Page 121
2. DIGITAL OPERATOR (JVOP-114) (Cont'd)
OUTPUT FREQUENCY LIMIT Item Name Output Frequency (Speed) Upper Limit
Factory Preset
LJ
100%
,~
0
Output Frequency (Speed) Lower Limit
Constant to be Set
The upper and lower limits for the output frequency can be set. When the lower limit is not 0, acceleration to that lower limit setpoint begins until frequency reference reaches the lower limit value when the start command is input . 100% 24 OUTUT FREQUENCY
100% FREQUENCY COMMAND
Note : By setting A to 110%, frequency up to 12~ X 1 .1 can be output. (Example) Assuming 2 = 60 Hz, '2] = 1 .1, up to 66 Hr. can be output. However, when the voltage exceeds 400 Hz, it is clamped at 400 Hz .
Page 122
2. DIGITAL OPERATOR (A/OP-1 14) (Cont'd) MOTOR STALL
P'REVENT~ON FUNCTION
Item Name
Operation Level for Stall Prevention during Acceleration
Constant to be Set
Factory Preset
®
170%
3~
160%
Operation Level for Stall Prevention during Running
Stall Prevention Function during Deceleration
0000
Automatically adjusts output frequency according to the load so as to continue operation of the machine without stalling the motor. Stall prevention during acceleration If the motor current exceeds the value set to 30 during acceleration, acceleration is, stopped until the motor current is reduced to the ® set value or less . MOTOR CURRENT
30
OUTPUT FREQ.
TIME
TIME
Page 123
2. DIGITAL OPERATOR (JV0P-114) (Cont'd) Stall prevention during running If the motor current exceeds the value set to 31 because of impact load during running, output frequency is automatically lowered. When the motor current is reduced to the [] set value or less, the motor starts acceleration again and the operation is continued. MOTOR CURRENT
OUTPUT FREQ 1
TIME
Stall prevention during deceleration Automatically adjusts deceleration rate with monitoring DC voltage to prevent overvoltage during deceleration . Set "1" for connecting braking resistor. F201 =ox x x
4th di ait
0 : Stall prevention during deceleration enabled 1 : Stall prevention during deceleration disabled
When the motor load is large or accel/decel time is short, the accel/decel time may be longer than the set value because of the stall preventive function .
Page 124
2 . DIGITAL OPERATOR (JNIOP-114) (Cont'd) FULL-RANGE AUTOMATIC TORQUE BOOST Item Name
Constant to be Set
Factory Preset
Torque Compensation Gain
1 .0
Automatic control of V/f ratio according to the load torque ensures tripless operation and optimum output current. Therefore, tripless operation with excellent energy-saving effect is available . When the wiring distance between the inverter and motor is long (normally approx . 100 m) and when the motor torque is a little short, increase torque compensation gain gradually, checking the motor current. Normally, no adjustment is necessary. Full-range automatic torque boost Motor torque requirement changes according to load conditions . Full-range automatic torque boost adjusts voltage of V/f pattern according to the requirement. The VS-606PC3 automatically adjusts the voltage not only during constant-speed operation but also during acceleration . Torque requirement is calculated by the inverter. Output voltage a
Automatic torque boost gam (no-29)
X
Required torque
OPERATION V (VOLTAGE) l TORQUE
INCREASE VOLTAGE f (FREQUENCY,
Page 125
2. D-IGITAL OPERATOR (JV0P-114) (Cont'd) Although torque boost operates automatically, the factory preset value of automatic torque boost gain 29 does not need to be changed. = 1 .0 (factory preset value) Change the value when the wiring distance between the inverter and motor is long or when the motor vibrates excessively . MULTIFUNCTION CONTACT INPUT' FUNCTION SELECTION Item Name Constant to be Set Multifunction Contact Input Function 5321, 33, '1]
Factory Preset
Refer to page 90.
The function of control circuit terminals U, OD and 0 can be changed if necessary. Set F3_21, R33 and R34 in the descending order . The same value cannot be set simultaneously . Terminal function : Set to []. Terminal function : Set to []. Terminal g5 function : Set to [].
0 4 r 9 CL
C
Page 126
2. DIGITAL OPERATOR (JVOP-114) (Confd) 32 Set Value and its Functions Set Value
Function
Page
0*
FIND/REV run command ;3-wire sequence selection)
1
External fault ( NO contact input)'-----
140
2
External fault (I NC contact input)
140
3
Multi-step speed reference 1
98
4
Multi-step speed reference 2
98
5
JOG command
104
6
Accel/decel time select
105
7
External baseblock 'NO contact input)
144
8
External baseblock (NC contact input)
144
9
Search command from maximum frequency
130
10
Search command from setting frequency
130
11
Accel/decel hold command
137
12
LOCAL/REMOTE selection
97
13
Alarm reset
I
97
Terminal function at 3-wire sequence selection.
VS-606PC3
STOP COMMAND
- MOMENTARY)
(STOP WHEN "OPENED", - MOMENTARY) " . SELECTION " RUI`\ "OPEN"
Page 127
2. DIGITAL OPERATOR (JVOP-114) (Cont'd)
0 Set Value and its Functions Function
Page
1
External fault (NO contact input)
140
2
External fault (NC contact input)
140
3
Multi-step speed reference 1
98
4
Multi-step speed reference 2
98
5
JOG command
104
6
Accel/decel time select
105
7
External baseblock (NO contact input)
144
8
External baseblock (NC contact input)
144
9
Search command from maximum frequency
130
10
Search command from setting frequency
130
11
Accel/decel hold command
137
12
LOCAL/REMOTE selection
97
13
Alarm reset
97
Set Value
Page 128
2. DIGITAL OPERATOR (JVOP-114) (Cont'd) 0 Set Value and its Functions Set Value
Function r
Page 140
1
External fault (NO contact input)
2
External fault (NC contact input)
140
~3
Mult i-step speed reference 1
98
4
Mult i-step speed reference 2
98
5
JOG command
104
6
Accel/decel time select
105
7
External baseblock (NO contact input)
144
8
External baseblock (NC contact input)
144
9
Search command from maximum freque ncy
130
10
Search command from setting frequency
130
11
Accel/decel hold command
137
12
LOCAL/REMOTE selection
97
13
Alarm reset
97
Page 129
2 . DIGITAL OPERATOR (JVOP-114) (Cont*d) MULTIFUNCTION ANALOG INP~T FUNCTION SELECTION Item Name Multifunction Analog Input
I
Constant to be Set
Factory Preset
0
See page 91 .
Select a function for the analog signal to be input from the auxiliary input terminal (option) . Note : This function becomes effective when analog input module JVOP-115 (option) is mounted .
Set Value 0
1
2
Function
Remarks
Not used
Auxiliary frequency reference
When frequency reference 2 is selected by multi-speed reference, the analog signal input from auxiliary input terminal (option) becomes frequency reference. The set value of ~1J is invalidated.
Frequency reference gain (FGAIN)
FGAIN is multiplied by frequency reference after calculation of internal gain and bias 23 on analog signal input from control circuit terminal 8 or 9. (Refer tc page 107 .)
Frequency reference bias (FBIAS)
FBIAS is added to frequency reference after calculation of internal gam [_2 and bias 23 i on analog signal input from control circuit terminal 8 or 9. (Refer to page 107.)
Output voltage bias (VBIAS)
n
VBIAS is added to the voltage of V/f pattern. (Refer to page 102.)
r
Page 130
2. DIGITAL OPERATOR (JVOP-114) (Cont'd) (1) When 30 = 1 FREQUENCY REFERENCE
I 1
(2) When 30 = 2
-0-00-
F G A I N
1
0V 10V MULTIFUNCTION ANALOG INPUT
,)00
'100
5V 10V 0V MULTIFUNCTION ANALOG INPUT
Set value of 02 = 100 % (3) When 35 = 3
(4) When 3© = 4
F B 1 A
V B *100V
1096 0u -1096
OV
-0000
5V
1
10V
MULTIFUNCTION ANALOG INPUT
Set value of Mi =100 * VBIAS for 460 V class drives are 0 to 200 V.
___ i
A S
L00-0~
I
0V 10V MULTIFUNCTION ANALOG INPUT