Page 111

2. DIGITAL OPERATOR (JVOP-114) (Cont'd)

S-CURVE PATTERN SELECTION Item Name S-curve Pattern Selection

Constant to be Set ~~

Factory Preset 0000

To prevent shock at machine starting/stopping, accel/decel in S-curve pattern is enabled by the setting of . 21 = X0X X

FREQUENCYI REFERENCE

3rd digit 0 : S-curve section not provided (linear accel/decel) 1 : S-curve section provided (0 .2 second)

i OUTPUT FREQUENCY

S-CURVE CHARACTERISTIC TIME 0.2 sec Note : S-curve characteristic time refers to the time from the acceleration rate 0 to regular acceleration rate determined by the set acceleration time.

Page 112

2. DIGITAL OPERATOR (JVOP-114) (Cont4 d) The following shows the time chart at FWD/REV run switching at deceleration to a stop. FWD RUN COMMAND REV RUN COMMAND

7

1 fi , DE CELERATION MINIMUM I OUTPUT ----- --1 ~ FREQ UENCY7 , OUTPUT FREQUENCY , MINIMUM MINIMUM '~ C)UTPUT OUTPUT FREQUENCY FREQUENCY ACCELERATION t, ~i S-CURVE CHARACTERISTICS ACCELERATION i a -;

IN '

'

DC INJECTION BRAKING TIME AT STOP . 27

Page 113

2. DIGITAL OPERATOR (JVOP-114) (Cont'd)

V/f CHARACTERISTIC SETTING Item Name

Constant to be Set

Factory Preset

'2;

60 .0 Hz

Max. Output Frequency Max. Voltage

230.0 V

Max. Voltage Output Frequency a

60 .0 Hz

Mid . Output Frequency

W,

1 .5 Hz

Mid . Output Frequency Voltage

M6

12.0 V

Min . Output Frequency i

1 .5 Hz

Min . Output Frequency Voltage

111

12 .0 V

Output Voltage Limiter Selection al 1

0000 u

. V/f pattern setting

Any desired V/f pattern can be set for special specifications, too . Any V/1' pattern can be set according to the load characteristics . The factory preset value is set to 60 Hz saturation type pattern . Factory Preset

VOLTAGE

VOLTAGE ~ 22 0 V

V/f PATTERN SETTING

0 _ i i i o 1-71 a T 1 i [21

® F6] 12 FREQ.

0 1 .5 Hz

C] [51

60 Hz

FREQ.

Note : If an excessively large value is set in low-speed area (3I-I/ or less), motor overheat or inverter malfunction may occur. Change the constant gradually monitoring load or motor current.

Page 114

2. DIGITAL OPERATOR {JVOR-114) (Cqnt'd)

JOG OPERATION Item Name Jog Frequency Reference Setting Jog Reference Selection

Constant to be ~~et » ~ '~, 33, !~

Factory Preset 6.0 Hz

See page 90.

To select the jog mode, close between terminals ~ - ~. Jog operation can then be performed by closing the FWD/REV run command (when setting ~=5). ~

71

FORWARD _ RUN

FREQUENCY

~

JOG SIGNAL i ~ ON

FORWARD RUN SIGNAL REVERSE RUN SIGNAL

'i

QN

F;EVERSE F UN i\ , i

I

~ I ON I

TIME

Page 115

P. DIGITAL OPERATOR (JVOP-114) (Confd)

ACCEL/DECEL TIME SETTING Item Name

Constant to be Set

Factory Preset

Acceleration Time 1

E91

10 .0s

Deceleration Time 1

~0

110 .0s

Acceleration Time 2

>>

110.0s

Deceleration Time 2

12

10.O s

0, 33, ®

See page 90.

Accel/Decel Time Select

I

0

00 Each item can be set from 0,.0 sec to 600 sec . -w The set time indicates the interval required before the ~maximum output frequency setting M is reached. Accel/decel time can be set for two-step switching using multifunction contact input, even during running. Between control circuit terminals 0) Open : F9_1 and F0 are selected. Closed : 11 and 12 are selected. (when setting F3_21 = 6)

I ~

I

OUTPUT FREQUENCY L__ 1

E 9 "I

11

Note : S-curve accel/decel reducing shock at motor starting is also enabled. When S-curve accel/decel is needed, refer to "S-CURVE PATTERN SELECTION" on page 100.

Page 116

2. DIGITAL OPERATOR (J%fOP-114) (Cont'd)

LOCAL/REMOTE MODE SELECTION Item Name LOCAL/REMOTE Selection Operation Mode Output

Constant to be Set

Factory Preset

LJ, '33, N-11

See page 90.

[361, M, FX-;

See page 91 .

The following modes of operation can be selected by presetting the LOCAL/REMOTE switch command for the multifunction input terminal (when setting 32 =12). When terminals 3 and 06 are disconnected LOCAL mode (operation mode output : no operation) Operation is possible by using the digital operator operation commands or frequency references . When terminals 0 and © are connected REMOTE mode (operation mode output : operation) Operation is possible by using the operation commands or frequency references determined by the set values of the first and second digits in [] . The same operation is available with the the digital operator.

=1CAL REMOTE key of

Page 117

2. DIGITAL OPERATOR (JVOP-1 i4) (Gont'd) OUTPUT FREQUENCY CONTROL (GAIN/BIAS)

Item Name

Constant to be Set ' C

Frequency Reference Gain Frequency Reference Bias

Factory Preset 1 .00 0.00

X2,_ 7 3_,

Output frequency (gain/bias) can be set freely according to frequency setting (0 to IOV or 4 to 20mA ) . [2] X

22

100° BIAS

24 r

[] X 23 -F 0 (4mA)

GAIN

1,

OUTPUT FREQUENCY UPPER LIMIT VALUE (Refer to "OUTPUT FREQUENCY LIMIT"on page 111 .)

F REQUENCY

SETTING 10 V (20mA)

For the setting method, refer to Par. 2.6.1 "Adjustment of Frequency Setting Value, Output Frequency Bias (No .23) and Gain (No .22)" on page 78 .

Page 118

2. DIGITAL OPERATOR (J\j'OP-114) (Cont'd) Relation between analog input voltage/current and frequency

UU zz ww Z) elf oUw w L-L Of

100% '

0

0 (4)

The figure shows the relation preset at the factory. The relation between analog input and frequency can be changed by resetting of gain (no-22) and bias (no-23) .

10V , (20 mA),

Example : 0 to 5 V analog input

SETTING GAIN (no-22,` = 2.00% BIAS (no-23) = 0 00% 5V

10V

Page 119

2. DIGITAL OPERATOR (JV0P-114) (Conttd) ELECTRONIC THERMAL OVERL0~D PROTECTION Item Name

Constant to be Set

Factory Preset

Motor Type

1s

0000

Motor Rated Current

M~

1 .9 A

* The example represents YASKAWA 0 .5HP (0.4 kW), 230 V, 4pole motor. The YASKAWA standard motor current value is set at factory prior to shipping . See page 86.

Motor output current is detected by the inverter built-in electronic thermal overload function, and inverter exclusive-use motors or standard motors are prevented from overloading . (It is not necessary to mount the thermal overload relay externally . However, to connect several motors to one inverter, a thermal overload relay must be inserted for each motor. It is necessary to reduce carrier frequency according to the wiring distance between the inverter and motor when thermal overload relays are inserted. For details, refer to the precautions on wiring described on page 29 .) 19 =Motor rated current value

Set the motor rated current value according to the value on the motor nameplate .

71~ =XX0X

2nd digit 0 : Standard motor Exclusive-use motor IN = X X X 1 can make electronic thermal overload function disabled. 1 st digit 0 : Electronic thermal overload protection provided 1 : Electronic thermal overload protection not provided

41 :

- 109 -

Page 120

2 . DIGITAL OPERATOR (JVOP-114) (Cont'd) MULTIFUNCTION ANALOG OUTPUT MONITOR SETTING Item Name

Constant to be Set

Factory Preset

Output Monitor Select

LYE

0000

Analog Monitor Gain

~a5!

1 .00

Either output frequency or output current can be monitored by analog output between control circuit and Q (0 to lOV output) terminals

(9

21=X X 0 X

T Z- Not used

Output contents between control circuit terminals 2nd digit 0 : Output frequency monitor 1 : Output current monitor

Analog output monitor gain can be set by 45 . Additionally, analog output monitor voltage is output as shown below Output frequency monitor Output voltage (V) , V 10 X 45 = Output frequency X z Max . output frequency Output current monitor Output voltage (V) 10V x F4,5 = Output current X Inverter rated current Note : Since output current becomes approx. 200% maximum of the inverter rated current, output voltage is clamped at approx . 1 l V when '45 is used at 1 .00 and the inverter rated current is exceeded . To keep linearity, set 0 to approx . 0.5.