Page 141
Control Relays & Timers Ground Fault Relays and Monitors
49-141
July 2008
D64R Series, Digital Ground Fault Relays
1.50 (38)
2.68 (68) 0.83 (21)
1.38 (35)
0.94 (24) 0.31 (8)
3.74 (95)
M5 3.27 (83)
2.72 (69) Panel Cutout
1.02 (26)
M5
3.74 (95)
3.27 (83) Panel Cutout
3.27 (83) 1.82 (46.2)
1.46 (37)
0.41 (10.5)
3.19 (81)
Right Side View
Rear View
Through-the-Panel Mounting
Figure 49-192. D64D1 and D64D2, Approximate Dimensions in Inches (mm) Table 49-210. C311CT Series Dimensions Catalog Number
Figure
Approximate Dimensions in Inches (mm) Wide A
High B
Deep C
Mounting D
E
F
G
H
C311CT1 C311CT2 C311CT3 C311CT4
A B C C
3.35 (85) 7.30 (185) 13.58 (345) 20.87 (530)
3.35 (85) 5.50 (140) 8.75 (222) 7.87 (200)
1.57 (40) 1.20 (30) 1.57 (40) 1.57 (40)
0.98 (25) 6.42 (163) 12.80 (325) 20.08 (510)
0.39 (10) 0.59 (15) 0.59 (15) 0.59 (15)
1.81 (46) 3.54 (90) 6.70 (170) 13.78 (350), - 5.90 (150) 3.94 (100), 0.89 (22.5) 0.89 (22.5) 0.89 (22.5)
C311CT5 C311CT6 C311CT8 C311CT9
B B A B
10.12 (257) 13.86 (352) 2.17 (55) 6.68 (167)
8.27 (210) 11.89 (302) 2.56 (65) 4.84 (123)
1.46 (37) 1.46 (37) 2.20 (56) 1.18 (30)
9.33 (237) 13.07 (332) 0.98 (25) 5.78 (147)
0.59 (15) 0.59 (15) 0.39 (10) 0.59 (15)
5.70 (145) 9.45 (240) 1.10 (28) 2.56 (65), - - - 0.89 (22.5) 0.89 (22.5), 0.89 (22.5)
C311CT11 C311CT12 C311CT13
B B B
6.68 (167) 10.12 (257) 13.86 (352)
4.84 (123) 8.27 (210) 11.89 (302)
1.18 (30) 1.85 (47) 1.85 (47)
5.78 (147) 9.33 (237) 13.07 (332)
0.59 (15) 0.59 (15) 0.59 (15)
2.56 (65) 5.70 (145) 9.45 (240), - - 0.89 (22.5) 0.89 (22.5) 0.89 (22.5)
Threaded Studs M4 1 mm
F
F
B
A
C E
B
A
F
C
E
B
A
D
D Figure A
Figure B Note: All Mounting Holes Are 0.25 (6.4) Dia.
Figure 49-193. C311CT Series Approximate Dimensions in Inches (mm)
CA08102001E
E
G
H C H
D
49
Split (If Split Core)
For more information visit: www.eaton.com
Figure C
Page 142
49-142
Control Relays & Timers Ground Fault Relays and Monitors July 2008
D64L Series, Digital Ground Fault Monitors
D64L Series, Ground Fault Monitors
D64L
■ Adjustable alarm setting 20% – 80%
■ 30A 600V screw terminals, 12 AWG of leakage current limit. ■ Adjustable trip setting 20% – 80% of leakage current limit. ■ 70 mS response time for alarm and trip level. Resample time, 2 seconds. ■ Minimum alarm signal duration, 70 mS. ■ 110/120V or 220/240V 50/60 Hz control power, 4 VA. ■ Isolated voltage free Form Z NO and NC contacts on both alarm and trip relays, 5A at 250V AC.
capacity, for phase and ground connections. ■ 10A 300V screw clamp terminals, 12 AWG capacity for relay outputs and control supply. ■ CSA certified. ■ 35 mm DIN rail or two screw mounting.
Suggested Fuse Block and Fuses ■ DIN Rail Mounting ❑ 1 – C350BD3C61 600V 30A 3-pole fuse block ❑ 3 – Class CC 600V 5A fuses
Product Description Type D64L ground fault monitors are designed to monitor ungrounded supplies on 3-phase AC power systems up to 600V. If an insulation fault develops anywhere on the system between the source and the load, the D64L will detect it and give an alarm or trip, depending on the adjustable field settings selected. The D64L is ideally suited for systems supplied from the secondary of either an ungrounded delta or an ungrounded wye connected transformer. Because D64L has high immunity from the effects of voltage transients and cable capacitance, it may be applied in automotive, sub-sea, mobile lighting, portable generators, sensitive equipment and other installations where ungrounded systems are used extensively.
49
The user is able to individually set the alarm level and the trip level from 20% – 80% of the maximum leakage current limit of the D64L selected. Any leakage current above the alarm level will activate the alarm relay and light the alarm LED. Should the leakage current rise above the trip level, the trip relay and trip LED will activate.
Product Selection When Ordering Specify ■ Catalog Number of Ground Fault Monitor. ■ Catalog Number of Fuse Block and Fuses as required.
Table 49-211. Fuse Block and Fuses Mtg. Fuse Fuse Type Holder Type Rating DIN Rail
600V 30A 3-Pole
Table 49-212. Line Insulation Monitors
Catalog Number
Price U.S. $
Class CC WMR633G 600V 5A
Line Voltage Range 50/60 Hz
Control Power
Catalog Number
380 – 600V
110/120V 50/60 Hz
D64L2A
220/240V 50/60 Hz
D64L2B
Price U.S. $
Wiring Diagram and Dimensions 480V Transformer Secondary
Load ST Alarm Current 20%
3-Pole HRC Fusing Suggested Test Circuit 1-Pole Deadfront Fuseholder with 0.5A HRC Fuse Resistor – Refer to Instruction Manual
Trip Current
80% 20%
80%
L1 L2 L3 120 V AC
G Trip
L1 L2 L3
Alarm
1 2 3 4 5 6 7 8 9 10
Power Trip Alarm Ok
NO Momentary Contact Pushbutton Rated 600 Volts
Reset
D64L2
120V AC Alarm
Separate Connection to Equipment Ground Trip
Features
Figure 49-194. Connection Diagram
■ Adjustable leakage current limit set- ting (20 mA, 35 mA or 50 mA). Factory set at 20 mA. ■ Built-in RESET button on all models. ■ Selectable failsafe/non-failsafe operation. ■ Auto reset after alarm condition. ■ Selectable auto/manual reset after trip. ■ Three LEDs for POWER ON, ALARM and TRIP. ■ Three LEDs to indicate which phase is faulted.
5.31 (135)
2.36 (60)
3.94 (100)
3.00 (76)
6.14 (156)
Figure 49-195. Approximate Dimensions in Inches (mm)
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.eaton.com