Installing Your PCM-11 Outputs
Installing Your PCM-11 The PCM-11 Motion Program Controller attaches to the front of any FX Amplifier with two locking arms. All electrical connections (except I/O) are made via the 48 pin connector. The PCM-11 is equipped with 8 input lines and 4 output lines, doubling the I/O capability of the standard FX drive. All inputs and outputs are optically isolated for +10.5 to +30 vdc operation. Each input and output line has 2 screw terminals associated with it to provide for either current sinking or current sourcing operation. 18 to 24 gauge wire must be used for I/O wiring. The use of larger gauge wire will cause the I/O terminals to prematurely fatigue.
The first 8 pairs of terminals (numbered 13 - 20) are inputs and the last 4 pairs of terminals (numbered 21 - 24) are outputs. The outputs are capable of sinking or sourcing 200 mA. You must limit the output current to less than or equal to 200 mA per line. See Figure 3 for I/O connection examples.
Inputs Inputs require an external voltage/current source for operation. This voltage source must be in a range of 10.5 to 30 VDC. The (-) lead of the external power supply must be connected to enclosure or safety ground.
Outputs Outputs are similar to inputs in that they can be connected to either sinking or sourcing type loads. Outputs require an external isolated supply voltage, usually the same supply as the inputs. Each output can sink or source 0.2 amps DC. The (-) lead of the external power supply must be connected to enclosure or safety ground. If inductive loads such as DC relay coils are connected to the outputs, a diode supression must be installed in parallel with the load coil with its cathode towards the positive end of the external power.
5
Page 12
PCM-11 Application Module Operator's Manual
Figure 3 PCM-11 Connection to an FX
EXAMPLE A: SOURCING INPUT
EXTERNAL POWER SUPPLY(10.5 to 30)VDC
| *| input switcn Ie
| EXAMPLE B: SINKING INPUT | | |
EXTERNAL POWER SUPPLY(10.5 to 30)VDC
EXAMPLE A:
SOURCING OUTPUT
EXTERNAL POWER SUPPLY(10.5 to 30)VDC
* @ EXAMPLE B:
| EXTERNAL POWER | SUPPLY(10.5 to 30)VDC LOAD |
]
SINKING OUTPUT
EXAMPLE C:
EXTERNAL POWER | SUPPLY(10.5 to 30)VDC | nw
Coo surttessat |< . DIODE SUPPRESSOR oe
PCM MODULE UTPUTS
INPUTSS
OUTPUTS<
SINKING OUTPUT WITH INDUCTIVE LOAD
INPUTS/O
13> ap isp 16> 7p is> is > 2>
ISS)
48 PIN CONNECTOR
2<q 224 23<q 244
GKYK OG GV HOSP DOS SVG PSV GP© PGS PSOg ggg
PCM - -11-1
Page 13
PCM-11 Features Axis ID Description
PCM-11 Features Each of the following PCM-11 features must be set up before you can use them in a program. The appropriate menu for each feature can be found under the PCX menu whose title follows the feature. Individual setup information for each feature is covered in this chapter.
•
Axis ID Description (Drive Setup, Drive Configuration, Parameters Menu)
•
Global External Input Time Limit (Drive Setup, Drive Configuration, Limits Menu)
•
Internal Input Lines (Drive Setup, Drive Configuration, Input Functions Menu)
•
Internal Output Lines (Drive Setup, Drive Configuration, Output Functions Menu)
•
Programmable Limit Switch Operations (Drive Setup, Drive Configuration, Programmable Limit Switches Menu)
•
User Registers (Drive Setup, Define Motion, Programming, User Registers Menu)
•
Equations (and Math Operations) (Drive Setup, Define Motion, Programming, Equations Menu)
•
User Messages (Drive Setup, Define Motion, Programming, User Messages)
Axis ID Description The following applies to all PCX entries: If you make an entry and press the up or down arrow keys instead of the <Enter> key, PCX will ignore your entry and restore the existing data to the screen.
This function allows you to enter a unique, 32 character, alphanumeric description for each axis in your system that will be displayed at the top of each PCX screen. The descriptions allow you to quickly identify an axis by it’s function in a multi-axis system. The axis description will also be displayed to the right of the axis ID on the “Select Drive Screen” when more than one FX Drive is communicating with PCX.
Axis ID Setup The Axis ID Description is entered in Drive Setup, Drive Configuration, Parameters. Move the cursor to the Axis ID Description line in the Parameters Menu and type the description for that axis. After you have typed the description, press the <Enter> key to transmit the information to the drive. Because the Axis ID description is stored in the Application Module’s non-volatile memory, the module will retain its Axis ID Description information when moved to another FX Drive.
7
Page 14
PCM-11 Application Module Operator's Manual
Figure 4 Drive Parameters Screen
Global External Input Time Limit An optional time limit has been added to the Wait for Input Function. This new function will prevent program execution from waiting indefinitely at a Wait for Input program statement when a required sensor input is not received. The time limit, entered in seconds, will monitor any instance of Wait for Input, Wait for Single Input, or Wait for Input Pattern Match and move to the next step in the program if an input is not received before the time limit expires. This time limit function, if used, times and monitors all external input lines and all program functions that use any form of Wait for External Input. The time limit resets after each wait statement and applies to all lines in use. If your application requires that individual input lines have different time limits, a separate program sub-section can be written to monitor the critical lines with time limits that are specific to that part of the program. (See the description of the Real-Time Clock (RT) under Direct Drive Commands of this manual).
Global External Input Time Limit Setup Select Drive Configuration, Limits Menu. Move the cursor to the “Global External Input Time Limit” line and enter the time limit needed in seconds. Minimum time monitored will be .001 seconds; maximum time is 2,147,483.647 seconds (or 24.8 days). After making the entry, press the <enter> key.
8
Page 15
PCM-11 Features Internal Input and Output Lines
Figure 5 Global External Input Time Limit Setup
Internal Input and Output Lines This feature enables the drive to signal itself without using hardware input or output lines. For example; If your application requires the drive to be flagged that a particular step has been completed while a program is running, you can simply assign an internal output to flag an internal input. There are 16 internal input and 16 internal output lines available, giving you access to a total of 32 input (16 hardware and 16 internal) and 24 output (8 hardware and 16 internal) lines per FX Drive with a PCM-11. The internal input lines support Jump and Wait statement conditions. The Jump and Wait inputs can also be overlapped between the hardware lines and the internal lines. For example, if input function #28 (Jumps/Wait Inputs) is assigned to hardware line 17, and 8 input lines are selected, then the Inputs would be assigned to hardware lines 17-20 along with internal input lines I1-I4. Half would be assigned to hardware inputs and half would be assigned to internal inputs (see Figure 6 and 7 ). Figure 6 Hardware (External) Input Line Assignments
9
Page 16
PCM-11 Application Module Operator's Manual
Press the F2 key to display the internal input lines. Figure 7 Software (Internal) Input Line Assignments
The maximum number of PGO lines is 16; the maximum number of Jump/Wait Input lines is 8.
Similarly, the internal output lines support programmable outputs (PGOs). The PGOs can be overlapped between the hardware output lines and the internal output lines. For example, if output #12 (PGOs) is assigned to hardware line 9, and sixteen output lines are selected, then the PGOs would be assigned to hardware output lines 9,10,11, and 12, along with internal output lines 1 through 12.
Figure 8 Internal Output Line Assignments
Press the F2 key to display the internal output lines.
10
Page 17
PCM-11 Features Internal Input and Output Lines
Figure 9 Internal Output Line Assignments
The “internal” lines are assigned just as normal hardware lines with the following differences: Internal Inputs are designated by I1 through I16 (i.e., letter “I”, not numeral 1). Internal Outputs are designated by O1 through O16 (i.e., letter “O”, not numeral Ø). All output lines, both hardware lines and internal lines, can be assigned to connect to input lines on the Input Function Screen. This allows you to attach a hardware or internal output line directly to an input line (hardware or internal) to allow outputs to trigger inputs without the need for external wiring. If you assign an internal or hardware output line to trigger a hardware input line, the LED on the FX Drive or PCM-11 associated with that line will not glow when the logic makes the line active. Only externally supplied current draw will cause the LED to light up.
Internal Input/Output Setup To equip a hardware or internal output line that internally enables either a hardware or internal input line, select Drive Setup, Drive Configuration, Input Functions and move the cursor to the end of the menu to the section labeled “Output Connections”. If you want to assign a hardware or internal output line to an input line (either hardware or internal), move the cursor to the output line you wish to use and enter the number of the input line (1 - 8, 13 - 20 or I1 - I16) that you want the output line to connect to. The input line that you designate will be activated any time the output line is turned on regardless of the function that turns on the output line.
11
Page 18
PCM-11 Application Module Operator's Manual
Figure 10 Output Connection to an Input Line
Input Functions - 1: TRAVERSE AXIS - MACHINE 1 - - - 10:41:56 Ext. Input Assignments Functio Line Polarity, 14: (9), 78-Clear Program Error 0 - 24: (01), OUTPUT CONNECTIONS 34: (3)-Dutput Line 9 i - 44: (10)- 10 0 - 5¢: (11)- 11, - __ 60 - 64: (12)- 12, - 9 - 74: (21)-Output Line 21, - - - 0 - Bd: (22)- 22, - _ 0 - 134: (23)- 23, _ 98 144: (24)- 24, - _ 9 154: (01)-Int. Output 1 - - _ Z| 164: (02)- 2 - - _- 0 - 174: (03)- 3 - - - 8 - 1B4: (04)- oC Ss & - E) cs 194: (05)- 5, -- oO -
204: (06)- 6 QO - rr
Press F2 for internal input lines Status: External Control Velocity: 0 RPM
Position: 0 ST
Range: OCunused) to 8, 13 to 20 Enc Pos: 2 counts Press T or J to choose; Enter to select/change; Esc to exit
In Figure 10, hardware output line #9 is internally connected to input line #1 and internal output line #01 is connected to hardware input line #2. On the left side of the screen under “Input Assignments” the output number isin parentheses to the right of the input it has been assigned to.
You can monitor function assignments to Internal Input and Output Lines by pressing the < F2> key. A second line listing will be displayed on the left side of the screen, showing all the assignments for the internal lines. If an input or output line, either hardware or internal, has so many functions assigned to it that the listing scrolls off the PCX screen in the upper left corner, use the <ALT> key plus the-> or <- arrow keys to scroll through all of the assignments.
Programmable Limit Switches (PLS)
Programmable Limit Switch (PLS) patterns can be updated at 16 specific motor positions using the existing Programmable Output Lines (PGOs) and user units to define motor position. The pattern you set is the way the lines will look after the motor enters that position range.
A PLS pattern consists of a specific combination of On, Off, and Don’t Change line conditions of the programmable output lines. Sixteen different patterns may be entered to occur at the intervals you specify. Patterns can be updated at 16 different motor positions. There are 3° (6561) possible patterns available. You may use a maximum of 16 output lines.
The default mask for programmable limit switch operation (all X’s, meaning Don’t Change the existing line condition) disables the PLS function. As the X's are changed to 1’s or @’s, the associated PLS pattern will become active at that motor position.
12
Page 19
PCM-11 Features Programmable Limit Switches (PLS)
Motor position is referenced by user units. Once PLS patterns are set up the motion range of the motor is divided into sections. When the specified section is reached (from either direction), the output pattern associated with that range will activate the assigned output lines and program execution will continue. Lines set to“X” will remain unchanged. The PLS pattern remains in that state until the next range is reached by virtue of the changing motor position. However, you may set a time delay to turn off a particular pattern.
When a non-zero pulse width is entered for a given PLS pattern, the pattern will remain in that state for that amount of time. After the pulse width time has expired, the lines are set to all @’s meaning “OFF”. Lines masked with “X" remain unchanged.
If another PLS range is reached before the pulse width time expires, the new pattern is set immediately and the time delay is ignored.
\cnos
The PLS functions remain active once they are enabled. There is no way to remotely enable or disable this function after patterns have been entered by PCX. The only way to disable the PLS function is through the Initialize Memory option: PLS Data.
PLS Setup
Figure 11 Programmable Limit Switches
Before setting up a PLS pattern you will need to assign one or more output lines (either hardware or internal) as programmable outputs. This is done in the Drive Setup, Drive Configuration, Output Functions menu. Select Output Function 12, Programmable Outputs. After you enter the line number of the hardware or internal Output Line that is the first of your programmable output lines, enter the number (quantity) of lines you want to use (maximum 16 lines) and press < Enter>.
Toset a Programmable Limit Switch Pattern, select Drive Setup, Drive Configuration, Programmable Limit Switches. The screen you see will look like Figure 11.
Progrannable Limit Switches, 1: TRAVERSE AXIS - MACHINE 1 - - 15:53:41
Position Pattern(9. .08) Pulse Width 0 | 9.688) 6000000011111111 0.008 Seconds 1 2.000 1010101000000000 5.000 Seconds 2 10.000 1111111100000000 0.000 Seconds 3 20 .080 0011001100000011 I 0.000 Seconds 4 25 .080 0101010100000000 3.000 Seconds 5 0.008 XXXXXXXXXXXXXXXX R 0.000 Seconds 6 0.008 RXXXXXXXXXXXXXXX 0.008 Seconds 7 0.008 XXXXXXXXXXXXXXXX 0.008 Seconds 8 0.000 XXXXXXXXXXXXXXXX 0.000 Seconds 9 0.000 XXXXXXXXXXXXXXXX 0.000 Seconds 10 0.008 RXRXXXXXXXAXXXXX 0.008 Seconds 11 0.000 XXXXXXXXXXXXXXXX I 0.000 Seconds 12 0.000 XXXXXXXXXXXXXXXX 0.008 Seconds 13 0.000 XXXXXXXXXXXXXXXX 0.008 Seconds
Status: External Control Drive 9-12 Module 21-24 Internal 01-016 Velocity: 0 RPM Position: 0.000 IN
Enter the position for PLS 0 Enc Pos: 3 counts Range: -2147483.648 to 2147483 .647 Press T or 1! to choose: Enter to select/change: Esc to exit
13
Page 20
PCM-11 Application Module Operator's Manual
Your cursor will highlight the starting point of the first position range (typically zero when starting out). Enter the first range starting position including decimal point and then press the <Enter> key. The cursor will move to the Pattern Area and highlight the first column. This column represents the first Programmable Output line that you assigned (that line number will be shown above next to the word “Pattern”). At this point, enter a 1 to turn a line On, a Ø to turn a line Off, or an X for Don’t Change this line. Do not press the <Enter> key at this point. You will notice that after every entry the cursor moves to the next column. Wait to press the <Enter> key until you are finished entering or correcting the desired pattern. When you have completed the pattern for this range, press the <Enter> key and the cursor will move to the Pulse Width area. If you enter a Pulse Width (or time delay) in seconds in this field, the pattern you have just entered will come on when the motor enters this range from either direction and stay on for the amount of time you enter. When the time expires, all lines marked with a “1” will be turned off. Lines with an “X” will not be changed. However, if the motor is moving through the range faster than the Pulse Width you have selected, the next range pattern will be set on the output lines as soon as that range is entered. Only lines marked with “X” in the next range will not be changed. After you enter the pulse width (or Ø for the pattern to remain until the motor enters the next range), press <Enter>. The cursor will move to the next PLS starting point. In the example screen in Figure 11, assuming a 25 inch linear range is active, the PLS pattern will show all lines off when the motor position goes below 2.000 in., including positions less than zero. The pattern will remain as in position 4, when the motor position is over 25.000 inches. If PLS positions are entered such that the sections are out of sequential order, PCX immediately sorts the positions in ascending numerical order after you enter a position and updates the display automatically.
Remember that the pattern will change according to 1) the position the motor enters, and 2) the direction that position is approached from. If the motor moves from 3.000 inches to 1.000 inches, the pattern will go from four lines ON, four lines OFF to four lines OFF, four lines ON as the position becomes less than 2.000 inches.
User Registers User Registers act as “workspaces” for the storage of data. Examples of stored data include:
14
• •
FX drive variables that are used in math equations.
•
Flags or counters that act as progress monitors in programs.
Values to be used in conditional branches in programs.