Page 151
2. DIGITAL OPERATOR (JVOP-114) (Cont'd) Protective Function
Error Causes
Acton to be Taken
Overload, long operation at low speed, improper V/f characteristic setting. Motor rated current [constant (No. 19)] setting is wrong.
Investigate the cause of overload and review the operation pattern, V/f characteristic, and motor/inverter capacities . (If inverter is repeatedly reset after an overload occurs, the inverter may fault. Investigate and correct the cause of overload before restart.). Set: the rated current of motor nameplate value to constant (No. 19). If the above measures are not effective, lower the carver frequency [constant (No 43)]
Overtorque Deteclion*
Motor current exceeds the preset value because of machine error or overload .
Check the use of machine. Correct the overload cause or set a higher detection level [constant (No. 41)] which is within the allowable range.
External Fault Signal Input
External fault condition occurred.
Correct the cause of the fault input.
Motor Overload Protection Inverter
Control Circuit Fault t
. External nose Excess vibration or shock
Record all data of C PF ii' then make initialization . Turn OFF power, then turn ON again. If an error is persistent, mplace the inverter .
* For overtorque detection (OL3), fault display or alarm display can be selected according to the constant (No. 40) setting . For details, refer to "OVERTORQUE DETECTION FUNCTION" on page 124. t For details of control circuit faults, refer to Table 1 9 "Details of CPF Display" on page 49. P,-, ,~, to #'-' S indicate the contents of digital operator display
Page 152
2 . DIGITAL. OPERATOR (JVOP-114) (Cont'd) 2.11 PROTECTIVE FUNCTIONS (WARNINGS) Protective Function
Explanation
Low-voltage Protection (Main Circuit Voltage Insufficient)
Monitor display appears when the main circuit DC voltage drops under the detecton level while the inverter output is off. Detection level : Approx . 210 V or less (230 V 3-phase) Approx. 170 V or less (240 V single-phase) Approx. 420 V or less (460 V 3-phase)
Overvoltage Protection
Monitor display appears when the main circuit DC voltage rises above the detection level while the inverter output is off. Detection level : Approx. 410 V or more (230 V class 3-phase, 240 V class single-phase) Approx. 820 V or more (460 V class)
Cooling Fin Overheat (Only for Types of Forced Cooling)
Monitor display appears when the cooling fin overheats : due to intake air temperature rise .
Overtorque Detection
Monitor Display (UV) ; ; ,~, (Blink)
(OV) tot u (Blink)
(OH) ~,
N (Blink)
Fault Contact Output
Non Operation
Non Operation
Non Operation
This function is used to protect the machine (OL3) and to monitor the inverter output torque . Non The motor operates according to selection Operation of constant (No. 40) when the inverter 3 L 3(Blink) output current exceeds the overtorque detection level . The monitor blinks when
"operation continues" is preset . Simultaneous Forward and Reverse Run Commands
When forward and reverse run commands are simultaneously closed for a period of time exceeding 500 ms, the inverter is stopped according to the preset stop method [constant (No. 01)]
(EF) ~_
L F (Blink)
Non Operation
Page 153
2. DIGITAL OPERATOR (JVOP-114) (Conttd) Protective Function
Motor Overload Protection
Error Causes
Overload, long operation at low speed, improper V/f characteristic setting. Motor rated current [constant (No . 19)] setting is wrong.
Inverter
Overtorque Motor current exceeds the preset Detec- value because of machine error or lion* overload.
External Fault Signal Input
External fault condition occurred.
I
Acton to be Taken Investigate the cause of overload and review the operation pattern, VA characteristic, and motor/inverter capacities . (if inverter is repeatedly reset ofper an overload occurs, the inverter may fault. Investigate and correct the cause of overload before restart.). Set the rated current of motor nameplate value to constant (No. 19). If the above measures are not effective, lower the carver frequency [constant (No 43)] . Check the use of machine. Correct the overload cause or set a higher detection level [constant (No. 41)] which is within the allowable range.
Correct the cause of the fault input. Record all data of [ then make initialization . Turn OFF power, then turn ON r ~r r~~ ~
Control Circuit Fault t
External noise Excess vibration or shock again . If an error is persistent, replace the inverter .
* For overtorque detection (OL3), fault display or alarm display can be selected according to the constant (No. 40) setting. For details, refer to "OVERTORQUE DETECTION FUNCTION" on page 124 t For details of control circuit faults, refer to Table 1 9 "Details of CPF Display" on page 49. to ,'; S indicate the contents of digital operator display.
Page 154
2. DIGITAL OPERATOR (J%fOP-114) (Cont'd) Protective Function Low-voltage Protection (Main Circuit Voltage Insufficient)
Overvoltage Protection
Error Causes
Input voltage drop
Motor current exceeds the preset value because of machine error or overload
Acton to be Taken - Check the main circuit DC . Check power supply capacity and power system.
Check the use of machine . Correct the overload cause or set a higher detection level [constant (No. 41)] which is within the allowable range r E
Cooling Fin Overheat (Only for Types of Forced Cooling)
Defective cooling fan Intake air temperature rise Clogged filter
Replace the cooling fan and clean the filter . Intake a~ temperature : 104° F(40t) or less
Overtorque Detection
Motor current exceeded the set value because of machine fault or overload .
Check the driven machine and correct the cause of the fault or increase the set value [constant (No. 41)J up to the machine allowable value.
' Operation sequence error ' 3-wire/2-wire selection error
Recheck the control sequence. - Recheck constant settings (Nos . 32, 33 and 34).
Simultaneous
Forward and Reverse Run Commands
Page 155
2 . DIGITAL OPERATOR (J'VOP-114) (Cont'd) Protective Function External Baseblock Signal Input (Main Circuit Transistor Instantaneous Shut-off)
om
10 During AccelCL a) eration
~o
° Ec
0 ,0 2 Cx
C~ U
Explanation
When an external baseblock signal is input, (BB) the motor coasts to a stop. When the external baseblock signal is removed, the inverter output is immediately turned on at ! ! (Blink) ~~ u the previously set frequency
Output frequency is decreased when 160% of the inverter rated current or greater is required by the load. This prevents motor and inverter overload (OL 1, OL2) . When current is reduced below 160%, inverter acceleration is enabled .
During Deceler~D If 0 a) anon
Deceleration is stopped when the DC voltage is caused to rise by motor regenerative energy . This prevents overvoltage trips (OV) . When DC voltage decreases, deceleration to the set value resumes.
a
Q 'c
Fault Contact Output Non Operation
Inverter acceleration is stopped when 170% or more of the inverter rated current is required by the load This prevents overload protection (OL 1, OL2) or overcurrent (OC) from occuring. When current is reduced to less than 170%, acceleration is enabled
During -0o Normal ~ oN 'o Operation E
Monitor Display
Non Operation
Page 156
2 . DIGITAL OPERATOR (JVOP-114) (Cont'd) Protective Function
Error Causes
Acton to be Taken
External Baseblock Signal Input (Main Circuit Transistor Instantaneous Shut-off) L
0
During Acceleration
UO
EC: 00 '
During Normal Opero anon cn .~' m
> a-00
UA a d~ D Lo
During Decelero - ation ..c
U> do
Insufficient power for accel/ decel Overload Phase loss
SE't proper accel/decel time [constant (Nos. 09 to 12)] for smooth operation . For stall prevention during normal operation, lighten the load or increase inverter capacity .
Page 157
Varispeed-606PC3
INSTRUCTION MANUAL TOKYO OFFICE New Pier iakesrba South Tower 1-16-1 Kaigan MmatokU Tokyo 105 Japan Phone 81-3-5402 4511 Fax 81 3-5402-4580 YASKAWA ELECTRIC AMERICA, INC Chicago-Corporate Headquarters 2942 MacArthur Blvd Northbrook IL 60062-2028 U S A Phone 1-847-291 2340 Fax 1-847-498-2430 Chicago-Technical Center 3160 MacArthur Blvd Northbrook IL 60062-1917 U S A Phone 1-847-291-0411 Fax 1-847-291-1018 MOTOMAN INC 805 Liberty Lane West Carrollton, OH 45449 U S A Phone 1-513-847-6200 Fax 1-513-847-6277 YASKAWA ELETRICO DO BRASIL COMERCIO LTDA Avenida Brigaderro Faria Lima 1664 5 CJ 504!511 Sao Paulo Braiil Phone 55-11-815-7723 Fax 55-11-870-3849 YASKAWA ELECTRIC EUROPE GmbH Am Kronberger Hang 2 65824 Schwalbach Germany Phone 49-6196 569-300 Fax 49-6196-888-301 Motoman Robotics AB Box 504 S38525 rorsas Sweden Phone 46-486-10575 Fax 46-486 41410 Motoman Robotec GmbH Kammerfeldstrape 1 85391 Allershausen Germany Phone 49-8166-900 Fax 49-8166-9039 YASKAWA ELECTRIC UK LTD 3 Drum Mans Park Orchardton Woods Cumbernauld Scotland G68 9LD U K Phone 44-1236-735000 Fax 44-1236-458182 YASKAWA ELECTRIC KOREA CORPORATION Park Nam Bldg 901 188-3 1-Ga Eulliro Joong-Gu Seoul Korea Phone 82-2-776-7844 Fax 82-2-753-2639 YASKAWA ELECTRIC (SINGAPORE) PTE LTD 151 Lorong Chuan, #04-01 New tech Park Singapore 556741 Singapore Phone 65-282-3003 Fax 65-289-3003 YATEC ENGINEERING CORPORATION Shen Hsiang Tang Sung Chiang Building 10F 146 Sung Chiang Road Taipei Taiwar Phone 886-2-563-0010 Fax 886-2-567-4677 BEIJING OFFICE Room No 301 Office Building of Beijing International Club, 21 Jianguomenwai Avenue, Beijing 100020 China Phone 86-10-532-1850, Fax 86-10-532-1851 SHANGHAI OFFICE Room No 8B Wan Zhong Building 1303 Yan An Road (West) Shanghai 200050 China Phone 86-21-6212-1015 Fax 86-21-6212-1326 YASKAWA JASON (HK) COMPANY LIMITED Rm 2916 Hong Kong Plaza 186-191 Connaught Road West, Hong Kong Phone 852-2858-3220 Fax 852-2547-5773 TAIPEI OFFICE Shen Hsiang Tang Sung Chiang Budding 10F 146 Sung Chiang Road Taipei Taiwan Phone 886-2-563-0010 Fax 886-2-567-4677