For the Cutler-Hammer D26MB and Eaton D26MB

Page 131

Control Relays & Timers Alternating Relays

49-131

July 2008

D85 Series

Technical Data and Specifications Table 49-203. Technical Data, D85 Series Description

Specifications

Voltage Tolerance Load (Burden) Output Contacts

+10%/-15% of control voltage at 50/60 Hz Less than 3 VA 10A Resistive @ 240V AC / 30V DC, 1/2 hp @ 120/240V AC (NO), 1/3 hp @ 120/240V AC (NC)

Life: Mechanical Electrical Temperature Transient Protection Indicator LEDs Optional Selector Switch Settings

10,000,000 operations 100,000 operations -20° to 150°F (-28° to 65°C) 10,000 volts for 20 microseconds 2 LEDs marked LOAD A and LOAD B ALTERNATE, LOCK LOAD A, LOCK LOAD B

Schematics Input Voltage L2

Input Voltage

L1

L1

L2

Control Switch 4 5 4

5

3

Lag

6

3

6

2 2

7 1

Load B

7 1 8

8 Lead Load A

Load A: Pin 2 Load B: Pin 8

Figure 49-174. Wiring for D851 Series Relays, SPDT

Input Voltage

L1

L2

Figure 49-176. Wiring for D852X Series Relays, DPDT Cross-Wired

Input Voltage L1

49

L2 Stop

Control Switch 4 5 4

5

6 7

3 2

8

Load A: Pins 3 or 11 Load B: Pins 1 or 9

Figure 49-175. Wiring for D852 Series Relays, DPDT

3

6

2

9 10 1 11

CA08102001E

Lag

7 1 8

Load B

Lead Load A

Figure 49-177. Wiring for D853 Series Relays, Three-Switch Applications

For more information visit: www.eaton.com

Page 132

Control Relays & Timers Alternating Relays

49-132

July 2008

D85 Series

Dimensions

2.4 (60)

2.9 (74)

1.7 (43)

3.1 (79)

Figure 49-178. D85 Series, Approximate Dimensions in Inches (mm)

Typical Installations SPDT and DPDT Alternating Relays In the OFF state (Standard Installation), the Control Switch is open, the Alternating Relay is in the LOAD A position, and both loads (M1 & M2) are off. When the Control Switch closes, it energizes the first load (M1). The red LED marked “LOAD A” glows. As long as the Control Switch remains closed, M1 remains energized. When the Control Switch opens, the first load (M1) is turned off and the Alternating Relay toggles to the LOAD B position. When the Control Switch closes again, it energizes the second load (M2). The red LED marked “LOAD B” glows. When the Control Switch opens, the second load (M2) is turned off, the Alternating Relay toggles back to the LOAD A position, and the process can be repeated again. On relays with

DPDT contacts, two pilot lights can be used for remote indication of LOAD A or LOAD B status. To eliminate any bounce condition of the Control Switch, the addition of a second switch (OFF) along with two auxiliary contacts is recommended as shown in the Anti-Bounce Installation.

L1 L1

L2 M2

L2

49

M2

SPDT

M1 M1 O/L

1 2 Control Switch

SPDT

M1 1

O/L 5

4

8

M2

Off

2

Control Switch

3

5

4

Standard Installation

8 3

Anti-Bounce Installation

Figure 49-179. Typical Installations for SPDT and DPDT Alternating Relays

For more information visit: www.eaton.com

CA08102001E

Page 133

Control Relays & Timers Alternating Relays

49-133

July 2008

D85 Series

DPDT Cross-Wired Alternating Relays In the OFF state, both the LEAD Control Switch and the LAG Control Switch are open, the Alternating Relay is in the LOAD A position, and both loads are off. When the LEAD Control Switch closes, it energizes the first load (M1). The red LED marked “LOAD A” glows. As long as the LEAD Control Switch remains closed, M1 remains energized. If the LAG Control Switch closes, it energizes the second load (M2). When the LAG Control Switch opens, the second load (M2) is turned off. When the LEAD Control Switch opens, the first load (M1) is turned off and the Alternating Relay toggles to the LOAD B position. When the LEAD Control Switch closes, it turns on the second load (M2). The red LED marked “LOAD B” glows. If the LAG Control Switch closes, it will energize the first load (M1). When the LAG Control Switch opens, the first load (M1) is turned off. When the LEAD Control

Switch opens, the second load (M2) is turned off, the Alternating Relay toggles back to the LOAD A position, and the process can be repeated again. To eliminate any bounce condition of the Control Switch, the addition of a second switch (OFF) along with two auxiliary contacts is recommended as shown in the Anti-Bounce Installation.

L2

L1 L1

L2

M2 M2 M1

Cross-Wired

M1

Lag

O/L

2 8

Cross-Wired

M1

Lag 2

Lead

O/L

1 7

M2

Off

Lead

8

1 7

3

6

3

Standard Installation

6

Anti-Bounce Installation

Figure 49-180. Typical Installations for DPDT Cross-Wired Alternating Relays

49

CA08102001E

For more information visit: www.eaton.com

Page 134

Control Relays & Timers Alternating Relays

49-134

July 2008

D85 Series

DPDT Cross-Wired for Three-Switch Applications In the OFF state, all three switches are open, the Alternating Relay is in the LOAD A position, and both loads are off. No action happens with the Alternating Relay or either load when the STOP Switch closes. When the LEAD Switch closes, Load #1 (M1) turns on. When the LAG Switch closes, Load #2 (M2) turns on. Both loads remain on as long as all three switches are closed.

L1 L2 L3 L1 L2

When the LAG Switch opens, Load #2 (M2) remains on because the STOP Switch is still closed. When the LEAD Switch opens, Load #1 (M1) remains on because the STOP Switch is still closed. When the STOP Switch opens, both Load #1 (M1) and Load #2 (M2) are turned off simultaneously. The Alternating Relay toggles to the LOAD B position. The entire cycle is then repeated, but with Load #2 (M2) energized first followed by Load #1 (M1).

If both the STOP Switch and LEAD Switch fail to close and turn on the first load, both loads will be turned on simultaneously when the LAG Switch is closed.

Lag Switch

M1 M1

This type of operation is known as “Sequence On – Simultaneously Off (S.O.S.O.)”, the two loads are energized sequentially, but remain on together until the STOP switch is opened.

M2

M1

7

M2

O/L

1 Stop Switch

M2

Motor 2

8 Lead Switch

Motor 1

M1

M2

O/L

2

4

L1

3

L2

6

L3

Figure 49-181. Typical Installations for DPDT Cross-Wired Relays for Three-Switch Applications

49

For more information visit: www.eaton.com

CA08102001E

Page 135

Control Relays & Timers Ground Fault Relays and Monitors

49-135

July 2008

D64R Series, Digital Ground Fault Relays

D64R Series, Digital Ground Fault Relays

Application Description D64R ground fault relays feature adjustable trip settings for both trip current and trip time. This allows the user to set the ground fault trip current just above the “charging” current of the system. This prevents nuisance tripping and provides meaningful protection of additional ground fault leakage currents. Every system has a “charging” current that can cause nuisance tripping if the trip current is set too low. The “charging” current is caused by the capacitance-to-ground effect of phase conductors in a system and will vary depending on:

D64RPB100 – Digital Ground Fault Relay with Built-In Current Sensor or Zero-Sequence CT

Contents Description Digital Ground Fault Relays Product Description . . . . . . Application Description . . . Features . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . Standards & Certifications Factory Options . . . . . . . . . Accessories. . . . . . . . . . . . . Product Selection . . . . . . . . Typical Connection Diagrams . . . . . . . . . . . . . Dimensions. . . . . . . . . . . . .

■ the overall length of the cables

Page 49-135 49-135 49-135 49-136 49-136 49-136 49-136 49-137 49-138 49-140

■ the types of loads ■ the quality of the insulation on the phase conductors ■ the surrounding equipment grounding, cable trays, junction boxes, etc. ■ the type and size of transformer A “rule-of-thumb” for systems 600V and lower: the “charging” current is 0.5A per 1000 kVA of transformer capacity.

Features Standard Models ■ Built-in current sensor (zero sequence CT) ■ Run and trip indicating LEDs ■ Built-in harmonic filtering for variable

Product Description The new D64R digital ground fault relays are microprocessor-based and replace the previous generation of analog-based devices. Microprocessor-based D64R GFRs combine more selectable features into a single model, which makes easier model selection and reduces spares inventory requirements. These devices are designed to provide reliable detection of ground fault conditions on three-phase AC resistance grounded or solidly grounded electrical distribution systems.

frequency drives or standard 50/60 Hz applications (see Table 49-204 for frequency response range) ■ DIN rail or panel mounting ■ Rugged epoxy encapsulated construction ■ Pull-apart terminal block connectors ■ Form “Z” (4 terminal) NO and NC output contacts, 5 Amps at 250V AC ■ Pulsed (trip) auto reset mode The pulsed (trip) auto reset mode is designed for applications where the output relay is operating a shunt trip device. The D64R relay resets automatically, three seconds after the ground fault current is interrupted by the tripping action of the circuit breaker. This opens the output contact wired to the shunt trip coil and prevents damage to the internal mechanism of the circuit breaker in the event that the operator tries to reset the circuit breaker. ■ Suitable for use on 600V systems, may be applied on higher voltages by using separate CTs with power conductors insulated for the system voltage CA08102001E

For more information visit: www.eaton.com

■ Built-in test circuitry, no external power or additional wiring is necessary, tests trip time and current settings ■ Communications port (standard RJ-10 jack) for connection to optional remote display (D64D1) and door mounted units (on D64RPB100 models only) ■ Failsafe selectable mode (on D64RPB100 models only) In the failsafe mode, the relay is energized when control voltage is applied and will trip when either: ■ a ground fault trip is detected or, ■ there is a loss of control power.

Service Protection Models ■ Service protection models require

C311CT 10,000:1 ratio CTs ■ Trip current range of 50 to 1200A ■ Green LED indicates “Power On” ■ Circuit breaker toggle position indicates “Normal” or “Tripped” condition ■ Form “C” (3 terminal) NO-NC output contacts, 3 Amps at 250V AC ■ Frequency response range of 40 to 200 Hz ■ Zone interlocking feature with green LED to indicate “Grading Input Active” and DIP switch array for zone grading backup delay and block signal override (on D64RPBH15 model only) ■ Test button to invoke test at 20A trip current, tests external CT, electronics and circuit breaker trip ■ Failsafe selectable mode (see above for description) ■ Inhibit selectable mode, this allows the relay to differentiate between normal ground fault trip levels and short circuit conditions The trip inhibit function is useful when the relay is being used to trip a contactor or motor starter on a solidly grounded system. Under a bolted fault condition, the relay would trip and could cause the contactor or motor starter to interrupt the high fault current with harmful results. By inhibiting the trip, the ground fault relay will not trip on bolted faults and will allow the upstream protective device to clear the fault instead. ■ Through-the-door or rear panel mounting

49

Page 136

49-136

Control Relays & Timers Ground Fault Relays and Monitors July 2008

D64R Series, Digital Ground Fault Relays

Technical Data and Specifications Table 49-204. Technical Data Specifications Catalog Number

D64RP18 D64RPB100

D64RPBH13 D64RPBH15

Control Power (Volts)

Frequency Response (Hz)

24 – 240V AC/DC Non-isolated 24 – 240V AC/DC Isolated

45 – 450 Hz 30 mA 6A

120V AC 120V AC

Trip Current Range Min. Max.

Trip Time Delay Range Min. Max.

Built-In Current Sensor

External Current Transformer Required Ratio

Test/Reset Provision Pushbutton on Cover

20 ms 500 ms

1.1"

Optional

500:1

No

Pushbutton

45 – 450 Hz 30 mA 9A 20 ms 5 Sec 3A 900A 30A 9000A

2.0"

Optional Required Required

500:1 500:5 5000:5

Yes

45 – 200 Hz 50A 40 – 200 Hz 50A

None None

Required Required

10000:1 Yes 10000:1 Yes

Pushbutton or RJ-11 Communications Port Pushbutton Pushbutton

1200A 35 ms 1 Sec 1200A 35 ms 1 Sec

Remote

With Zone interlocking feature.

Standards and Certifications

Accessories

■ UL 1053 ❑ Ground Fault Sensing and Relaying Equipment, Class 1

(UL File # E195341) ■ CSA C22.2 No. 144-M91 ❑ Ground Fault Circuit Interrupters (CSA File # 700103)

C311CT9

■ CE Mark, Declaration of Conformity

Zero Sequence Current Transformers

■ IEC 60755 ❑ General Requirements for residual current operated protective devices ■ EN 50081-1 ❑ Electromagnetic compatibility (radiated emission), “household” directive D64R ground fault relays are UL listed as Class 1 devices designed to protect electrical equipment against extensive damage from arcing ground faults.

Factory Options ■ Other ranges of trip currents and times

49

■ Fixed trip current and times ■ Other control voltages ■ Custom packaging for volume OEM requirements ■ Separate outputs for alarming vs trip ■ Relays for neutral grounding resistance monitoring

■ A complete size range of zero sequence CTs designed specifically for use with D64R relays provide excellent coupling to the monitored circuit. This means accurate ground fault leakage current detection over the full setting range of the relay with no saturation. ■ Built-in back-to-back zeners across the output terminals of all 500:1 and 10,000:1 CTs provide personnel safety should the secondary circuit be opened. ■ Rectangular split core CTs make retro-fitting easy. ■ All CTs are epoxy potted, panel mounted and come with either secondary screw terminals or threaded studs. ■ The core is very high grade silicon iron to give superior coupling characteristics and to withstand high shock and vibration. ■ All CTs are 600 Volt class. They may be used on higher voltage circuits provided that power conductors are insulated for the system voltage.

■ Relays for ground fault detection on DC power systems

Table 49-205. Zero Sequence Current Transformers for D64RP18 & D64RPB100 Relays

■ Other sizes of current transformers

Description/Window Size

Ratio 500:1 CTs Catalog Number

Price U.S. $

Toroidal Zero Sequence CT 1.1 inch (28 mm) 1.8 inch (46 mm) 2.5 inch (65 mm) 3.5 inch (90 mm) 5.7 inch (144 mm) 9.5 inch (240 mm)

C311CT8 C311CT1 C311CT9 C311CT2 C311CT5 C311CT6

Split Core (Rectangular/Square) Zero Sequence CT 5.9 x 6.7 inch (150 x 170 mm) 4.0 x 13.8 inch (100 x 350 mm) 11.8 x 11.8 inch (300 x 300 mm)

C311CT3 C311CT4 C311CT7

The maximum allowable continuous current through CTs is 1000A. D64RP18 relays use 500:1 ratio CTs if needed.

Sample D64R Ground Fault Relay in Custom Packaging for OEM

D64RPB100 relays can use 500:1 ratio CTs when needed for 30 mA – 9A, 500:5 ratio for 3A – 900A and 5000:5 ratio for 30A – 9000A trip current ranges. For 500:5 or 5000:5 ratio CTs, select any commercially available 5 Amp secondary CT with the same ratio.

Discount Symbol. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1CD1 For more information visit: www.eaton.com

CA08102001E

Page 137

Control Relays & Timers Ground Fault Relays and Monitors

49-137

July 2008

D64R Series, Digital Ground Fault Relays Table 49-206. Zero Sequence Current Transformers for D64RPBH13 and D64RPBH15 Relays Description

Ratio 10,000:1 CTs Catalog Number

Price U.S. $

■ The Numerical LCD window displays actual ground fault current in Amps. When a 5000:5 ratio interposing CT is used, all displayed values are to be interpreted as kAmps rather than Amps.

Toroidal Zero Sequence CT Window, 2.5 inch (65 mm) 5.7 inch (144 mm) 9.5 inch (240 mm)

C311CT11 C311CT12 C311CT13

The maximum allowable continuous current through 10,000:1 ratio CTs is 10,000A.

D64D1 Digital Display Unit

Table 49-207. Remote Display Unit for D64RPB100 Description

Catalog Number

Price U.S. $

Remote Digital Display D64D1 with Numerical LCD, RUN & TRIP LEDs, TEST, RESET and VERIFY Pushbuttons: C/W 3 ft. (1m) of cable

Product Selection When Ordering Specify ■ Catalog Number of relay from tables ■ Catalog Number of zero sequence current transformers, if or when required, remote digital display or remote indicator units

Standard Models

D64RP18 without Plug-In D64D1

The D64D1 digital display unit is connected to the D64RPB100 by up to 30 feet (10m) of standard 4-wire telephone type cable. It is supplied with door mounting hardware. It provides the following remote indications and functions:

D64RPB100 Full-Featured Ground Fault Relay

Table 49-208. Ground Fault Relay with Built-In Current Sensor Control Power

Catalog Number

24 – 240V AC/DC

24 – 240V AC/DC

Price U.S. $

Trip Current Range

Current Transformer Selection

D64RP18

30 mA – 6A

Built-in 1.1” CT. If external CT is required for specific application, select 500:1 ratio CT.

D64RPB100

30 mA – 9A

Built-in 2.0” CT. If external CT is required for specific application, select 500:1 ratio CT

■ Continuous reading of actual ground fault current, employing auto ranging ■ Display of the pre-trip ground fault current, after a trip has occurred (flashing display) ■ Display of the trip current setting, after a Test Trip has been activated ■ Green RUN LED, Red TRIP LED ■ TEST and RESET pushbuttons. The RESET button must be held pressed before the TEST is pressed to invoke the test procedure. The function of this button can be enabled/disabled by inserting the interconnecting cable from the D64RPB100 relay into one of two sockets, TEST ON or TEST OFF, on the right side of the display. ■ Pushing VERIFY pushbutton shows if D64RPB100 tripped due to a ground fault prior to loss of its control voltage, red TRIP LED lights, or if there was no ground fault trip, green RUN LED lights. This indication will remain available for at least ten hours.

3A – 900A

Select 500:5 ratio CT

30A – 9000A

Select 5000:5 ratio CT

Maximum allowable continuous current through built-in CT is 100 Amps. Maximum allowable continuous current through built-in CT is 200 Amps. For 500:1 ratio CTs, select from Table 49-205. For 500:5 or 5000:5 ratio CTs, select any commercially available 5 Amp secondary CT with the same ratio.

Service Protection Models

D64RPBH15 Ground Fault Relay with Zone Interlocking

Table 49-209. Ground Fault Relay Control Power

Catalog Number

120V AC 120V AC

Price U.S. $

Zone Interlocking Feature

Trip Current Range

Current Transformer Selection

D64RPBH13

No

50A – 1200A

Select 10,000:1 ratio CT -

D64RPBH15

Yes

50A – 1200A

Select 10,000:1 ratio CT -

- For 10,000:1 ratio CTs, select from Table 49-206.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 CA08102001E

For more information visit: www.eaton.com

49

Page 138

49-138

Control Relays & Timers Ground Fault Relays and Monitors July 2008

D64R Series, Digital Ground Fault Relays

Typical Connection Diagrams Power Source

Power Source GROUNDED SYSTEMS – 1-Phase 2-Wire – 1-Phase 3-Wire – 3-Phase 3-Wire – 3-Phase 4-Wire

GROUNDED SYSTEMS – 1-Phase 2-Wire – – 3-Phase 3-Wire – 3-Phase 4-Wire

Current Carrying Neutral, When Used Trip R

O/L

Current Carrying Neutral, When Used

1M

R

STOP

O/L 1M

1M

1M

Reset “Double Click for Test” T

Chassis Close to D64RPB100

GF Trip Range 30 mA to 9A. Remote Test/Reset

1M

1M

O/L

O/L

Figure 49-182. Typical Field Connection of D64RP18 Using Built-In Current Transformer

Figure 49-184. Typical Field Connection of D64RPB100 Using Built-In Current Transformer and Remote Test/Reset Power Source

Power Source

Current Carrying Neutral, When Used

49

ST

Current Carrying Neutral, When Used ST

Chassis Close to D64RPB100 “Double Click for Test” T (Pulsed Trip-Auto Reset)

IN TE

GF Trip Range 3A to 900A

50

RP

OS

IN

G

0:1

LOAD

50

0:5

C SE 311 RI CT ES

GROUNDED SYSTEMS – 1-Phase 2-Wire – – 3-Phase 3-Wire – 3-Phase 4-Wire

GROUNDED SYSTEMS – 1-Phase 2-Wire – 1-Phase 3-Wire – 3-Phase 3-Wire – 3-Phase 4-Wire

Figure 49-183. Typical Field Connection of D64RP18 with External 500:1 Current Transformer and Pulsed Trip-Auto Reset

LOAD

Figure 49-185. Typical Field Connection of D64RPB100 with Interposing 500:5 Current Transformer, Pulsed Trip-Auto Reset for Shunt Trip Breaker

For more information visit: www.eaton.com

CA08102001E

Page 139

Control Relays & Timers Ground Fault Relays and Monitors

49-139

July 2008

D64R Series, Digital Ground Fault Relays

GROUNDED SYSTEMS – 1-Phase 2-Wire – 3-Phase 3-Wire – 1-Phase 3-Wire – 3-Phase 4-Wire

Power Source

GROUNDED SYSTEMS – 1-Phase 2-Wire

Current Carrying Neutral, When Used Power Source

– 3-Phase 3-Wire – 3-Phase 4-Wire

ST

Current Carrying Neutral, When Used

CB Coil Clearing Contact

C311CT Current Transformer

ST

Chassis Close to D64RPB100

50 0:1 C3 11 C

TS ER IES

Range: 30 mA to 9A

LOAD LOAD

To Upstream Zone

Figure 49-186. Typical Field Connection of D64RPB100 with External 500:1 Current Transformer (C311CT Series) Pulsed Trip-Auto Reset for Shunt Trip Breaker

GROUNDED SYSTEMS – 1-Phase 2-Wire – 1-Phase 3-Wire – 3-Phase 3-Wire – 3-Phase 4-Wire

CB Coil Clearing Contact

Figure 49-188. D64RPBH15 Typical Field Connection

Current Carrying Neutral, When Used Power

49

C311CT Current Transformer

ST

LOAD

Figure 49-187. D64RPBH13 Typical Field Connections CA08102001E

From Downstream Zone

For more information visit: www.eaton.com

Page 140

49-140

Control Relays & Timers Ground Fault Relays and Monitors July 2008

D64R Series, Digital Ground Fault Relays

Dimensions 2.76 (70)

1.77 (45) 1.38 (35)

Mounting Hole 0.22 (5.5) Dia. 1.10 (28) Dia.

2.76 2.36 (70) (60)

1.38 (35)

35 mm DIN Rail

3.58 (91)

DIN Rail Release

4.43 (112.5)

1.38 (35)

Clip

1.26 (32)

Rear Panel Mounting DIN Rail or 2 Screw

Right Hand Side View

Figure 49-189. D64RP18, Approximate Dimensions in Inches (mm) 2.00 (50.8) Dia.

0.82 (21)

Mounting Hole 0.22 (5.5) Dia.

3.94 (100)

1.97 (50) 3.94 (100)

4.02 (102) 2.36 1.38 (60) (35)

DIN Rail Release

0.20 (5) 0.30 (7.5)

3.35 (85)

35 mm DIN Rail

2.76 (70)

2.17 (55)

49

1.77 (45)

3.94 (100) Bottom Side View

Rear Panel Mounting DIN Rail or 2 Screw

Figure 49-190. D64RPB100, Approximate Dimensions in Inches (mm) 0.20 (5) 0.30 (7.5)

3.35 (85)

0.73 (18.4)

2.36 (60) 1.38 (35)

DIN Rail Release

3.94 (100)

4.92 (125)

0.30 (7.5)

3.15 (80)

0.16 (4)

2.83 (72) Door Cutout

Mounting Hole 0.158 (4) Dia.

4.01 (102) Door Cutout

3.94 (100)

4.92 (125)

4.33 (110) 35 mm DIN Rail

Mounting Hole 0.22 (5.5) Dia.

2.76 (70)

0.59 (15)

Rear Panel Mounting DIN Rail or 2 Screw

3.94 (100) 4.14 (105) Right Side View

0.30 (7.5)

3.74 (95) 0.16 (4) Through-the-Door Mounting

Figure 49-191. D64RPBH13 and D64RPBH15, Approximate Dimensions in Inches (mm) For more information visit: www.eaton.com

CA08102001E