Varispeed-606PC3 Instruction Manual, pages 141 to 150

Pages 141 to 150 of 157

The original document is the PDF (8.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the EMS PC3-21P5

Page 141

2.

DIGITAL

OPERATOR (JVOP-114) (Conttd)

The following shows the time chart where the speed search command is input. °w -~ 0 5 SEC OR MORE

FWD (REV) RUN COMMAND SEARCH COMMAND

°'

MAXIMUM FREQUENCY OR j FREQUENCY REFERENCE --; AT RUN COMMAND INPUT I OUTPUT FREQUENCY _

SYNCHRONOUS SPEED DETECTION

I i

MINIMUM BASEBLOCK TIME I I (0 5 sec) j I VOLTAGE AT SPEED SEARCH

RETURN TO VOLTAGE AT NORMAL OPERATION

OUTPUT VOLTAGE

SIGNAL DURING SPEED SEARCH

;SPEED SEARCH (OPERATION i I I ON

Notes

1.

2.

When the search commands are input from maximum frequency and setting frequency simultaneously, the search command of lower terminal No . has the priority. Make such sequence that FWD (REV) run command is to be input at the same time or after the search command . If run command is input before search command, search command becomes ineffective . RELAY 1 TYPICAL SEQUENCE

RELAY 1

RELAY 2

SEARCH COMMAND FWD (REV) RUN COMMAND

Page 142

2. DIGITAL OPERATOR (JVOP-114) (Cont'd) ~CONTINUOUS OPERATION AT MOMENTARY POWER LOSS Item Name Operation Selection after Momentary Power Loss Speed Search Operation Level Minimum Baseblock Time

Constant to be Set

Factory Preset

K61

0000 15096 (fixed) 0.5 s (fixed)

Even if a momentary power loss occurs, operation can be continued without any problem. 46=XXX0 1 st digit 0 : Continuous operation after momentary power loss riot provided l : Continuous operation after momentary, power loss provided Momentary power loss ride-thru time differs as shown below, according to the capacity of the models. (common to both 3-phase and single-phase series) Models CIMR-PCU20P 1 to PCU20P7 CIMR-PCUBOP 1 to PCUBOP7 CIMR-PCU40P2 to PCU40P7

Approx. 1 sec.

Models CIMR-PCU21 P5 to PCU23P7 CIMR-PCUB 1 P5 to PCUB3P7 CI MR-PCU41 P5 to PCU43P7

Approx. 2 sec.

Note : If a power loss exceeds the momentary power loss ride-thru time, in the momentary power loss assurance time after the power loss, low voltage fault occurs, fault contact is output and the motor coasts to a stop.

Page 143

2 . DIGITAL OPERATOR (JV(:)P-114) (Cont'd) Operation when continuous operation after momentary power loss is provided is as described below (D When undervoltage (UV) is detected, the inverter output is shut off and the frequency reference value and run command given before the momentary power loss are held. Additionally, counting of the undervoltage time starts ; during counting, Uu is displayed, blinking on the digital display unit and digital operator. If undervoltage is detected, the inverter output is shut off for the minimum baseblock time 0.5 sec. C2) After recovery from the momentary power loss, after checking that the inverter DC voltage has recovered sufficiently, speed search operation is performed . 0 Speed search operation starts when the inverter output current exceeds the speed search operation level . At this time, the new frequency reference value and run command are read in. The frequency in which the inverter output current is smaller than the speed search operation level is judged to be the speed synchronized point, and reacceleration/ redeceleration is performed up/down to the set frequency in the set accel/decel time .

J a

Page 144

2. DIGITAL OPERATOR (JVOP-114) (Cont'd) INPUT POWER SUPPLY UV DETECTION SIGNAL BB MOTOR SPEED INVERTER OUTPUT FREQUENCY

I

RECOVERY

MOMENTARY POWER LOSS OCCURRENCE pt ' I

I I ------ ------------

COASTING

SEARCH

REACCELERATION

I i

* 2~t :

Varies according to the inverter size. (Assured at 15 ms minimum .) Operation is automatically continued if recovery from momentary power loss in ~t or less.

Page 145

2. DIGITAL OPERATOR (JV0P-114) (Conttd) RESTART AF~ Item Name

Constant to be Set

Factory Preset

Fault Retry Selection

0

Speed Search Operation Level

150% (fixed)

Minimum Baseblock Time

0 .5 s (fixed)

V/f during Speed Search

100% (fixed)

If an inverter fault occurs during running, the inverter performs self-diagnosis to restart automatically . The number of the self-diagnosis and restarting times can be set up to 10 times to 91. By setting 0 times, the fault retry function becomes disabled. The inverter restarts automatically in case of the following faults. (DOvercurrent protection (OC) Overvoltage protection (OV) Cooling fin overheat (OH) The number of fault retry times is cleared to 0 in the following cases U No fault occurs for more than 10 minutes Fault reset input signal (or [R ?S ET key on the digital J operator) is turned ON when the fault is checked . 30 The power supply is turned OFF.

Page 146

2 . DIGITAL OPERATOR (JVOP-114) (Confd) Fault retry operation is descdribed below (D If a fault is detected, the inverter output is shut off for the minimum baseblock time 0.5 sec. While the inverter output is shut off., the fault is displayed on the digital display unit ands the digital operator . (2) After the minimum baseblock time 0 .5 sec, the fault is automatically reset, and the speed search operation is performed from the output frequency at the fault occurrence . 30 If the inverter output current is larger than the speed search operation level, the speed search operation starts . The frequency in which the inverter output current is, smaller than the speed search operation level is judged to be the speed synchronized point, and reacceleration/redeceleration is performed up/down to the set frequency in the set accel/decel time . ® If the total number of faults exceeds the number of retry times 47, automatic reset is not performed and the inverter output is kept -off. Then fault contact is output. (Fault contact is not output during fault retry.) FAULT DETECTION OUTPUT FREQUENCY i

~---- --.1

O

O `3)

_"__

MOTOR r/min

Page 147

2 . DIGITAL OPERATOR (JVOP-114) (Conttd) C.C .-ELY DECEL

HOLD

Item Name

COMMAND

Constant to be Set

Factory Preset

~32, 0, i9

See page 90.

Accel/Decel Hold Function

When the accel/decel hold command is input during acceleration or deceleration, acceleration or deceleration is prohibited while: the command is input, and the output frequency is held. By inputting the stop command, the accel/decel command is released and the operation is in the stopped condition . The accel/decel hold command is input from multifunction contact input terminal 30, ® or 05 . For the function of terminal 3;, RD or (1, set "8" to 32 , R or ®. Terminal 30 function : Set to 32 . Terminal U function : Set to 33 . Terminal (3) function : Set to ®. The following shows the time chart when the accel/decel hold command is input FWD RUN ACCEL/DECEL HOLD COMMAND FREQUENCY ~, REFERENCE I

ON

I

I I

I oN i

N

I

I

I

I OUTPUT I FREQUENCY

I

1 -1

FREQUENCY AGREED SIGNAL

ON

ON

I I oN

Note : When the FWD (REV) run command is input in the status where the accel/decel hold command is input, the baseblock status is continued and the motor does not operate . However, when frequency reference lower limit 25 ? minimum output frequency C is set, the motor operates at the frequency reference lower time 25 .

-

13 7 -

;

Page 148

2. DIGITAL OPERATOR (JVOP-114) (Cont'd) 2.10 PROTECTIVE FUNCTIONS Protective Function

Monitor Display

Fault output

,, U

(UV 1)

Operation

~"

(OC)

Operation

Explanation

When the inverter power supply voltage drops, torque becomes insufficient and motor is overheated. Inverter output is Low Main Circuit stopped when the main circuit DC voltage Voltbecomes lower than the low voltage Voltage detection level. Protec- age Detection level : Approx . 210 V or less Low bon (230 V, 3-phase), 170 V (240 V, single-phase), 420 V (460 V, 3-phase) .

I

Overcurrent Protection

The inverter output is shut-off when the inverter output current becomes approx . 200°"6 and above of inverter rated current .

Ground-fault Protection

The inverter output is shut-off when a ground-fault occurs at the inverter output side.

u

(GF)

Operation

The inverter output is shut-off when the main circuit DC voltage becomes excessive because of regeneration energy caused by motor deceleration and negative load. Detection level : Approx. 410 V or more (230 V class 3-phase, 240 V class single-phase), 820 V or more (460 V class) .

0U

(OV)

Operation

Fuse Blown

The fuse clears to prevent wring from bung damaged by the short-circuit current when the main circuit transistor fads.

(Not displayed)

Cooling Fin Overheat (Only for Types of Forced Cooling)

The inverter output is shut-off when the cooling fin overheat is detected by thermistor . Check for a defective cooling fan or clogged filter

Overvoltage Protection

(OH)

Non Operation

Operation

Page 149

2. DIGITAL OPERATOR (JV0P-114) (Gont'd)

Protective Function

Low Voltage Protection

Man Circuit Voltage Low

Overctxrent Protection

Error Causes

Action to be Taken

Inverter capacity is too small. Voltage drop due to wring . A motor of large capacity connected to the same power system has been started. Rapid acceleration with generator power supply Operation sequence when power is off Defective electromagnetic contactor

Check the power supply voltage. Check the power capacity and power system.

Extremely rapid accel/decel Motor ON/OFF switching at the inverter output side Transistor error may occur Short-circuit at the inverter output Investigate the error cause, side Motor of a capacity greater than the correct it, then restart. inverter rating has been started. High-speed motor or pulse motor has been started . Ground-fault at the inverter output side .

Check that motor insulaton ~s not deteriorated . Check that wring of load side are not damaged.

Overvoltage Protection

Insufficient deceleration time Negative load (Motor is turned by the toad.) High input voltage compared to motor rated voltage

If braking torque is not proper, extend the decel time or connect a braking resister unit (option) Check that the load is not minus . Check the power supply voltage .

Fuse Blown

Repeated overcurrent protection (OC) Repeated overload protection (OL2) power reset Rapid deceleration in excess excitation (improper V/f characteristic setting)

Turn OFF the power supply once and turn it ON again If the fault occurs again, replace the inverter Do not replace the fuse.

Ground-fault Protection

Cooing Fn Overheat (Only for Types of Forced Cooing)

Defective cooling fan Intake air temperature rise Clogged filter

- 13 9 -

. Replace he t inverter when the inverter cooling fn is defective. Intake air temperature 104° F (40V or less i

Page 150

2. DIGITAL OPERATOR (jVOP-114) (Confd) Protective Function

Monitor Display

Fault Output

Motor

The inverter output is stopped when output current to the motor is detected by the electronic thermal in the inverter . Either a inverter duty constant-torque specialized motor or general-purpose motor can be selected. If more than two motors are driven, overload protection should be disabled. Use a thermal relay or thermal protector for each motor.

v

(OL 1)

Operation

Inverter

The electronic thermal operates by the inverse time limit and the inverter output is shut-off when 1056 or more of the inverter rated current occurs. Overload capacity - 150%, 1 min.

,u L 2 (OL2)

Operation

Overtorque Detection*

The motor operates according to operation selection [constant (No . 40)] when the inverter output current exceeds the overtorque detection level. This function is used to protect the machine or to monitor the output torque .

o

(OL3)

Operation

External Fault Signal Input

When an external fault signal is input, zhe EF 3 (EF3) EPI (EF4) inverter output is shuft-off. EF S (EF5)

Operation

Control Circuit

The inverter output is shut-off when a transmission error occurs in the control circuit or a component fails .

Overload Protecton

Fault t

Explanation r prrnn i r Lr Lr

4 to r n rr n r

I r

Operation

LO-J-

* For overtorque detection (OL3), fault display or alarm display can be selected according to the constant (No. 40) setting . For details, refer to "OVERTORQUE DETECTION FUNCTION" on page 124 t For details of control circuit faults, refer to Table 1 9 "Details of CPF Display" on page 49

Pr'- ~_i ii to ~~ S indicate the contents of digital operator display