Page 111
APPENDIX B - FORMULAS B
INTRODUCTION
This appendix contains the actual formulas used to calculate M-Drive Speed Control values, and is divided into two sections. Symbols defines each symbol used by these formulas, and Speed Control Formulas provides 3 methods of calculating Speed Control Equations for Master, Follower and Auxiliary Reference Frequency Formats.
SYMBOLS SP Setpoint EU Engineering Unit (Maximum Setpoint) Rf RPM of Subject Shaft Rfmx Maximum Rf Pf PPR of gear on Subject Shaft Re RPM of External Reference Shaft Remx Maximum Re Pe PPR of gear on External Reference Shaft Ra RPM of Auxilliary Reference Shaft Ramx Maximum Ra Pa PPR of gear on Auxilliary Reference Shaft C Offset constant ER External Reference Frequency FB Feedback Frequency AX Auxilliary Reference Frequency SPEED CONTROL FORMULAS
These equations are stated using three different methods: General, Hz, and RPM.
MASTER FORMAT ENERAL: S$P = _Rf
EU Rfmx
H SP * Rimx*Pf = FB EU 60
RPM SP * Rimx = Rf EU
Page B-1
Page 112
FOLLOWER FORMAT
GENERAL: SP* Re = Rf EU Remx Rfmx
Hz: SP * ER*Rimx*Pf = FB EU Remx*Pe RPM: SP * Re*Rfmx = Rf
EU Remx
AUXILIARY REFERENCE FREQUENCY FORMAT
GENERAL: SP* Re + Ra + C = Rf EU Remx Ramx (Rimx*Pf)/60 Rfmx
Hz: SP * ER*Rimx*Pf + AX*Rimx*Pf + C = FB EU Remx*Pe Ramx*Pa RPM: SP * Re*Rimx + Ra*Rimx + _C = Rf
EU Remx Ramx, - Pf/60
Page B-2
Page 113
APPENDIX C - CODE LIST (COMPLETE TEXT) C
INTRODUCTION
This appendix provides in numeric order a complete list of all control and monitor code select variables present in the M-Drive. The Code Select Procedure is also provided.
CODE SELECT PROCEDURE
The Code Select Procedure indicates how the Operator gains access to the various control and monitor parameters through their unique identification codes. Opening the lower door on the front of the M-Drive keypad exposes the programming keypad.
Accessing the desired parameter is a simple procedure:
1) Press the Code Select Key. 2) Enter the desired parameter code number. 3) Press the Enter Key.
At this point, the two digit code is displayed in the lower display window and the existing parameter value is displayed in the upper four digit display window. In addition, the keypad is enabled for changing the desired parameter. To make a change, simply enter the new value and press the Enter Key.
Page C-1
Page 114
1 - PRIMARY SETPOINT 1
Primary Setpoint 1 is invoked when the M-Drive is in the Primary Scaling Mode and the Primary Setpoint Select switch input is open. This setpoint is the absolute setpoint if the Primary Scaling Mode is programmed as a Master Scaling Mode. This setpoint is the multiplier ratio if the Primary Scaling Mode is programmed for Follower Scaling Mode.
This parameter is entered in engineering units. The decimal point location and scaling for this entry is set up through the Scaling procedure (Code Select 20).
2 - PRIMARY SETPOINT 2
Primary Setpoint 2 is invoked when the M-Drive is in the Primary Scaling Mode and the Primary Setpoint Select switch is closed. This setpoint is the absolute setpoint if the Primary Scaling Mode is programmed as a Master Scaling Mode. This setpoint is the multiplier ratio if the Primary Control Mode is programmed for Follower Scaling Mode.
3 - SECONDARY SETPOINT 1 Secondary Setpoint 1 is invoked when the M-Drive is in the Secondary Scaling Mode and the Secondary Setpoint select switch is open. This setpoint is the absolute setpoint for the Master Scaling Mode and the multiplier ratio for the Follower Scaling Mode.
4 - SECONDARY SETPOINT 2 Secondary Setpoint 2 is invoked when the M-Drive is in the Secondary Scaling Mode and the Secondary Setpoint select switch input is closed. This setpoint is the absolute setpoint for the Master Scaling Mode and the multiplier ratio for the Follower Scaling Mode.
5 - JOG SETPOINT
This is the setpoint source for Jog operation. This entry is always entered in RPMs.
6 - OUTPUT SETPOINT
Output Setpoint is the setpoint source when the Direct Scaling is invoked by either the Primary or Secondary Scaling Modes. This setpoint directly sets the output level, in percent, of the Drive Output to the motor.
Page C-2
Page 115
10 - MINIMUM LIMIT This parameter sets the minimum level of RPMs for Operation. Although it is possible to enter a setpoint below this level, the control will always attempt to maintain a speed at or above the minimum limit except to recover position error.
11 - MAXIMUM LIMIT This parameter sets the maximum level of RPMs for operation. Although it is possible to enter a setpoint above this limit, the control will always attempt to maintain a speed at or below the maximum limit except to recover position error.
12 - LOW ALARM
This parameter sets the RPM level at which the Low Alarm output is energized. The output will energize when the feedback RPMs are at or below this level.
13 - HIGH ALARM
This parameter sets the RPM level at which the High Alarm output is energized. The output will energize when the feedback is at or above this RPM level.
14 - ERROR ALARM 1 - RAMPED ERROR This parameter establishes the error band (Ramped Reference minus feedback) in
RPMs at which the Error Alarm 1 output is energized. Any positive or negative error at or above this level will energizes the output.
15 - ERROR ALARM 2 - SCALED ERROR
This parameter establishes the error band (Scaled Reference minus feedback) in RPMs at which the Error Alarm 2 output is energized. Any positive or negative error at or above this level will energize the output.
16 - ACCELERATION TIME
Acceleration Time determines the acceleration rate of the setpoint. The number entered is the amount of time required to increase the setpoint from 0 to 2000 RPMs.
Page C-3
Page 116
17 DECELERATION TIME
Deceleration Time determines the deceleration rate of the setpoint. The number entered is the amount of time (in seconds) required to decrease the setpoint from 2000 to O RPMs.
18 - LAG PULSE LIMIT
The Lag Pulse Limit sets a maximum pulse error count for the difference between the idealized feedback pulses minus the Feedback pulses. It may not always be desirable to recover all of the position error lag. Set this parameter to the desired lag pulse limit.
19 - LEAD PULSE LIMIT The Lead Pulse Limit sets a maximum pulse error count when the Feedback pulses exceed the idealized feedback pulse count. Set this parameter to the desired lead pulse limit.
20 - ENGINEERING UNITS (PRIMARY SETPOINT) This is the desired Engineering Units scaling number for the primary Scaling Mode setpoint.
21 - ENGINEERING UNITS (SECONDARY SETPOINT) This is the desired Engineering Units scaling number for the Secondary Scaling Mode setpoint.
22 - ENGINEERING UNITS (PRIMARY DISPLAY)
This is the desired Engineering Units scaling number for the Primary Scaling Mode display.
23 - ENGINEERING UNITS (SECONDARY DISPLAY)
This is the desired Engineering Units scaling number for the Secondary Scaling Mode display.
29 - RECOVERY MULTIPLIER The Recover Multiplier determines the rate at which the pulse error is reduced to zero.
This parameter multiplied by the pulse error count is the number by which the speed setpoint is adjusted every 100 milliseconds.
Page C-4
Page 117
30 - PPR (EXTERNAL REFERENCE INPUT)
This number should be set for the Pulses per Revolution of the External Reference Frequency Input.
31 - PPR (FEEDBACK INPUT)
This number should be set for the Pulses per Revolution of the Feedback Frequency Input.
32 - PPR (AUXILIARY INPUT)
This number should be set for the Pulses per Revolution of the Auxiliary Frequency Input if present.
33 - MAX RPM (EXTERNAL REFERENCE INPUT: PRIMARY MODE)
This parameter should be set for the maximum RPMs of the External Reference Frequency Input when operating in the Primary Scaling Mode.
34 - MAX RPM (FEEDBACK: PRIMARY MODE)
This parameter represents the maximum RPMs of the Feedback Frequency Input when operating the Primary Scaling Mode.
35 - MAX RPM (AUXILIARY INPUT: PRIMARY MODE)
This parameter represents the maximum RPMs of the Auxiliary Frequency Input when operating in the Primary Scaling Mode.
36 - MAX RPM (EXTERNAL REFERENCE INPUT: SECONDARY MODE)
This parameter represents the maximum RPMs of the External Reference Input when operating in the Secondary Scaling Mode.
37 - MAX RPM (FEEDBACK: SECONDARY MODE)
This parameter represents the maximum RPMs of the Feedback Frequency Input when operating in the Secondary Scaling Mode.
Page C-5
Page 118
38 - MAX RPM (AUXILIARY INPUT: SECONDARY MODE)
This parameter represents the maximum RPMs of the Auxiliary Frequency Input when operating in the Secondary Scaling Mode.
40 - TACH
Tach is the feedback displayed in scaled engineering units. The feedback input is read by the M-Drive every 10 milliseconds. The readings are summed and averaged for one second before displaying.
41 - EXTERNAL REFERENCE INPUT
The External Reference Input displays the frequency of this input in hertz (pulses per second). The number displayed is not averaged. It represents the frequency calculation from the prior 10 milliseconds before the display update. Because it is not averaged over the display update period, it appears less stable than the Tach display due to sensor irregularities or other system dynamic errors.
Note: Codes 41, 42, 43, 45 and 46 may contain numbers larger than 9999. When this occurs, the value is displayed differently. For example, a "10.00." display indicates 10,000 hertz.
42 - AUXILIARY FREQUENCY INPUT
The Auxiliary Frequency Input displays the frequency of this input in hertz (pulses per Second). This display is not averaged. It is a 10 millisecond number. See Note above.
43 - FEEDBACK FREQUENCY INPUT
The Feedback Frequency Input displays the feedback input in hertz (pulses per second). The number displayed is not averaged over the display period. itis a 10 millisecond calculated number. See Note above.
44 - DEVIATION (ERROR)
The Deviation display is the difference between the setpoint and the feedback (Ramped Reference (46) - Feedback (43)). It is also a 10 millisecond calculated variable.
Page C-6
Page 119
45 - SCALED REFERENCE The Scaled Reference is the scaled setpoint number in hertz. The Scaled
Reference is the calculated variable input to the Acceleration /Deceleration routine. See Note on Page C-6.
46 - RAMPED REFERENCE
The Ramped Reference is the calculated output of the Acceleration/Deceleration routine in hertz. The Ramped Reference is the setpoint input to the control algorithm. See Note on Page C-6.
47 - OUTPUT
The Output variable represents the level of the Drive Output to the motor. The Output variable is represented in percent of full output.
48 - TRIM OUTPUT
The Trim Output is the calculated output of the control algorithm. It is equivalent to the total output minus the feedforward {output(47) = Trim Output (48) + Feedforward}. The Trim Output is represented in DAC bits where 4096 equals 100% output, 2048 equals 50% output, etc.
49 - PULSE ERROR COUNT
The Pulse Error Count indicates the difference between the number of External Reference pulses received and the number of Feedback pulses received during the Follower Scaling Mode of operation. It is an indicator of the position error between the lead and follower devices. This error is cleared to zero when the M- Drive enters a stop state.
50 - ACTIVE MODE The Active Mode is an M-Drive status indicator of the active scaling mode. 0 - Direct Mode 1 - Master Mode 2 - Follower Mode 3 - Offset Mode
A description of these modes is available in the Control Parameters - Scaling Mode Control section of the manual.
Page C-7