Page 91
2 . DIGITAL OPERATOR (JV40P-114) (Contid) 2 .6.2 Calibration of Frequency Meter/Ammeter Calibration of frequency meter or ammeter* connected to the inverter can be performed even without providing a calibration resistor. <Example> When the frequency meter specifications are 3V full-scale and 3V full-scale output is used at maximum output frequency [constant (No.02) ] operation, set [constant (No.45)] to 0.30.
No 45 kiL~
3V
* Inverter output current can be monitored by setting constant No .21 . For details, refer to "MULTIFUNCTION ANALOG OUTPUT MONITOR SETTING" on page 110.
Page 92
2. DIGITAL OPERATOR (jVOP-114) (Confd) Frequency Meter Calibration [Description]
Select PRGM mode . Select constant (No.45) .
"
[Key Operation]
Irlo-Un
D R IVE DSPL
Data are displayed.
DATA E NT E R
Change the set value.
RESET
Write in the set value. DATA ENTER (End is displayed for 1 second.) The data are displayed again after End is displayed.
[Digital Operator Display "j
ZI 11 j u
10 vx 0 .3 = 3 .0 V* -
- u U
* Since analog monitor gain is set to 1 .00 prior shipping, IOV is output at maximum output frequency [constant (No.02)] operation . Note : By data display of constant (No.45) in the program mode, voltage at 100% level according to the constant (No.45) set value is output by the meter calibrating function without any conditions. (Example) Assuming constant (No.45) = 0.30 : 10V X0.30 = 3V is output without any conditions.
Page 93
2 . DIG ITAI. OPERATOR (AFOP-114) (Cont'd) 2 .7 MONITOR Frequency reference value, output frequency, output current and fault contents can tie monitored.
2.7 .1 Typical Monitor Contents and Display (DRIVE Mode) The monitor item is changed every time the
DSPL is depressed . Key Operation
DSPL
DRIVE MODE FREQUENCY REFERENCE VALUE DISPLAY/ SETTING
Typical Display rEL
Tr inn r L L! U ]
OUTPUT FREQUENCY MONITOR DISPLAY
DSPL
DSPL
OUTPUT CURRENT MONITOR DISPLAY ri r- 1 READING key
~uu If a fault occurs, the contents are displayed. f- rn
Fault reset
R E SE T
Page 94
2. DIGITAL OPERATOR (JVOP-114) (Cont1d) 2.7.2 Monitoring of Fault Contents - If a fault occurs, the fault contents are displayed with priority over other display items . Depress the key or turn on the fault reset input aT signal to reset the fault. - Since the latest fault content data are stored in the inverter, even if the power supply is turned off, they can be monitored after the power supply is turned on again. (1) Checking fault contents The latest data are stored in the constant (No .48). (except UV) (2) Clearing fault contents The contents are cleared by setting "6" to the constant (No.00). Or they are also cleared by constant initialization. [Set constant (No.00) = 8 or 9.] At this time, other constants are changed to the factory setting values . Therefore, record all of the constant data before initializing constant. (3) Faults to be stored OC (overcurrent), OV (overvoltage), OH (cooling fin overheat), OL 1 (motor overload), OL2 (inverter overload), OL3 (overtorque detection), EF4, EF5 (external fault), CPF05 (AD converter fault). For details, refer to Table 1 .8 "Fault Display and Contents" on page 47 .
,
Page 95
2 . DIGITAL OPERATOR (JVOP-114) (Cont'd) 2.8 FUNCTION/CONSTANT LIST
2.8.1 First Functions (Constant Nos. 00 to 19) Function
No.
Constant Group Selection
Fault Contents Clear
00 Password
Constant Initialization
Operation Method Selection
Stopping Method Selection V/f Pattern Setting .
Description
Initial Setting
0 = Password (No. 00) setting/ reading and first function (constant Nos. 01 to 19) reading possible 1 : First function (constant Nos. 00 to 19) setting/ reading possible 2 : First and second functions, (constant Nos. 00 to 29) setting/reading possible 3 First, second and thud functions ;constant Nos. 00 to 59) setting/ reading possible 6 Fault record clear 8 Initialize (multifunction terminal initial value setting) 9 Initialize (3-wire sequence)
1
N
User ReferSet once Values Page
95
1st digit = 0 : Master frequency reference-Control circuit terminals 8 and 11, or 9 and 11 inputs = 1 : Master frequency reference-Oper ator Run Fxxxx Signal 2nd digit = 0 : Run by control circuit 0000 01 * Selection 1 terminal run command = 1 : Run by operator run (~ 11) t command 3rd digit = 0 : Deceleration to a stop = 1 - Coasting to a stop Output Voltage Limner Selection
96
4th digit = 0 :
Free choke V/f with output voltage limiter = 1 : Free choke V/f without output voltage limner
* The first to fourth digits indicated in the description of constant (No 01) mean the following digits . This also applies to the other constants. r The value in parentheses is factory set value of models with digital operator .
0 0 0 0
IL
1st digit 2nd digit 3rd digit 4th digit
Page 96
2. DIGITAL OPERATOR (JVI:)P-114j (Cont*d) Function
V/f Pattern Setting
No.
Second Accel/ Decel Time Setting
Description
Initial Setting
02
Maximum Setting unit : 0.1 Hz, Output Frequency Setting range : 50.0 to 40C .0 Hz
60.0
03
Maximum Voltage
Setting unit : 0.1 V*, Setting range : 0.1 to 255.0 V*
230.0 V
04
Maximum Voltage Setting unit : 0.1 Hz, Output Frequency Setting range : 0.2 to 400.0 Hz (Base Frequency)
60 .0 Hz
05
Mid. Voltage Setting unit : 0.1 Hz Output Setting range : 0.1 to 399.9 Hz Frequency
1 .5 Fiz
Mid . Output 06 Frequency Setting unit : 0.1 V*, Setting range : 0.1 to 255.() V* Voltage
12 .0 V*
Minimum Voltage Setting unit : 0.1 Hz, Setting range : 0.1 to 10 Hz Output Frequency
1 .5 Hz
08
Minimum Output Setting unit : 0.1 V*, Frequency Setting range : 0.1 to 50 V Voltage
12 .0 V*
09
Acceleranon Time 1
Setting unit : 0.1 s, Setting range : 0.0 to 600.() s
10.O s
1p
Deceleranon Time 1
Setting unit . 0.1 s, Setting range . 0 0 to 600.() s
10.0 s
11
Acceleranon Time 2
Setting unit . 0.1 s, Setting range : 0 0 to 600.0 s
10.O s
12
Deceleranon Time 2
Setting unit : 0.1 s, Setting range : 0.0 to 600.() s
10.0 s
07
First Accel/ Decel Time Setting
Name
* For 460 V class, the value is twice as that of 230 V class
User ReferSet ence Values Page
102
105 at
Page 97
2 . DIGITAL . OPERATOR (JVOP-1ia) (Corlfd) Function
Frequency Reference *
Name
13
Frequency Reference 1
Setting unit : 0 1 Hz, Setting range : 0 .0 to 400.() Hz
0.0 Hz
14
Frequency Setting unit : 0.1 Hz, Reference 2 Setting range : 0.0 to 400.() Hz
0.0 Hz
15 16 17
Description
User ReferInitial Set ence Setting Values Page
No.
Frequency Reference 3 Frequency Reference 4
Setting unit : 0.1 Hz, Setting ran ge . 0.0 to 400.() Hz
0.0 Hz 0.0 Hz
Jog Frequency Reference
Setting unit : 0.1 Hz, Setting range . 0 .0 to 400.0 Hz Setting unit : 0.1 Hz, Setting range : 0.0 to 400 0 Hz
6.0 Hz
Electronic thermal overload motor protection provided = 1 : Electronic thermal overload motor protection not provided 2nd cligit = 0 : Electronic thermal overload characteristics is for standard motor -_ 1 Electronic thermal overload characteristics is for constant torque motor
98
1st digit = 0
Electronic Thermal Overload Motor Protection
18
Motor Protecton Selection
0000 109
3rd digit : Not used 4th digit : Not used Electronic Thermal Overload Reference Current
19
Motor Rated Current
Setting unit : 0.1 A, Setting range 10 to 120°6 of inverter rated current
1 .9 A t
* Can be changed even during run . The maximum setting frequency to be set to frequency reference is the maximum frequency (No . 02) . t Initial setting differs according to the inverter capacity. The values in the above list are provided when model CIMR-PCU20P4T [0.75 HP (0 4 kW)] and YASKAWA standard motor 230 V 60 Hz 0.75 HP (0.4 kW) are combined.
Page 98
2. DIGITAL OPERATOR (JV'OP-114) (Cont*d) The following shows the standard set value for each capacity . If the general-purpose motor rated current value is different from the standard value, change the setting .
10 230 V Class
3-phase Series
VS-606PC3
Max . Applicable Motor Capacity HP (kW) Motor Current Value at Factory Setting A
20P2
20P4
20P?
21P5
22PO
22P2
23P7
013 (01) 0 25 (0 2) 0 75 (04)
1(075)
1 5 (15)
20(20)
3(22)
5(3.7)
NEMA4 013 (01) 0 25 (0 2) 075(04)
1(075)
20(15)
-
3(22)
5(37)
20P1
Model CIMR-PCU NEMA 1 NEMA 1
0.6
1 .1
1 .9
3 .3
6.2
6.2
8 .5 i 4.1
NEMA4
0.6
1 .1
1 .9
3 .3
6.2
-
8.5
14.1
10 240 V Class
Single-phase Series
VS-606PC3
BOP 1
BOP2
BON
BOP?
B1P5
B2P2
B3P7
Max . Applicable NEMA 1 Motor Capacity HP (kW) NEMA4 Motor Current NEMA 1 Value at Factory Setting A [NEMA4
013(01)
0 25 (0 2)
0 75 (0 4)
1(075)
15(15)
3 (2 2)
5(37)
013(01)
025(02)
075(04)
1(075)
20(15)
3(22)
-
0 .6
1 .1
1 .9
3 .3
6.2
8.5
14.1
0.6
1 .1
1 9
3 .3
6.2
85
Model CIMR-PCU
0 460 V Class
I
-
3-phase Series
VS-606PC3
40P2
40P4
40P-
41P5
42P2
43P7
HP (kW)
0.5 (0 .2)
0.75 (0 .4)
1 .5 (0.75)
2 (1 .5)
3 (2.2)
5 (3.7)
Motor Current Value A at Factory Setting
0.6
1 .0
1 .6
3.1
4.2
7.0
Model CIMR-PCU
Max. Applicable Motor Capacity
Page 99
2. DIGITAL OPERATOR (JVOP-1i4) (Cont'd) 2.8.2 Second Functions (Constant Nos. 20 to 31) Function
No.
Name
REV Run Prohibit Stall Prevention During Deceleration
20 Run Signal Selection 2 output Monitor Selection
Analog Monitor Selection
Description 1 st digit = 0 : REV run enabled = 1 ' REV run disabled 4th digit= 0 : Stall prevention during deceleration provided = 1 : Stall prevention during deceleration not provided (when braking resistor connected) 1st digit : Not used 2nd digit _- 0 : Analo monitor output frequency = 1 : Analog monitor output current (Analog monitor gain is set by constant No. 45.)
21 S-curve Accel/decel Selection Frequency 22 Reference Gain Frequency
23 Reference Bias
User ReferInitial Set ence Setting Values Page 96 0000 113
110 0000
3rd digit = 0 : S-curve acce!/decel not provided = 1 : S-curve accel/decel provided (0 2 sec .) 4th digit : Not used
100
Setting unit : 0.01 ~ Setting range : 0.01 to 2 .00
1 .00
107 setting unit : 0.01, Setting range : -1 .00 to 100
000
107
Page 100
2. DIGITAL OPERATOR (JVO-P-11#) (Cont'd)
Function
Frequency Limit Control
DC Injection Braking
Name
24
Frequency Upper Limit
Setting unit : 196, Setting range : 0 to 11096
100%
Frequency Lower Limit
Setting unit : 196, Setting range : 0 to 11096
096
26
DC Injection Braking Current
Setting unit : 196, Setting range : 0 to 10096 of inverter rated current
50%
27
DC Injection Braking Time at Stop setting unit : 0.1 s, Setting range : 0.0 to 5.0 s
0.0 s
DC Injection Braking Time at Start
Setting unit : 0.1 s Setting range : 0.0~ to 5.0 s
0.0 s
29
Automatic Torque Boost Gain
Setting unit : 0.1, Setting range : 0.0 to 3.0
1.0
30
Stall Prevention Level while Acceleration
Setting unit : 1 % Setting range : 30 to 200% of inverter rated current Note : Stall prevention during acceleration does not operate at 200%.
17096
25
28 Torque Compensation
Stall Prevention 31
Stall Prevention Level during Running
Description
Initial Setr encer Setting Values Page
No.
123
114
112
Setting unit
Setting range : 30 to 200% of inverter rated current Note : Stall prevention during run does not operate at 200% .
111
16096