The text of a manual · part 11 of 16
Varispeed-606PC3 Instruction Manual, pages 101 to 110
Pages 101 to 110 of 157
The original document is the PDF (8.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the EMS PC3-21P5
Page 101
2. DIGITAL OPERATOR (JVOP-114) (Cont'd) 2 .8 .3 Third Functions (Constant Nos . 32 to 59) Function
No.
32
Name
Multifunction Input Selection 1 (Terminal 3 Function Selection)
c °Contact c o Input Signal
Description 0 . FWD/REV run command (3wire sequence selection) 1 : External fault (NO contact input) 2 : External fault (NC contact input) 3 : Multi-step speed reference 1 4 Multi-step speed reference 2 5 : JOG command 6 : Accel/decel time select 7 : External baseblock (NO contact input) 8 : External baseblock (NC contact input) 9 : Search command from maximum frequency 10 : Search command from setting frequency 11 : Accel/decel hold 12 : LOCAL/REMOTE select 13 : Alarm reset
User ReferSet e Values Page
13
116
1
117
1
33
Multifunction Input Selection 2 (Terminal 4 Function Selection)
External fault (NO contact input) 2 : External fault (NC contact input) 3 : Multi-step speed reference 1 4 - Multi-step speed reference 2 5 : JOG command 6 : Accel/decel time select 7 : External baseblock (NO contact input) 8 : External baseblock (NC contact input) 9 : Search command from maximum frequency 10- Search command from setting frequency 11 : Accel/decel hold 12 - LOCAL/REMOTE select 13 . Alarm reset
Initial Setting
Page 102
2 . D IGITAL OPERATOR (JV10P-114) (Cont1 d)
Function
Contact Input Signal
No.
3
4
Description
Multifunction Input Selection 3 (Terminal 5 Function Selection)
1 . External fault (NO contact input) 2 : External fault (NC contact input) 3 : Mufti-step speed reference 1 4 : Mufti-step speed reference 2 5 : jOG command 6 : Accel/decel time select 7 : External baseblock (NO contact input) 8 ; External baseblock (NC contact input) 9 : Search command from maximum frequency 10 : Search command from setting frequency 11 : Accel/decel hold 12 : LOCAL/REMOTE select 13 : Alarm reset
3
118
Multifunction Analog Input Selection
0 : Not used 1 : Auxiliary frequency reference 2 : Frequency reference gain 3 : Frequency reference bias 4 : Voltage bias
0
119
5
121
0
U
Analog Input Signal
Contact Output Signal
35
36
User ReferInitial Set Setting Values ence page
Name
Multifunction output Selection 1 (Terminals FLT-A, FLT-B, FLT-C Function Selection)
0 : Running 1 : Frequency agreement 2 : Zero speed 3 ; Frequency detection (output frequency ?frequency detection level) Overtorque detection 5 : Fault 6 : Frequency detection (output frequency :-5-frequency detection level) 7 . During BB 8 : During UV 9 : During speed search 10 : Operation mode (LOCAL/REMOTE)
4-
Page 103
2. DIGITAL OPERATOR (JV'OP-114) (Cont*d) Function
No.
37
Name
Description
Multifunction Output Selection 2 (Terminal 13 Function Selection)
0 : Running 1 : Frequency agreement 2 : Zero speed 3 : Frequency detection (output frequency>frequency detection level) 4 Overtorque detection 5 Fault 6 Frequency detection (output frequency s_frequency detection level) 7 : During BB 8 : During UV 9 : During speed search 10 : Operation mode (LOCAL/REMOTE)
Multifunction Output Selection 3 (Terminal 14 Function Selection)
0 : Running 1 : Frequency agreement 2 : Zero speed 3 : Frequency detection (output frequency>-_frequency detection level) 4 : Overtorque detection 5 : Fault 6 : Frequency detection (output frequency!-5- frequency detection level) 7 : During BB 8 : During UV 9 : During speed search 10 : Operation mode (LOCAL/REMOTE)
Frequency Detection Level
Setting unit 0.1 Hz, Setting range 0.0 to 4C0 .0 Hz
0 0
PhotoCoupler Output Signall
38
Desired Speed Detection
39
User ReferInitial Set ence Setting Values Page
0
121
1
0.0 Hz
126
Page 104
2 . DIGITAL OPERATOR (JVOP-114) (Confd) Function
No.
Name
Description
Initial Setting
User ReferSet ence Value Page
1 st digit = 0 : Overtorque detection not provided
= 1 : Overtorque detection provided
40
Overtorque Detection Function Selection
2nd digit = 0 : Detected only during frequency agreement = 1: Detected during running
0000 124
3rd digit = 0 : Operation continues after overtorque detection = 1: Output shul-off at overtorque detection
Overtorque Detection
C
4th digit : Not used
Carrier Frequency Adjustment
41
Overtorque Detection Level
Setting unit : 1%, Setting range : 30 to 200% of inverter rated current
160%
42
Overtorque Detection Time
Setting unit : 0.1 s, Setting range : 0.1 to 10.0 s
0.1s
43
Carrier Frequency
Setting unit : 1 (2.5 kHz) Setting range : 1 to 6 (2.5 to 15 kHz)
4
441Not-used
I (Setting disabled .)
(10 kft)
125
Page 105
2 . DIGITAL OPERATOR (JVOP-114} (Cont'd) Function Analog Monitor Scale Calibration Momentary Power Loss Protection
No.
Name
45
Analog Monitor Gain
46
Operation Selection after Momentary Power loss
I
Description Setting unit : 0.01, Setting range : 0.01 to 2.00 1st digit= 0 - Continuous operation after momentary power loss not provided = 1 : Continuous operation after momentary power loss provided 2nd, 3rd, 4th digits : Not used .
User ReferInitial Set ence Setting Values Page 1 .00
110
0000
132
0
135
Fault Retry 47
Fault Retry Selection
Setting unit : 1 time, Setting range : 0 to 10 times Note : By setting 0 times, fault retry function becomes disabled.
Fault Trace
48
Fault Record
The latest fault is displayed (setting disabled .)
Software Version
49
PROM No.
PROM No. is displayed (setting disabled.)
50
Prohibited Frequency
Setting unit : 0.1 Hz, Setting range : 0.0 to 400.0 Hz
0.0 Hz
51
Prohibited Width
Setting unit : 0.1 Hz, Setting range : 0.0 to 25 5 Hz
1 .0 Hz
52 to 59
Not Used
(Setting disabled .)
Prohibited Frequency
128
Page 106
2. DIGITAL OPERATOR (JVOP-114) (Cont'd) 2 .9 DESCRIPTION OF FUNCTIONS AND CONSTANTS Constant Nos. are indicated as
N] .
PASSWORD SETTING Item Name Constant Group Selection
I
Constant to be Set 170
Factory Preset 1 l01=0
Password FO-1 setting/reading and the first function (~0 to 0) reading are enabled. This setting prevents constant from being reset by improper operation after completion of constant setting. D can be written in .
- F-01 =0 The first functions can be read .
0=1 The first functions ([0 to 19) can be set and read. DO =2 The first and second functions 01 to F2-91) can be set and read. ~=3 The first, second and third functions (~0 to 59) can be set and read. 0=6 Fault history is cleared . 0=8 All control constants can be initialized . Terminal functions are returned to the factory setting. 0 = 9 All control constants: can be initialized . Terminal functions are of 3-wire sequence. Refer to "MULTIFUNCTION CONTACT INPUT FUNCTION SELECTION" on page 115 .
Page 107
2. DIGITAL OPERATOR (JVOP-114) (Cont 4 d)
OPERATION MODE SELECTION. Item Name Start/Stop Procedure Reverse Rotation Prevention
Constant to be Set
Factory Preset
[i]
0000 (0011)* 0000
* The value in parentheses is factory setting of models with digital operator .
Start procedure Operation can be performed from the operator or control circuit terminal input. 10 = X X 0 0 (X means 1 or 0.) 1 st digit 0 : Frequency reference from control circuit terminal 1 : Frequency reference from the operator 2nd digit r0 : Start/stop control from control circuit terminal 1 : Start/stop control by the operator Stop procedure Stopping mode can be selected according to the application.
11 =Xoxx rd digit 0 : Deceleration to a stop 1 : Coasting to a stop
Reverse rotation prevention Prevents accidental selection of reverse rotation. REV run command is disregarded if input . F24
=xxxi lst digit 0 : Reverse rotation is possible . 1 : Reverse rotation is impossible.
Page 108
2. DIGITAL OPERATOR (JV,OP-1 14) (Conlfd) Operation mode selection by RED key on digital operator changes LOCAL/REMOTE mode alternately . LOCAL mode : can be operated by run command and/or frequency reference by digital operator. REMOTE mode : can be operated by the set value in the first/second digits of constant 0.
Note : The first to fourth digits indwated in the description of the constant mean the following digits . Fi-1.
=oooo
1 st digit 2nd digit 3rd digit 4th digit
ALARM RESET FUNCTION SIELECTION Item Name Alarm Reset
(
Constant to be Set
Factory Preset
121,13&E
See page 90.
Alarm status of the inverter can be reset by presetting the multifunction input terminal . When an alarm occurs, reset it by connecting terminals (I and (when setting 32 = 13).
~m
CIO
Page 109
2. DIGITAL OPERATOR (JV'OP-114) (Cont 1 d) 4-STEP SPEED C H ANGE Item Name Multi-speed Frequency Reference Multi-speed Operation Function
-
Constant to be Set
Factory Preset
B to ~s
See page 86.
E32], 33, EI
See page 90.
Up to 4 steps of speed can N', set by contact input by setting multi-speed references to multifunction contact input terminals . This eliminates the need for an analog signal thereby enabling operation even at low speed without being affected by noise . See: the following example . (When setting 32 = 3, 33 = 4) Set according to run specifications .
j
Page 110
2 . DIGITAL OPERATOR (JVOP-114) (Cont'd) 16 15 W9e NCY
14 FREQUENCY REF.
~*
'ENCY , EF03
REFZ ~Y
MASTER FREQUENCY
( I
TERMINAL
FWD RUN REF. REV RUN REF.
MULTI-SPEED REF. 1 MULTI-SPEED REF.2
CLOSED
O OPEN O-
OPEN
Q OPEN
0 OPEN
I I
I I I I I
I I I
(CLOSED
I I I I i
TIME i
I
I CLOSED i I ~-
I
(CLOSED
I I
I
I
I I I
I
I
I
I
I
I I j
Note : For frequency reference change during running, only frequency reference selected by multi-speed reference during frequency reference value display can be changed. Additionally, when either multi-speed reference 1 or 2 is used, the other multi-speed reference that is not set is regarded to be always "open" . * 1 st digit of 01 0 : Frequency reference or auxiliary frequency reference from control circuit terminal 1 : Set value of l3
> t~ ~ 00