51 - ENTRY ERRORS

The Entry Errors display can be used to indicate why a keypad entry was not accepted by the M-Drive.

0 - No Error

1 - Invalid Code

2 - Above Maximum Value 3 - Below Minimum Value 4 - Keypad Lockout

5 - Entry Timeout

If an entry is not accepted by the M-Drive, the last valid value is displayed. Code 51 can be used to interrogate why the new value was not accepted.

52 - ALARM STATUS

The Alarm Status display indicates the status of the limits and alarms in the M-

Drive. The presence of the number associated with that alarm indicates that alarm is active.

1 - Low Limit

2 - High Limit

3 - Low Alarm

4 - High Alarm

5 - Error Alarm 1 6 - Error Alarm 2 7 - Current Limit

53 - CONTROL STATE

The Control State display indicates the control or operating state of the M-Drive.

1 - Jog 32 - Run 64 - Ramped Stop 128- Fast Stop

Page C-8

Page 121 read from a scan by OCR; it may hold reading errors

54 - CONTROL MODE

The Control Mode display indicates the status of the optional switch inputs to the M- Drive. This number is a weighted sum of the numbers associated with the switched inputs. This code, along with code 53, is intended for use by the computer interface. It is available through the keypad for trouble-shooting convenience only.

128 - Primary Mode/Secondary Mode 64 ~-Not Used 32 - Closed/Open_Loop 16 - Pri. Setpt. 1/Pri. Setpt. 2 8 - Sec. Setpt. 3/Sec. Setpt. 4 - Local/Computer

4 2 - Keypad Enable/Disable 1 - Ramp Enable/Ramp Disable

To decode the display, subtract the highest number from the above list consecutively from the display number.

For example, a display of 178 would be decoded as: 178 -128 Primary Mode 50 -32 Closed Loop 18 -.16 Primary Setpoint 1 2

-_2 Keypad Enable 0

Also Secondary Setpoint 4, Computer, Setpoint Hold because these numbers were not subtractable.

55 - A/D INPUT

The A/D Input display indicates the status of the Analog Input. This number is filtered but is not zero and span adjusted.

56 - A/D INPUT - ADJUSTED

This monitor variable displays the status of the Analog Input after the zero and span calculations have been made.

Page C-9

Page 122 read from a scan by OCR; it may hold reading errors

57 - POWER LINE FAILURE

MV- 57 is a counter that is incremented every time the AC line falls below the specified level. It can be used to determine if inductive loads are causing line notches or dips. The count can be reset to zero by pressing the “Clear” key when this variable is accessed.

58 - SERIAL COMMUNICATIONS ERROR

MV-58 displays the communications error code for the last message transmitted to the M-Drive. This code is intended for use by the communications interface, and is a weighted sum of the error code bit pattern:

32 Data was out of minimum/maximum range

16 Invalid Parameter Code, Checksum or Decimal Point Error

8 Receive buffer filled before ETX received or Message Format Error 4 Invalid Parameter Data

2 Parity error

1 M-Drive in Local not Computer Mode

0 No errors

To decode the display, subtract the highest number from the list consecutively from the display number.

For example, a display of 37 would be decoded as:

37 -32 Data out of minimum/maximum range if O1

Invalid Parameter Data

M-Drive in Local not Computer Mode

1 ol a|

MV-59: FREQUENCY OVERFLOW

MV-59 is a counter that is incremented every time the frequency inputs to the M-

Drive cause an overflow. The count can be reset to zero by pressing the “Clear” key when this variable is accessed.

60 - CURRENT LIMIT RESPONSE

This parameter can be used to adjust the Current Limit response rate. A higher value for CP-60 will reduce the phase angle at a faster rate going into and out of current limit.

Page C-10

Page 123 read from a scan by OCR; it may hold reading errors

61 - PRIMARY SCALING MODE

This parameter selects the scaling format that is used for setpoint calculation when the Primary Scaling mode is switch selected.

O - Direct 1 - Master

2 - Follower 3 - Offset

62 - SECONDARY SCALING MODE

This parameter selects the scaling format that is used for setpoint calculation when the Secondary Scaling Mode is switch selected.

0 - Direct 1 - Master

2 - Follower 3 - Offset

63 - PRIMARY DISPLAY MODE

This parameter selects the scaling format that is used for the display calculation when the Primary Scaling Mode is switch selected.

1 - Master 2 - Follower

64 - SECONDARY DISPLAY MODE

This parameter selects the scaling format that is used for the display calculation when the Secondary Scaling Mode is switch selected.

1 - Master 2 - Follower

65 -GAIN

Small numbers increase the contribution of the Proportional component (of the PID) except that an entry of 0" eliminates the Gain contribution.

Page C-11

Page 124 read from a scan by OCR; it may hold reading errors

66 - RESET (Integral)

Small numbers increase the contribution of the Integral component (of the PID) except that an entry of “O" eliminates the Reset contribution.

67 - RATE (Derivative)

Small numbers increase the contribution of the Differential component (of the PID) except that an entry of "0" eliminates the Rate contribution.

68 - TRIM AUTHORITY

Trim Authority determines how much of the output is influenced by the Gain, Reset and Rate terms, and how much is determined by feedforward. If it is not possible to achieve stable operation with 100% Trim Authority, reduce this parameter and repeat the tuning procedure.

69 - RATE THRESHOLD

If erratic operation is exhibited only at very low feedback frequencies, the Rate Threshold can be increased slightly. This parameter determines the minimum amount of differential error required before the Rate term influences the control output.

70 - DEVICE ADDRESSES

The M-Drive has a settable physical address from 1 to 32. This is used to separately identify the individual M-Drive units on a multidropped RS422 line. Address references to 0 will globally be accepted by all M-Drive Units.

71 - BAUD RATE There are six different baud or data rates for the M-Drive:

300 Baud 600 Baud 1200 Baud 2400 Baud 4800 Baud 6 = 9600 Baud

1 2 3 4 5 loan iud

Page C-12

Page 125 read from a scan by OCR; it may hold reading errors

72 - CHARACTER FORMAT The M-Drive accepts 3 different character formats: Data Bits, No Parity, One Stop Bit

8 7 Data Bits, Even Parity, One Stop Bit 8 Data Bits, No Parity, Two Stop Bits

1 2 3 73 - CONTROL MASK

When the computer control is switch selected, it is possible to allow the computer to control some of the functions associated with the discrete switch inputs. These include: 1 = Ramp_Enable/Disable 4 = Run/R-Stop 8 = Secondary Setpoint Select 16 = Primary Setpoint Select 32 = Closed/Open Loop 64 = Not Used

128 = Primary/Secondary Control Mode

To delegate control of the selected function to the computer, simply add the associated function number to the total. For example, a value of 36 for code 73 would mean the computer has control of the Closed/Open Loop and the Run/R- Stop functions.

74 - ZERO SPEED LOGIC CP-74 determines the logic of the zero speed discrete output. If CP-74 = “O", the output is controlled only by the Ramped Reference (MV-46). If CP-74 = "1", the output is controlled by both the Ramped Reference and the Feedback (MV-43). The direct effects of CP-74 on the output are:

O Output is HIGH whenever the Ramped Ref is "0" and LOW whenever the Ramped Ref is not "0".

1 Output is LOW whenever Ramped Ref is not "0", but will not go HIGH until both the Ramped Ref and Feedback are "0". Once HIGH the output will not go LOW until the Ramped Ref is not "0". 75 - PRIMARY MODE POSITIVE OFFSET CP-75 is the Primary Mode Positive Offset.

Note: Refer to Chapter 8 for a full discussion of CP-75, CP-76, CP-77, and CP-78. Page C-13

Page 126 read from a scan by OCR; it may hold reading errors

76 - PRIMARY MODE NEGATIVE OFFSET

CP-76 is the Primary Mode Negative Offset.

77 - SECONDARY MODE POSITIVE OFFSET

CP-77 is the Secondary Mode Positive Offset.

78 - SECONDARY MODE NEGATIVE OFFSET CP-78 is the Secondary Mode Negative Offset.

79 - SETPOINT MASK

CP-79 determines which setpoints are disabled when the keypad is locked out (see Page 3-14). The table below identifies the enable/disable status during a keypad lockout for each valid CP-79 value.

CP-79 Setpoints Setpoints Value Enabled Disabled 0 1,2,3,4 None 1 None 1,2,3,4 2 1,3 2,4

80 - ANALOG OUTPUT FUNCTION SELECT CP-80 allocates the Analog Output to the desired Monitor Variable or Control

Parameter. Allocation is accomplished by entering the corresponding code number (CP-xx or MV-xx) for the selected variable into CP-80.

81 - ANALOG OUTPUT RANGE

CP-81 ranges the selected CP-80 variable by determining the value for the selected variable that provides a 100% analog output signal.

Page C-14

Page 127 read from a scan by OCR; it may hold reading errors

82 - ANALOG OUTPUT ZERO

CP-82 is used to zero adjust the Analog Output during calibration. For further details, refer to Chapter 4 (Calibration).

83 - ANALOG OUTPUT SPAN

CP-83 is used to span a just the Analog Output during calibration. For further details, refer to Chapter 4 (Calibration),

84 - ANALOG INPUT FUNCTION SELECT

CP-84 allocates the Analog Input to the desired function. Allocation is accomplished by entering one of the following codes into CP-84:

Code FEunction

Analog Input Not Used

External Reference Freq. Replacement Feedback Frequency Replacement Offset Frequency Replacement Setpoint 1 Replacement

Setpoint 2 Replacement

Setpoint 3 Replacement

Setpoint 4 Replacement

NOOBGM=HO

85 - ANALOG INPUT ZERO

CP-85 is used to zero adjust the Analog Input during calibration. For further details, refer to Chapter 4 (Calibration).

86 - ANALOG INPUT SPAN

CP-86 is used to span adjust the Analog Input during calibration. For further details, refer to Chapter 4 (Calibration).

99 - SOFTWARE CODE REVISION MV-99 displays the code revision number of the M - Drive's software (EPROM).

00 - SOFTWARE PART NUMBER

MV-00 Steck the last four digits of the eight digit part number for the M - Drive's software OM). The first four digits are assumed to be “1000”.

Page C-15

Page 128 read from a scan by OCR; it may hold reading errors

NOTES