Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 13 of 15

Control Relays & Timers, pages 121 to 130

Pages 121 to 130 of 142

The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Cutler-Hammer D26MB and Eaton D26MB

Page 121

Control Relays & Timers Current Monitoring Relays

49-121

July 2008

D65C Series, Undercurrent Monitors

Technical Data and Specifications

Schematics

Table 49-189. Technical Data, D65C Series, Undercurrent Monitors Description

Specifications

Input Voltage Tolerance Load (Burden) Current Settings: Pick-Up Drop-Out Temperature Response Times: Pick-Up Drop-Out Output Contacts

AC Operation: +10/-15% of nominal voltage at 50/60 Hz. Less than 5 VA

Monitored Current

Input Voltage (L1)

Fixed at 5% above adjustable drop-out setting Adjustable throughout current range monitored -20 to 131°F (-28 to 55°C)

4 5 3

6

2 Fixed at 100 mS Adjustable 0.1 – 10 seconds 10A Resistive @240V AC / 30V DC 1/2 hp @ 240V AC (NO); 1/3 hp @ 240V AC (NC) 10,000,000 operations 100,000 operations Green when input voltage is applied; Red Flashing when in time delay; Red Steady when relay is energized Automatic Requires an 8- or 11-pin socket

Mechanical Life Electrical Life Indicator LED Reset Mounting

(L2)

7 1 8

Figure 49-162. Wiring for 8-Pin Socket

Monitored Current

Dimensions 4

5

6 7

3 2

8 9 10

1 11

(L1)

2.4 (60)

(L2)

Figure 49-163. Wiring for 11-Pin Socket 2.9 (74)

1.7 (43)

3.5 (89)

Figure 49-160. D65CL Series, Approximate Dimensions in Inches (mm)

49 6-32 x 0.312 Combination Head Screw and Pressure Clamping Plate (8 Places)

6-32 x 0.312 Combination Head Screw and Pressure Clamp (11 Places)

Two 0.165 (4.2) Dia. Slots

2.14 (54.3)

2.05 (52.07) Max.

2.03 (51.4)

1.30 (32.9) 1.60 (40.5) Max.

Two 0.17 (4.3) Dia. Holes

2.06 (52.3)

0.82 (20.8) 0.58 (14.7) 0.97 (24.6) Tolerances: ± 0.010 Max. ± (0.25) Unless Otherwise Shown

2.33 (59.1) 0.97 Max. (24.6) Tolerances: ± 0.010 ± (0.25) Unless Otherwise Shown

D3PA2

D3PA3

Figure 49-161. D3PA2 and D3PA3 Sockets, Approximate Dimensions in Inches (mm)

CA08102001E

0.125 – 0.156 (3.17 – 3.96))

For more information visit: www.eaton.com

0.15 (3.6) 0.58 (14.7) 0.77 (19.6)

Page 122

49-122

Control Relays & Timers Voltage Monitoring Relays July 2008

D65V Series, Product Family Overview

Contents Description

Product Family Selection Page

D65V Series, Voltage Monitoring Product Family Overview . . . . . . . 49-122 Fixed Time Delay for Over/Undervoltage, D65VMP and D65VMKP Series . . . . . . . . . . 49-123, 49-125 Adjustable Time Delay for Over/Undervoltage, D65VAP and D65VAKP Series . . . . . . . . . . 49-124, 49-125 Voltage Band, D65VW Series . . . 49-126

Over/Undervoltage Relays Over/Undervoltage Relays provide protection to equipment where either an overor undervoltage condition is potentially damaging. Each relay can be used as either an overvoltage or an undervoltage relay, depending on the output contact used. When used as an undervoltage relay, it provides protection to equipment that is required to operate above a minimum voltage. When used as an overvoltage relay, it protects equipment against excessive voltage conditions. Over/undervoltage relays are designed to operate when the operating voltage reaches a preset value and drop out when the operating voltage drops to a level below the preset value. Table 49-190. D65V Product Family Selection, Over/Undervoltage Relays Series

Pick-Up Voltage

D65VMP D65VMKP

Adjustable Fixed at 95% of Pick-Up 85 – 115% Nomi- Adjustable 75 – 95% of nal Pick-Up Fixed at 95% of Pick-Up Adjustable 75 – 95% of Pick-Up

D65VAP D65VAKP

Drop-Out Voltage

Time Delay Drop-Out

Page

Fixed 500 mS

49-123 49-123

Adjustable 0.5 – 10 seconds

49-124 49-124

Fixed time delay eliminates nuisance tripping due to short voltage surges or drops.

Voltage Band Relays Voltage Band Relays provide protection to equipment that is required to operate within an upper and lower voltage limit. As long as the operating voltage remains within an over- and undervoltage range, the internal relay stays energized. If the operating voltage falls outside this range, the relay will drop out. Table 49-191. D65V Product Family Selection, Voltage Band Relays

Product Family Overview

49

Voltage Monitoring Relays monitor either AC single-phase (50/60 Hz) or DC voltages to protect equipment against voltage fault conditions. No separate supply (input) voltage is required. All versions are available in a compact plugin case utilizing an 8-pin octal socket.

Series

Pick-Up Voltage

Drop-Out Voltage

D65VWP D65VWKP

Adjustable 100 –- Adjustable 125% Nominal 75 – 100% of Nominal

Time Delay Drop-Out

Page

Fixed 500 mS Adjustable 0.5 – 10 seconds

49-126 49-126

Fixed time delay eliminates nuisance tripping due to short voltage surges or drops.

There are two styles of Voltage Monitoring Relays, ■ Over/Undervoltage Relays ■ Voltage Band Relays

Standards and Certifications When used with accompanying Eaton socket.

For more information visit: www.eaton.com

CA08102001E

Page 123

Control Relays & Timers Voltage Monitoring Relays

49-123

July 2008

D65V Series, Fixed Time Delay Over/Undervoltage Relays

Fixed Time Delay for Over/Undervoltage Pick-Up Voltage Monitored Voltage Drop-Out Voltage T

Relay Output

T

On Off

Figure 49-164. Fixed Time Delay Over/Undervoltage

Product Selection D65VMP & D65VMKP Series Over/Undervoltage Relays

Product Description The D65VMRP & D65VMKP Over/Undervoltage Relays provide protection to equipment where either an over- or undercurrent condition is potentially damaging. They are designed to operate when the operating voltage reaches a preset value and drop out when the operating voltage drops to a level below the preset value. The pick-up voltage setting is useradjustable from 85 – 115% of the nominal voltage rating. As standard, the D65VMRP Series has a drop-out voltage setting fixed at 95% of the pick-up voltage setting. An adjustable dropout setting of 75 – 95% of the pick-up setting is available on the D65VMKP Series. The relay energizes when the monitored voltage is above the pick-up setting. The relay de-energizes when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay, which is fixed at 500 mS. An adjustable time delay on drop-out of 0.5 – 10 seconds is available.

Table 49-192. Product Selection, D65VMP & D65VMKP Series, Over/Undervoltage Relays Nominal Voltage

Voltage Range Pick-Up

Drop-Out

Catalog Number

21 – 27V AC 102 – 138V AC

20 – 26V AC 97 – 131V AC

D65VMRPT D65VMRPA

10 – 14V DC 21 – 27V DC 41 – 55V DC 94 – 126V DC

9 – 13V DC 20 – 26V DC 39 – 52V DC 89 – 121V DC

D65VMRPR1 D65VMRPT1 D65VMRPW1 D65VMRPA1

21 – 27V AC 102 – 138V AC

16 – 26V AC 77 – 131V AC

D65VMKPT D65VMKPA

10 – 14V DC 21 – 27V DC 41 – 55V DC 94 – 126V DC

8 – 13V DC 16 – 26V DC 32 – 52V DC 71 – 121V DC

D65VMKPR1 D65VMKPT1 D65VMKPW1 D65VMKPA1

Price U.S. $

Adjustable Pick-Up, Fixed Drop-Out Settings 24V AC 120V AC 12V DC 24V DC 48V DC 110V DC

Adjustable Pick-Up and Drop-Out Settings 24V AC 120V AC 12V DC 24V DC 48V DC 110V DC

Drop-out voltage is fixed at 95% of the adjusted Pick-Up Setting. Drop-out voltage is adjustable from 75 – 95% of the adjusted Pick-Up Setting. Time delay on drop-out fixed at 500 mS.

49

Accessories Table 49-193. Accessories, Over/Undervoltage Relays Description

Standard Pack

Catalog Number

8-Pin Socket Hold Down Spring

10 10

D3PA2 D65CHDS

Price U.S. $

Features ■ Monitors AC single-phase and

DC voltages ■ Wide range of user-adjustable pick- up and drop-out settings ■ Fixed time delay on drop-out of

500 mS ■ LED indicates output relay status ■ Compact plug-in case utilizing industry standard 8-pin socket Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . 1CD1

■ 10A DPDT output contacts

CA08102001E

For more information visit: www.eaton.com

Page 124

49-124

Control Relays & Timers Voltage Monitoring Relays July 2008

D65V Series, Adjustable Time Delay Over/Undervoltage Relays

Adjustable Time Delay for Over/Undervoltage Pick-Up Voltage Monitored Voltage Drop-Out Voltage T

Relay Output

T

On Off

Figure 49-165. Adjustable Time Delay Over/Undervoltage

Product Selection D65VAP & D65VAKP Series Over/Undervoltage Relays

Product Description The D65VAP & D65VAKP Over/Undervoltage Relays provide protection to equipment where either an over- or undercurrent condition is potentially damaging. They are designed to operate when the operating voltage reaches a preset value and drop out when the operating voltage drops to a level below the preset value.

49

The pick-up voltage setting is useradjustable from 85 – 115% of the nominal voltage rating. As standard, the D65VAP Series has a drop-out voltage setting fixed at 95% of the pick-up voltage setting. An adjustable drop-out setting of 75 – 95% of the pick-up setting is available on the D65VAKP Series. The relay energizes when the monitored voltage is above the pick-up setting. The relay de-energizes when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay, which is adjustable from 0.5 – 10 seconds. A fixed time delay of 500 mS is available with the D65VMP Series.

Table 49-194. Product Selection, D65VAP & D65VAKP Series, Over/Undervoltage Relays Nominal Voltage

Voltage Range Pick-Up

Drop-Out

Catalog Number

21 – 27V AC 102 – 138V AC

20 – 26V AC 97 – 131V AC

D65VAPT D65VAPA

10 – 14V DC 21 – 27V DC 41 – 55V DC 94 – 126V DC

9 – 13V DC 20 – 26V DC 39 – 53V DC 89 – 121V DC

D65VAPR1 D65VAPT1 D65VAPW1 D65VAPA1

21 – 27V AC 102 – 138V AC

16 – 26V AC 77 – 131V AC

D65VAKPT D65VAKPA

10 – 14V DC 21 – 27V DC 41 – 55V DC 94 – 126V DC

8 – 13V DC 16 – 26V DC 32 – 52V DC 71 – 121V DC

D65VAKPR1 D65VAKPT1 D65VAKPW1 D65VAKPA1

Price U.S. $

Adjustable Pick-Up, Fixed Drop-Out Settings 24V AC 120V AC 12V DC 24V DC 48V DC 110V DC

Adjustable Pick-Up and Drop-Out Settings 24V AC 120V AC 12V DC 24V DC 48V DC 110V DC

Drop-out voltage is fixed at 95% of the adjusted Pick-Up Setting. Drop-out voltage is adjustable from 75 – 95% of the adjusted Pick-Up Setting. Adjustable time delay on drop-out from 0.5 – 10 seconds.

Accessories Table 49-195. Accessories, Over/Undervoltage Relays Description

Standard Pack

Catalog Number

8-Pin Socket Hold Down Spring

10 10

D3PA2 D65CHDS

Price U.S. $

Features ■ Monitors AC single-phase and

DC voltages ■ Wide range of user-adjustable pick- up and drop-out settings ■ Adjustable time delay on drop-out of 0.5 – 10 seconds ■ LED indicates output relay status ■ Compact plug-in case utilizing industry standard 8-pin socket Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1

■ 10A DPDT output contacts

For more information visit: www.eaton.com

CA08102001E

Page 125

Control Relays & Timers Voltage Monitoring Relays

49-125

July 2008

D65V Series, Fixed and Adjustable Time Delay Over/Undervoltage Relays

Technical Data and Specifications

Application Description

Table 49-196. Technical Data, D65VMP, D65VMKP, D65VAP & D65VAKP Series, Over/Undervoltage Relays

Each relay can be used as either an overvoltage or an undervoltage relay, depending on the output contact used.

Description

Specifications

Voltage Tolerance

+25%/-50% of nominal voltage; AC voltages are 50/60 Hz; No supply (input) voltage is required Less than 3VA

Load (Burden) Voltage Settings: Pick-Up Drop-Out

Adjustable from 85 – 115% of nominal voltage Fixed at 95% of the pick-up setting for D65VMP and D65VAP Adjustable from 75 – 95% of the pick-up setting for D65VMKP and D65VAKP -20 to 131°F (-28 to 55°C)

Temperature Response Times: Operate Release

500 mS Fixed 500 mS for D65VMP and D65VMKP Adjustable 0.5 – 10 seconds for D65VAP and D65VAKP 10A Resistive @240V AC / 30V DC, 1/2 hp @ 240V AC (NO), 1/3 hp @ 240V AC (NC) 10,000,000 operations 100,000 operations Red Steady when relay is energized; Green when relay is off 10,000 volts for 20 microseconds Automatic Requires an 8-pin socket

Output Contacts Mechanical Life Electrical Life Indicator LED Transient Protection Reset Mounting

Schematics

4 5 3

6

2

7 1 8

(DC)+ L1

(DC)− L2

Overvoltage Relay Provides protection to equipment that cannot handle excess voltages. Uses a normally closed contact (NC). As long as the monitored voltage remains below the maximum voltage the equipment can withstand (Pick-Up Setting), the relay remains energized and the NC contact remains closed, keeping the load energized. If the operating voltage increases beyond the maximum rating of the equipment, the relay energizes and the NC contact opens, turning off the load. When the voltage falls below the Drop-Out Settings (hysteresis), the relay de-energizes and the NC contact re-closes, turning on the load.

Undervoltage Relay Provides protection to equipment that is required to operate above a certain minimum voltage. Uses a normally open contact (NO). As long as the monitored voltage is above the minimum value required (Pick-Up Setting), the relay will energize and the NO contact closes, turning on the load. If the voltage drops below the Drop-Out Setting (the minimum voltage required minus hysteresis), the relay will de-energize and the NO contact will re-open, turning off the load.

Monitored Voltage

49 Figure 49-166. Wiring for 8-Pin Socket

Dimensions

2.4 (60) D65VMKP & D65VAKP Only

1.7 (43)

2.9 (74)

3.5 (89)

Figure 49-167. D65V Series, Approximate Dimensions in Inches (mm)

CA08102001E

For more information visit: www.eaton.com

Page 126

49-126

Control Relays & Timers Voltage Monitoring Relays July 2008

D65V Series, Voltage Band Relays

Voltage Band Over Voltage Monitored Voltage Under Voltage

Relay Output

On

T

T

T

T

Off

Figure 49-168. Voltage Band Relays D65VW Series Voltage Band Relays

Product Selection Table 49-197. Product Selection, D65VWP & D65VWKP Series, Voltage Band Relays

Product Description The D65VWP & D65VWKP Series Voltage Band Relays provide protection to equipment that is required to operate within an upper and lower voltage limit. As long as the operating voltage remains within an over- and undervoltage range, the internal relay stays energized. If the operating voltage falls outside this range, the relay will drop out.

49

When nominal operating voltage is applied, the internal relay will energize (pick up). If the operating voltage falls outside the preset over trip point (adjustable 100 – 125% of nominal), or under trip point (adjustable 75 – 100% of nominal), for a period longer than the drop-out time delay, the relay will deenergize (drop out). When the voltage returns to normal (within the preset over- and undervoltage trip points), the unit automatically resets and the relay energizes. Choose between a unit with fixed drop-out time of 500 mS or one with an adjustable 0.5 – 10 seconds drop-out time.

Nominal Voltage

Voltage Range Over

Under

Catalog Number

24 – 30V AC 120 – 150V AC

18 – 24V AC 90 – 120V AC

D65VWPT D65VWPA

12 – 15V DC 24 – 30V DC 48 – 60V DC 110 – 137V DC

9 – 12V DC 18 – 24V DC 36 – 48V DC 83 – 110V DC

D65VWPR1 D65VWPT1 D65VWPW1 D65VWPA1

24 – 30V AC 120 – 150V AC

18 – 24V AC 90 – 120V AC

D65VWKPT D65VWKPA

12 – 15V DC 24 – 30V DC 48 – 60V DC 110 – 137V DC

9 – 12V DC 18 – 24V DC 36 – 48V DC 83 – 110V DC

D65VWKPR1 D65VWKPT1 D65VWKPW1 D65VWKPA1

Price U.S. $

Fixed Drop-Out Time Delay, 500 mS 24V AC 120V AC 12V DC 24V DC 48V DC 110V DC

Adjustable Drop-Out Time Delay (0.5 – 10 Seconds) 24V AC 120V AC 12V DC 24V DC 48V DC 110V DC

Accessories Table 49-198. Accessories, Voltage Band Relays Description

Standard Pack

Catalog Number

8-Pin Socket Hold Down Spring

10 10

D3PA2 D65CHDS

Price U.S. $

Features ■ Monitors AC single-phase and

DC voltages ■ Provides voltage band (window)

protection ■ Wide range of user-adjustable over- voltage and undervoltage settings ■ Fixed or adjustable time delay on drop-out ■ LED indicates output relay status ■ Compact plug-in case utilizing industry standard 8-pin octal socket ■ 10A DPDT output contacts

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com

CA08102001E

Page 127

Control Relays & Timers Voltage Monitoring Relays

49-127

July 2008

D65V Series, Voltage Band Relays

Technical Data and Specifications Table 49-199. Technical Data, D65VWP & D65VWPK Series, Voltage Band Relays Description

Specifications

Voltage Tolerance

+25%/-50% of nominal voltage; AC voltages are 50/60 Hz; No separate supply (input) voltage is required. Less than 3 VA

Load (Burden) Voltage Settings: Overvoltage Undervoltage Temperature Indicator LED Reset

100 – 125% of nominal voltage 75 – 100% of nominal voltage -20° to 131°F (28° to 55°C) Red steady when relay is energized; Green when relay is OFF Automatic. Contact Eaton for information on how to order a unit with Manual Reset.

Response Times: Operate Release

500 mS Fixed 500 mS (D65VWP Series) Adjustable 0.5 – 10 seconds (D65VWKP Series) 10A Resistive @ 240V AC / 30V DC, 1/2 hp @ 240V AC (NO), 1/3 hp @ 240V AC (NC)

Output Contacts Life: Mechanical Electrical Transient Protection

10,000,000 operations 100,000 operations 10,000 volts for 20 microseconds

Schematic

4 5 3

6

2

7 1 8

(DC)+ L1

(DC)− L2 Monitored Voltage

49

Figure 49-169. Wiring for 8-Pin Socket

Dimension

2.4 (60)

D65VWKP Only

1.7 (43)

2.9 (74)

3.5 (89)

Figure 49-170. D65V Series, Approximate Dimensions in Inches (mm)

CA08102001E

For more information visit: www.eaton.com

Page 128

49-128

Control Relays & Timers Voltage Monitoring Relays July 2008

VSR Series, Solid-State, Single-Phase

VSR Series, Solid-State, Single-Phase Voltage Sensing

Note: 12A RMS maximum inrush for 3 cycles. If inrush current is greater than 12A and relay is operated more than 30 times per minute, derating may be necessary. If surge current is 12A or less, no derating is necessary. If currents exceeding these ratings could occur, a series fuse having an I2t rating equal to 3A squared seconds is recommended.

■ Ambient Temperature Range:

-20° to 60°C Note: For operation in a higher ambient temperature, derating may be necessary. ■ Open Contact Leakage Current:

3 mA maximum ■ Closed Contact Voltage Drop:

3V AC maximum

Product Selection When Ordering Specify ■ Catalog Number of Basic Relay.

Catalog Number VSR Voltage Sensitive Relay

Table 49-200. Voltage Sensing Relays Description

Voltage Range

Catalog Number

Product Description

Undervoltage Relay

70 – 120V AC 200 – 280V AC

VSRUA VSRUB

The Catalog Number VSR voltage sensing relays are highly accurate, solidstate, AC voltage sensing devices available in both overvoltage and undervoltage types. They include built-in locking shaft potentiometers for voltage and differential adjustment. Relay circuit boards are conformal contact for environment-free operation. Input is transformer isolated from solid-state output contact. Mounting dimensions are the same as Catalog Number BF relays.

Overvoltage Relay

100 – 140V AC 200 – 280V AC

VSROA VSROB

Features

Price U.S. $

Operating Curves Undervoltage Relay

Overvoltage Relay

Solid-state NO contact closes when voltage exceeds upper limit set by voltage adjustment potentiometer. Contact remains closed until voltage drops below the value set with differential adjustment. Contact will not reclose until voltage once again exceeds upper limit.

Providing a minimum of 60V input is present, solid-state contact is NC. Differential adjustment sets upper limit where contact will open. After opening, contact will remain open until voltage drops below value set with voltage adjustment potentiometer.

■ Same base plate as Catalog Number

BF relay, mounts in same area

Relay Contact Status Dropping Voltage

Technical Data and Specifications Electrical Ratings ■ Operating Voltage Range:

70 – 140V AC, 200 – 280V AC 3 VA burden ■ Variable Differential Range: see curves at right ■ Repeatability: ±0.5V AC of setting ■ Solid-State Contacts: 2A continuous maximum inductive or resistive, 132V AC maximum

Relay Contact Status Rising Voltage CW

CCW

Voltage Adjustment (Pickup)

CCW

1 Volt Minimum Recommended Differential

CW

Differential Adjustment (Dropout)

Potentiometer Rotation 0 Volts Relay Contact Status Dropping Voltage Line Volts Minimum Maximum 200 Volts to 280 Volts 100 Volts to 140 Volts

49 accept 1 or 2 solid or stranded 14 AWG or smaller wires ■ Adjustment potentiometer with locking shafts, provides shockproof adjustment ■ Conformal coated printed circuit board, protects relay against shock, moisture, dirt and other environmental hazards ■ Built-in surge protection, protects internal solid-state contact from damage due to load and line transients

Line Volts Minimum Maximum 200 Volts to 280 Volts 70 Volts to 120 Volts

■ Captive, pressure clamp terminals, Relay Contact Status Rising Voltage CW

Differential Adjustment (Dropout)

CCW

3 Volts Minimum Recommended Differential

CW

CCW

Voltage Adjustment (Pickup)

60 Volts Potentiometer Rotation 0 Volts

Figure 49-171. Operating Curves

Note: Can initiate a Size 4 motor starter.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.eaton.com

CA08102001E

Page 129

Control Relays & Timers Voltage Monitoring Relays

49-129

July 2008

VSR Series, Solid-State, Single-Phase

Voltage Ranges Pickup Voltage (Variable from 70 to 120 Volts AC or 200 to 280 Volts AC)

Dropout Voltage (Variable Between 70 Volts AC and 1 Volt AC Less Than Diff. Adj. Pickup Voltage) Max. CCW

70 or 200 0

Diff. Adj. Max. CW 50 % Rotation Voltage Adj. Control

100

Diff. Adj. Max. CW

140 or 280 Line Voltage (VA-C) on Terminals 1 & 2

Line Voltage (VA-C) on Terminals 1 & 2

120 or 280 1 VA-C

Diff. Adj. Dropout Voltage Max. CCW (Variable Between 3 Volts AC More Than Pickup Voltage and Pickup Voltage 140 Volts AC) (Variable from 100 to 137 Volts AC or 200 Volts AC)

100 or 200 0

3 VA-C 50 100 % Rotation Voltage Adj. Control Overvoltage

Undervoltage

Figure 49-172. Relay Pick-Up and Drop-Out Voltage Ranges

Dimensions 0.16 (4.1)

1.63 (41.4) 0.81 (20.6) 0.17 (4.3) Dia. 3 Mtg. Slots

2.81 (71.4) 3.13 (79.5)

Lock Nut

Voltage Input: Terminals 1 and 2 Solid-State Output: Terminals 3 and 4

0.5 (12.7) 1 (25.4)

4.69 (119.1) Catalog Number VSR

Figure 49-173. Approximate Dimensions in Inches (mm)

49

CA08102001E

For more information visit: www.eaton.com

Page 130

49-130

Control Relays & Timers Alternating Relays July 2008

D85 Series

D85 Series, Alternating Relays

Each of the D85 Series alternating relays is available with an optional three-position selector switch, which allows the unit to alternate the two loads as normal, or lock the relay to one load or the other. By locking the alternating relay to one load, the other load can be removed for service without rewiring the first load for continuous operation. The selector switch has a low profile to prevent any accidental actuation.

Product Description Alternating relays are used in applications where the optimization of load usage is required by equalizing the run time of two loads. They are also used where additional capacity is required in case of excess load requirements. This alternating action is initiated by a control switch, such as a float switch, manual switch, timing relay, pressure switch or other isolated contact. Each time the initiating switch is opened, the output relay contacts will change state, thus alternating the two loads. Two LED indicators show the status of the output relay.

49

The D851 and D852 Series Relays are used with one control switch and are available in either SPDT or DPDT output configurations with or without a selector switch to lock in one sequence. The D852X Series Relays are available in DPDT Cross-Wired output configurations for use with one or two control switches (LEAD and LAG). The D853 Series is designed for use with three-switch applications (LEAD, LAG and STOP). The D853 Series combines a standard DPDT Cross-Wired alternating relay, contactor auxiliary contacts, and a control relay into one compact and economical product. This saves space and labor, while reducing the number of components needed. The D853 Series uses Sequence On – Simultaneous Off (S.O.S.O.) operation, where the two loads are energized sequentially, but remain on together until the STOP switch is opened. This device also protects against failure of the STOP and LEAD switches. If both switches fail, the two pump motors will be energized simultaneously when the LAG switch is closed.

industry standard sockets ■ 10A SPDT or DPDT output configurations ■ Optional low profile selector switch to lock in one sequence ■ 2 LEDs indicate relay status ■ D853 Series replaces separate components in duplex panel, saving space and reducing labor

Standards and Certifications

Features D85 Series Alternating Relays

■ Compact plug-in design utilizing

■ For duplex loads with Eaton socket

■ Works with 1-, 2-, or 3-switch applications

Product Selection Table 49-201. Product Selection, D85 Series Output Contacts

Control Voltage

Socket

Catalog Number

SPDT SPDT SPDT SPDT

12V AC 24V AC 120V AC 240V AC

8-Pin 8-Pin 8-Pin 8-Pin

D851NR D851NT D851NA D851NB

SPDT w/Selector Switch SPDT w/Selector Switch SPDT w/Selector Switch SPDT w/Selector Switch DPDT DPDT DPDT DPDT DPDT w/Selector Switch DPDT w/Selector Switch DPDT w/Selector Switch DPDT w/Selector Switch DPDT Cross-Wired DPDT Cross-Wired DPDT Cross-Wired DPDT Cross-Wired DPDT Cross-Wired w/Selector Switch DPDT Cross-Wired w/Selector Switch DPDT Cross-Wired w/Selector Switch DPDT Cross-Wired w/Selector Switch

12V AC 24V AC 120V AC 240V AC 12V AC 24V AC 120V AC 240V AC 12V AC 24V AC 120V AC 240V AC 12V AC 24V AC 120V AC 240V AC 12V AC 24V AC 120V AC 240V AC

8-Pin 8-Pin 8-Pin 8-Pin 11-Pin 11-Pin 11-Pin 11-Pin 11-Pin 11-Pin 11-Pin 11-Pin 8-Pin 8-Pin 8-Pin 8-Pin 8-Pin 8-Pin 8-Pin 8-Pin

D851LR D851LT D851LA D851LB D852NR D852NT D852NA D852NB D852LR D852LT D852LA D852LB D852XNR D852XNT D852XNA D852XNB D852XLR D852XLT D852XLA D852XLB

Price U.S. $

Contact Eaton for relays for 3-switch applications (Lead-Lag-Stop).

Accessories Table 49-202. Accessories, D85 Series Description

Standard Pack

Catalog Number

8-Pin Socket 11-Pin Socket Hold Down Spring

10 10 10

D3PA2 D3PA3-A2 D65CHDS

Price U.S. $

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com

CA08102001E