Page 31

1 . VS-606PC3 INVERTER MAIN UNIT (Cont'd) Terminal position Main circuit and control circuit terminal blocks are shown below. Usually the terminal Nos . are shown on the terminal No. nameplate . For some inverters, the terminal Nos. are printed on the printed board. The location of terminal blocks for both enclosed wall-mounted type (NEMA 1) and water and dust tight type (NEMA4) is the same . The photo shows the enclosed wall-mounted type (NEMA 1) .

CONTROL CIRCUIT TERMINAL BLOCK (M3 .5) MAIN CIRCUIT TERMINAL BLOCK (M4 OR M5)

692-365

GROUNDING\ TERMINAL CHARGE LAMP

1 .5.2 Standard Wiring Diagram

Models with digital operator can be operated from the digital operator only by main circuit wiring . When these models are operated by control circuit terminals, control constant change is required. For details, refer to "OPERATION MODE SELECTION" on page 96 . Models without digital operator (with indicating cover) are preset in operation mode from control circuit terminals at the factory prior to shipping .

Page 32

t . VS-606PC3 INVERTER MAIN UNIT (Confd) MAIN CIRCUIT POWER SUPPLY ONLY TERMINAL L1, L2 FOR SINGLE-PHASE POWER SUPPLY

BRAKING RESISTOR ;OPTION)*

MCCB r---

L1 --o L2 -~ L3 --o FORWARD RUN/STOP

1

I I I

FAUL T RESET _XTE NAL FAULT

I

SPEED SREP TEP t-0

1

I

4

VS-606PC3

'

I

3 4

I I i I l

5

M ULTIFUNCTION CONTACT INPUT

I

10

,

8 9 u iv + iu vI I --

4 TO 20 rrA

-

P

P

I

I I

MONK ; cJF,

~F

1

>

~

1 roo--~

SHIELDED LEAD CONNECTION TERMINAL AIN CI CU T ) WI TH

2c ~~A

RE~f+ l12 v MASTER REF E ) 4-O0 A E RE ) (VOLTA

G

6URREN T REF _ '4-20 mA '.2500) OV

1

J

APALOGOUTPUT 0 TO + 10 VDC FACTORY SETTING IS 'OUTPUT FREQUENCY"

MULTIFUNCTION CONTACT OUTPUT CONTACT CAPACITY LESS THAN 1 A FOR 250 VAC AND 30 VDC FACTORY SETTING IS "FAULT SIGNAL"

FLT

SEQUENCE COMMON

POWER f 1 ~

J

- _-----

FL T-B

G VOLUME2 VOLUME 1 '

IM

T3~

1 ANALOG

.0

FREQUEN - ~ cv CY REF .

T1 o T2 o G

1

Y

B2

'

RUN/SOP

MA5 I tt-t

B1/p+

L1 o L2 o L3 o

-13 DURING RUN 14 j FREO EN(:Y 7ACx~ AGREEMENT

ANALOG INPUT MODULE JVOP-1 15 !OPTION Fig. 1 .2 Standard Wiring Diagram

1

MULTIFUNCTION PHOTO-COUPLER I, OUTPUT : LESS THAN 48 V 50 mA

Page 33

1 . LAS-606PC3 INVERTER MAIN UNIT (Contod) Notes 1.

indicates shielded leads and 1 ^ gyp twisted-pair shielded leads .

2 . External terminal 10 of + 12 V has maximum output current capacity of 20 mA. 3. Terminal symbols : 0 shows main circuit ; O shows control circuit . 4 . Terminal point 6 (sequence common) is isolated from terminal point 11 (OV) . * Set thermal overload relay between braking resistor and inverter when using braking resistor without thermal overload relay (ex. : type ERF-150WJ, option) to protect it from overheating . Use sequencer to break power supply side on thermal overload relay trip contact when using braking resistor . Also, when using braking resistor unit with thermal overload relay (type LKEB, option), use sequencer to break power supply side on thermal overload relay trip contact .

T Volume 1 : For frequency setting

± Volume 2 : Resistor to reduce the voltage from +12V to +10 V . Considering the voltage drop by wiring impedance, power supply voltage is set to +12 V . When volume 2 is not provided

OV ' v

10V (MAX FREQUENCY) 17V

VOLUME 1

Max frequency when turning volume 1 to 80% . Even if turning more, frequency remains at the maximum . Even if +12 V loads on terminal 8, it will not damage the inverter nor affect its operation.

Page 34

1 . VS-606PC3 INVERTER MAIN UNIT (Cont'd)

1 .5 .3 Main Circuit (""Suitable for use on a circuit capable of delivering not more than 1000 rms symmetrical amperes, 240 V Max." Models with 20P1, 20P2, 20P4, BOPI, BOP2 and BON suffix only. "Suitable for use on a circuit capable of delivering not more than 1000 rms symmetrical amperes, 460 V Max." Models with 40P2 and 40P4 suffix only. "Suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical amperes, 240V Max." Models with 20P7, 21P5, 22P2, 23P7, BOP7, B 1 P5, E,2P2 and B3P7 suffix only. "Suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical amperes, 460V Max." Models with 40P7, 41P5, 42P2 and 43P7 suffix only. (1) Main circuit wiring Connect wiring as shown in Fig. 1 .3. BRAKING RESISTOR UNIT OR BRAKING RESISTOR (BOTH OPTIONAL)

F 1-tW~21 P

MCCB

B

-moo}- - , o

B2 { B1/(D 1 ---° ~L 1 3-PHASE L POWER L2 --o0 o :L2 T2 VS-606PC3 SUPPLY L3 __,^0 °. L3 ONLY TERMINAL L1, L2 FOR SINGLE-PHASE POWER SUPPLY

Fig. 1 . 3 Main Circuit Wirinig

T 1,°

T3 C' t ° o

MOTOR

IM

Page 35

7 . VS-606PC3 INVERTER MAIN UNIT (Cont'd)

(2) Main circuit terminals lx~

Table 1 .1 VS-606PC3 Main Circuit Terminals Terminal L1 L2 L3 T1 T2 T3 B 1/ p+ B2

Description

Main circuit power input "L 1 ", "L2" are used for single-phase input specifcations. Inverter output Braking resistor or braking resistor unit connector (options) Grounding (ground resistance should be 100 ohms or less)

* Use screw for frame ground .

Main circuit terminal arrangement 3-phase series (all models) L1

L2

L3 B1/Q

B2

T1

T2

T3

240 V single-phase series 240 V single-phase series NEMA 1 0.13 to 1 .5 HP (0.1 to 1 .5 kW) 3 and 5 HP (2.2 and 3 .7 kW) NEMA4 0.13 to 2 HP (0.1 to 1 .5 kW) L1 L2 B1is B2 T 1 T2 T3 B2 BLANK (Do not use

(3)

L1

L2 B1/ D

T1

T2

T3

Molded-case circuit breaker (MCCB) and Fuse for branch circuit protection Be sure to connect MCCBs or Fuses between AC main circuit power supply and VS-606PC3 input terminals L1, L2, L3 to protect wiring. Recommended ratings of MCCB and Fuse are listed in Table 1 .2. The fuses should be Listed Class RK5 fuses. When a ground fault interrupter is used, select one not influenced by high frequency . Setting current should be 200 mA or more and operating time, 0.1 sec or more to prevent malfunctions . (Example) NV series by Mitsubishi Electric Co., Ltd. (manufactured in and after 1988), EGSG series by Fuji Electric Co., Ltd . (manufactured in and after 1984) -23-

Page 36

1 . VS-606PC3 INVERTER MAIN UNIT (Cont'd) Table 1 .2 Branch Circuit Protection 0 230 V Class 3-phase Input Series VS-606PC3 Model CIMRInverter Capacity

, ;, , ,

PCU20P , "-Cb'2CP2 PCU2"-L

, , .,1-"" 1 20'P7 PCU2 ~P5 PCU22PC PCU22P2 PC''23P7

NEMA 1 NEMA4

0.3

06

1 .1

1 .9

2.5

2.8

4.2

67

03

06

1 1

1 .9

-

42

6.7

Rated Output NEMA 1 A Current NEMA4

28

08

1 5

3

5

6.5

7.3

11

175

0.8

1 .5

3

5

7.3

-

11

175

MCCB or Fuse, Class RK5

3A

5A

5A

10A

20A

20A

20A

WA

I 30A

" 240 V Class Single-phase Input Series VS-606PC3 Model CIMRInverter Capacity

PCUBOP 1

0CU80P2

QCUBC~4

PGJB0o7

-'CuB 1 P5

PCUB2P2 pCuB3P7

06

1 1

1 .9

2.5

4.2

6.7

06

1 .1

1 .9

28

4.2

-

WA

NEMA 1 NEMA4

0.3

Rated Output A Current

NEMA 1 NEMA4

0.8

1 .5

3.0

50

6.5

11 .0

17 .5

0.8

1 5

3.0

5.0

73

110

--

MCCB or Fuse, Class RK5

3A

5A

10A

20A

20A

40A

50A

9 460

03 j

V Class 3-phase Input Series VS-606PC3 Model CIMR-

PCU4OP2

PCU40P4

PCU4OP7

PCUA 1 P5

PCU42P2

PCU43P7

WA

08

1 2

2

3

37

6 1

A

1

1 6

26

4

4 8

8

MCCB or Fuse, Class RK5

4A

5A

5A

1 0A

Inverter Capacity Rated Output Current

F 1 0A

_

20A

Page 37

1 . VS-606PC3 INVERTER MAIN UNIT (Confd) (4) Surge suppressor

The surge suppressors should be connected to the coils of control relays, magnetic contactors, magnetic valves, or magnetic brake used for the VS-606PC3 periphery. Otherwise, large surge voltage occurs at switching and may cause devices to be damaged or to malfunction . Select type from Table 1 .3 . Table 1 .3 Surge Suppressors

Coils of Magnetic Contactor and Control Relay 200 V to 230 V

Large-size Magnetic Contactors Control Relay MY-2,-3 10MRON) HH-22, -23 (Fuji`, MM-2, -4(OMRON) 380 to 460 V Units

* Made by MARCON Electronics

Surge Suppressor* Model DCR2-

Specifications

Code No

50A 22E

250 VAC 0.5 p F 200 Q

C002417

10A 25C

0.

1 pF VAC 1000

C002482

50D 100B

1000 VDC 05pF 2200

0002630

Page 38

1 .,

VS-606PO3 INVERTER MAIN UNIT (Cont'd)

(5) Wire and terminal screw sizes

Use 600 V vinyl-sheathed lead or equivalent . Use 75 °C copper wires only. Low voltage terminals shall be wired with Class I Wiring.

Table 1 .4 Torque Value and Wire Size for Field Wiring Terminals " 230 V Class 3-phase Input Series Circuit

VS-606 PC3 ; CIMRNode PCU20P 1

PCU20P2

Main

Circuit

PCU20P4

PCU20P7

PCU21 P5

Sy'oo,

Terminal

L1, L2, L3, B B2, T 1 . T2, T3

M4

L1, L2, L3, B1 /0, B2, T1, T2 . T3

M4

G

G

L1, L2, L3, B1/ p, B2 . T 1 . T2, T3

PCU22P2

M4

G

L1, L2, L3, B1/p, B2, T1, T2, T3 G L1, L2, L3, B1/p, 13 2, T 1. T2, T3 G L1, L2, L3, B

PCU22PO

Screw

B2 . T 1, T2, T3

M4

M4

M4

G L1, L2, L3, B1 B2, T 1 . T2, T3

M4

G L1, L2, L3, B

PCU23P7

Control Circuit

Common to All Models

B2, T 1. T2, T3

G

1 ,o 14

FLT A, FLT B. FLT C

M4

M35

Wire Size

Torc;,e

AWG mm z

143

14-10

2to55

143

14-10

2'o 5 5

143

14-10

2tto55

14,3

14-10

2 ;o 5 5

1413

14-10

2

143

14-10

2 o55

1413

14-10

2to55

14,3

14-10

2 ;0 5 5

143

14-10

2 ;o55

14,3

12-10

3 5 :o 5 5

14,3

1L-10

2 to 5 5

14,3

12-10

35 - o55

143

12-10

3 5 to 5 5

143

12-10

3 5 to 5 5

143

10

55

143

10

55

0 9, ;

22-14

0 3 to 2

1

" Water and dust tight type (NEMA4', not provided for this model

-

0 55

Page 39

1 . VS-606PO3 INVERTER MAIN UNIT (Contod)

Table 1 .4 Torque Value and Wire Size for Field Wiring Terminals (Cont'd) " 240 V Class Single-phase Input Series Circuit

VS-606 PC3 Mood CIMR PCUBOP 1 PCUBOP2

Main Circuit

PCUBOP4 PCUBOP7 PCUB 1 P5 PCUB2P2 PCUB3P7'

Control Circuit

Common to All Models

Terminal

Wire Size Torque

AWG mm 2

143

14-10

2 to 5 5

143

14-10

2 to 5 5

143

14-10

2 to 5 .5

143

14-10

2 to 5 5

143

14-10

2 to 5 5

143

14-10

2 to 5 5

143

14-10

2 to 5 5

143

12-10

3 5 to 5 5

143

12-10

35to55

143

12-10

3 5 to 5 5

M5

2 24

10-8

5 5 to 8

M4 M5

143

10-8

5 5 to 8

224

8

8

G

M4

143

10-8

5 5 to 8

1 Lo 14 FLT-A, FLT-B, FLT-C

M3 5

0 95

22-14

0 3 to 2

Symbol L 1, L2, B 1 / O , B2, T 1, T2, T3 G L 1, L2, B 1 / O , B2, T 1, T2, T3 G L 1, L2. B 1 / 0 , B2, T 1, T2, T3 G L 1, L2, B 1 / O , B2, T1, G T2, T3 L1, L2, 131/9 , B2, T1, T2, T3 G L1, L2, 8 1/p , B2, T 1, T2, T3 G L1, L2, B1/ 0+, B2, T 1 . T2, T3

Screw M4 M4 M4 M4 M4

Water and dust tight type (NEMA4) not provided for this model

Page 40

t . VS-606PC3 INVERTER MAIN UNIT (Contrd)

Table 1 .4 Torque Value and Wre Size for Field Wring Terminals (Cont'd) 0 460 V Class 3-phase Input Series Circuit

Main Circuit

Syr~boi

Screw

PCU40P2

L1, L2, L3, B1/3, B2, T 1, T2, T3

M4

PCU40P4

L1, L2, L3, B1/p+ , B2, T1, T2, T3

PCU40P7 PCU41 P5 PCU42P2 PCU43P7

Control Circuit

Terminal

VS-606 PC3 Mode CIMR-

Common to All Models

G G

L1, L2, L3, B1 B2, T 1, T2, T3

G

L1, L2, 1-3, B1 B2, T 1, T2, T3

G

L1, L2, L3, B B2, T 1, T2, T3

G

L1, L2, L3, B1/O, B2, T 1, T2, T3

G 1 to 14 FLT-A, FLT-B, FLT-C

M4

I

M4 M4 M4 M4 M3 5

Wire S ize

Torque

AWG mm z

143

14-10

2to55

1Q

14-10

2 -.o55

1Q

14-10

2 :055

143

14-10

2 :0 5 5

1 ~3

14-10

2 `.° 5 5

163

14-10

2 :o 5 5

1 ~3

1a-10

2 to 5 5

163

14-10

2 to 5 5

1!3

14-10

2zo55

1 !3

14-10

2 to 5 5

1 ~3

14-10

2 ~° 5 5

1 '-3

12-10

0 ,35

22-14

35to55 0 3 to 2