240V AC (NO); 1/3 hp @ 240V AC (NC) 10,000,000 operations 100,000 operations Green when input voltage is applied; Red Flashing when in time delay; Red Steady when relay is energized Automatic Requires an 8- or 11-pin socket

Mechanical Life Electrical Life Indicator LED

Input Voltage

Figure 49-157. Wiring for 8-Pin Socket

Monitored Current

Dimensions

4

5

6 7

3 2

8 9 10

1 11

(L1) 2.4 (60)

(L2)

Figure 49-158. Wiring for 11-Pin Socket D65CHK Only 2.9 (74)

1.7 (43)

3.5 (89)

Figure 49-155. D65CH Series, Approximate Dimensions in Inches (mm) 6-32 x 0.312 Combination Head Screw and Pressure Clamping Plate (8 Places)

6-32 x 0.312 Combination Head Screw and Pressure Clamp (11 Places)

Two 0.165 (4.2) Dia. Slots

2.14 (54.3)

Two 0.17 (4.3) Dia. Holes

2.05 (52.07) Max.

2.03 (51.4)

1.30 (32.9) 1.60 (40.5) Max.

49

2.06 (52.3)

0.82 (20.8) 0.58 (14.7) 0.97 (24.6) Tolerances: ± 0.010 Max. ± (0.25) Unless Otherwise Shown

2.33 (59.1) 0.97 Max. (24.6) Tolerances: ± 0.010 ± (0.25) Unless Otherwise Shown

D3PA2

D3PA3

Figure 49-156. D3PA2 and D3PA3 Sockets, Approximate Dimensions in Inches (mm)

CA08102001E

0.125 – 0.156 (3.17 – 3.96))

For more information visit: www.eaton.com

0.15 (3.6) 0.58 (14.7) 0.77 (19.6)

Page 120

49-120

Control Relays & Timers Current Monitoring Relays July 2008

D65C Series, Undercurrent Monitors

Undercurrent Monitors Monitored Current

Pick-Up Current Drop-Out Current

Input Power (Voltage)

On Off On

D65C Series Undercurrent Monitors

Relay Output

Off T

Product Description The D65CL Series is designed to detect an undercurrent condition. The drop-out current setting is user-adjustable within one of three ranges shown below. An external current transformer can be used to extend the range beyond 10A. The pick-up current setting is fixed at +5% of the selected drop-out setting. The relay will energize when the monitored AC current is above the pick-up setting. It will de-energize when the monitored AC current is below the drop-out setting for a period longer than the adjustable time delay of 0.1 – 10 seconds. This delay prevents nuisance tripping caused by momentary line dips. The relay will energize when the current rises 5% above the drop-out setting.

Figure 49-159. Undercurrent Monitoring

Product Selection Table 49-187. Product Selection, D65C Series, Undercurrent Monitors Pick-Up Setting

Drop-Out Setting

Input Voltage

Current Range Monitored

Catalog Number

Adjustable

24V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CL1C1T D65CL1C5T D65CL1C10T

120V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CL1C1A D65CL1C5A D65CL1C10A

24V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CL2C1T D65CL2C5T D65CL210T

120V AC

0.1 – 1A 0.5 – 5A 1 – 10A

D65CL2C1A D65CL2C5A D65CL2C10A

SPDT, 8-Pin Plug-In Fixed (At 5% of Drop-Out)

SPDT, 11-Pin Plug-In Fixed (At 5% of Drop-Out)

Adjustable

Features

49

■ Monitors AC single-phase currents for undercurrent conditions ■ Three separate current monitoring ranges covering 0.1 – 10 amperes ■ External CT can be used to extend ranges ■ Adjustable drop-out setting with fixed pick-up setting ■ Adjustable time delay of 0.1 – 10 seconds on drop-out ■ LED indicates output relay status ■ Choice of compact SPDT (8-pin) or DPDT (11-pin) plug-in case ■ 10A output contacts

Price U.S. $

Accessories Table 49-188. Accessories, D65CL Undercurrent Monitors Description

Standard Pack

Catalog Number

8-Pin Socket 11-Pin Socket Hold Down Spring

10 10 10

D3PA2 D3PA3-A2 D65CHDS

Price U.S. $

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com

CA08102001E