Page 41

1 . VS-606PO3 INVERTER MAIN UNIT (Contod) IMPORTANT Lead size should be determined considering voltage drop of leads . Voltage drop can be obtained by the following equation : select such lead size that voltage drop will be within 2% of normal rated voltage . phase-to-phase voltage drop (V) =F X lead resistance ( 0 /km) X wiring, distance (m) X current (A) X 10 Insertion of power supply coordination AC reactor When the power supply capacity exceeds 600 kVA, connect an AC reactor at the inverter input side for power supply coordination. This reactor is also effective for power factor improvement of the power supply. Refer to Par. 1 .10 "OPTIONS AND PERIPHERAL UNITS" on page 60. Wiring length between inverter and motor If total wiring distance between inverter and motor is excessively long and inverter carrier frequency (main transistor switching frequency) is high, harmonic leakage current from the cable will increase to affect the inverter unit or peripheral devices. If the wiring distance between inverter and motor is long, reduce the inverter carrier frequency as shown below . Carrier frequency can be set by constant No . 43 . For details, refer to "CARRIER FREQUENCY" on page 125 . Carrier frequency is set to 10 kHz at the factory prior to shipping. Wiring Distance between Inverter and Motor

Up to 30 m up to 50 m

Up to 100 m

100 m or more

Allowable Carrier Frequency (Constant No 43 set value)

15 kHz or less (6)

10 kHz or less (4)

5 kHz or less (2)

2 5 kHz or less (1)

Page 42

1 . VS-606PC3 INVERTER MAIN UNIT (Cont'd) (6) Wiring

(a) Main circuit input/output (1) Phase rotation of input terminals Ll, L2, L3 is available in either direction, clockwise or counterclockwise . (2) When inverter output terminals T1, T2, and T3 are connected to motor terminals T1, T2, and T3, respectively, motor rotates counterclockwise, when viewed from opposite drive end, upon forward run command. To reverse the .rotation, interchange any two of the motor leads. (3) Never connect AC main circuit power supply to output terminals T1, T2, or T3 . Inverter may be damaged. (4) Care should be taken to prevent contact of wiring leads with the VS-606PG3 cabinet, for a ground fault or a short-circuit may result. (5) Insert an L noise filter to the VS-606PG3 output, but never connect power factor correction capacitor, LC or RC to VS-606PG3 output. (6) Be sure to tighten the main circuit terminal screws. (7) Be sure to separate the main circuit wiring from inverter and peripheral device control lines . Otherwise, it may cause the devices to malfunction .

Page 43

t . VS-606PC3 INVERTER MAIN UNIT (Cont - d) (b) Grounding

Ground the casing of the VS-606PC3 using ground terminal G. (1) Ground resistance should be 100 SZ or less . (2) Never ground VS-606PC3 in common with welding machines, motors, or other largecurrent electrical equipment, or a ground pole . Run the ground lead in a conduit separate from leads for large-current electrical equipment. (3) Use the ground leads which comply with AWG standards and make the length as short as possible. (4) Where several VS-606PC3 units are used side by side, all the units should be grounded as shown in (a) or (b) of Fig 1 .4. Do not form a loop with the ground leads as shown in (c) .

(a)

GOOD

QW 1

LM4

(b) GOOD

(c) POOR

Fig. 1 .4 Grounding of Three VS-6()6PC3 Units

Page 44

t . VS-606PO3 INVERTER MAIN UNIT (Confd) 1 .5 .4 Control Circuit CAUTION Low voltage terminals shall be wired with Class I Wiring. (1) Control circuit wiring The control signals are connected by screws. Refer to Fig. 1 .2 for I/O signals and screw terminal numbers. The terminal functions shown in the figure indicate standard setting prior to shipping . Since operation mode from the digital operator is set for the model with the digital operator, it is necessary to change the control constants when operation is performed from the control circuit terminals . For details, refer to "OPERATION MODE SELECTION" on page 96 . For the model without digital operator (with indicating cover), operation mode from the control circuit terminals is the standard setting preset at the factory prior to shipping.

Page 45

i . VS-606PC3 INVERTER MAIN UNIT

(Cont"d)

(2) Controrl circuit terminals (factory preset) Table 1 .5 Control Circuit Terminal Functions Classification Te- ;^al

Sequence Input Signal

Forward run /stop signal

Forward run at "closed", stop at "open"

2

Reverse run/stop signal

Reverse run at "closed", stop I at "open"

3

Fault reset input

4

10 8

_

9 11 13

Sequence output

Signal

Reset at Multifunction closed contact input I Fault at External fault signals "closed" available to Effective at select"` Multi-step speed ref . 1 "closed" Sequence control Common terminal for input common terminal se;: #j=u*tw - )ut Power supply terminal for frequency setting Speed ref power supply 0 to + 10V/Max. output frequenc Frequency ref. 4 to 20 mA/Max . output fregency Common terminal for 0V control circuit I During running

14

Frequency agreed signal

7

Photo-coupler output

FLT-A FLT-B

Analog output Signall

Funcl ion

1

5

Analog Input Signal

Signal Name common

Fault signal contact output

FLT-C

Fault signal contact output common

12

Frequency meter

11

Common

Multifunction photocoupler output: two 'L" level at set frequency=output signals available to frequency select t

Signal Level

Photo-coupler insulation input 24 VDC 8 mA

+12 V IAlbwable current 20 mA max.) 0 to + 10 V (20kQ) 4 to 20 mA 250

"L" level at run

Photo-coupler output +48 V 50 mA or less

Common terminal for sequence output

Poss,ole to se:ecl.

!he ',,rcton as t,or -LA fu # output "Closed" between A and C at "ault "oxen" between function contact output

Contact capacity 250 VAC 1 A or less 30 VDC . 1 A or less

B and C a; `aul;

0 to 10 V/max. output frequency Possible to select current meter output

0 to 11 V max. 2 mA or less

* For details, refer to "MULTIFUNCTION CONTACT INPUT FUNCTION SELECTION" on page 115. r For details, refer to "MULTIFUNCTION OUTPUT FUNCTION" on page 121 . For details, refer to "MULTIFUNCTION ANALOG OUTPUT MONITOR SETTING" on page 110. it For details, refer to "MULTIFUNCTION OUTPUT FUNCTION" on page 121 .

-33-

Page 46

i . VS-606PC3 INVERTER MAIN UNIT (Confd) Control circuit terminal arrangement oooo00 8 o

FLT FLT FLT 1 -A -B -C

9

2

10 11

3

4

12

5

13 14

6

7

(3) Precautions on control circuit wiring

Separate the control signal line from power lines . Otherwise, it may cause a malfunction . For frequency setting signal (analog), use shielded lead and conduct termination sufficiently. SHIELDED SHEATH r

TO VS-606PC3 SIGNAL -~ TERMINALS L

OUTER JACKET

Z5

TO SHIELD ~ ~ WRAP BOTH ENDS SHEATH OF SHEATH WITH TERMINAL INSULATING TAPE (TERM. G) CRIMP CONNECTION

TO ~ EXTERNAL CIRCUIT DO NOT CONNECT

Page 47

1 . VS-608PC3 INVERTER MAIN UNiI" (Cqnt'd} 1 .6 OPERATION 1 .6 .1 Pre-operation Check

Check the following items after completion of installation and wiring

(1) Proper wiring. Double check that the power supply is not connected to the output terminals T1, T2 and T3. (2) No shortcircuit due to wiring contamination (dust, oil, etc.). (3) Screws and terminals are tightened. (4) For safe operation, the motor should be uncoupled from the load. Pay close attention to output current when the motor is operated with the load coupled. (5) Wiring is not grounded. (6) Run command is not input. When the forward/reverse run command is input in the operation mode (factory setting for the model with indicating cover} from the control circuit terminal, the motor is activated automatically after the main circuit power supply is turned on. Turn on the inverter only after making sure that the run command is not input.

Page 48

t . VS-606PC3 INVERTER MAIN UNIT (Cont'd) 1 .6 .2 Pre-operation Setting

Since the standard inverter models are provided with the values indicated in Par.2 .8 (see page 84 and beyond), the digital operator (J VOP-114) must be used in order to change the constants from the initial values LU Lilt; VQILIGJ III QLLVIUdllUG WIL.ll Lilt IUdU JPGL111LdLIVIIJ . (1)

Preset values prior to shipping The following describes the functions and initial constant set values which are often used for operation . (a) Output frequency and accel/decel time The maximum output frequency is set to 60 Hz and accel/decel time to 10 seconds at the factory prior to shipping. To change the values, refer to "ACCEL/DECEL TIME SETTING" on page 105 .

OUTPUT FREQ. (Hz) 10 sec

I

DECEL TIME Fig . 1 .6 Output Frequency and Accel/Decel Time

M h= u-1g F.

Page 49

1 . VS-606PC3 INVERTER MAIN UNIT (Cont'd) (b) Frequency setting signal and output frequency Fig. 1 .7 shows the inverter output frequency change as a result of changes of the input voltage signal at terminal ® or current at terminal ~9 .

(c) V/f characteristics Fig. 1 .8 shows the output voltage for inverter output frequency. When its characteristic (max . voltage / frequency) differs from that of the optimum motor, refer to "V/f CHARACTERISTIC SETTING" on page 102.

60

230

OUTPUT FREQ. (Hz )

i i i 15,/ 0 0.25 i

,

10V

0 1 5

FREQ. SETTING VOLTAGE (V)

Fig. 1 .7 Frequency Setting Signal and Output Frequency

(2)

OUTPUT VOLTAGE

OUTPUT FREQ (Hz)

60

Note ; For 460 V class, the value is twice that of 230 V class. Fig . 1 .8 V/f Characteristics

Motor rated current setting Since the inverter is provided with an electronic thermal overload to protect the motor from overheating, the motor rated current should be programmed into constant (No .19). YASKAWA standard 4-pole motor current value is set as the initial value . For details, refer to "ELECTRONIC THERMAL OVERLOAD PROTECTION" on page 109. Note : Provide a thermal overload relay or thermal protector when more than one motors are operated simultaneously .

Page 50

t . VS-606PC3 INVERTER MAIN UNIT (Coht"d) 1 .6 .3 Test Run Method

The inverter can be operated i n the following two ways. The model with digital operator is set to "OPERATION MODE BY DIGITAL OPERATOR" and the model without digital operator (with indicating cover) is set to Vr Li~ti 1 lkJll lV1kJliju- r'itkjj.Vl %..kill 1 1Xkjl_j

TERMINAL" prior to shipping.

V1 1

Run by digital operator (Standard setting of model with digital operator)

Run by control circuit terminal input (Standard setting of model with indicating cover)

This method is to operate the inverter by using the RUN (run command) key, etc . of the digital operator. Since this operation mode is set at the factory prior to shipping, operation can be performed only by main circuit wiring . For details of the operation method, refer to Section 2 "DIGITAL OPERATOR" beginning on page 64.

This method is to operate the inverter by frequency setter or operation switch connected to the control circuit terminal. To perform operation by control circuit terminal input of the model with digital operator, change the operation mode to "OPERATION FROM CONTROL CIRCUIT TERMINAL" (No . 01=0000).

POWER SUPPLY -o

INVERTER 606PC3

MOTOR

POWER SUPPLY

IM FWD SIGNAL REV SIGNAL

FREQ. SETTER

INVERTER 606PC3

MOTOR IM

Ujz

92