Page 35
CALIBRATION 4
INTRODUCTION
This chapter contains the information required to calibrate the current limit and analog input/output of the M-Drive. Prior to using these procedures, the M-Drive must be properly configured and installed in accordance with Chapters 2 and 3 of this Manual.
CURRENT LIMIT
The current limit level on the M-Drive is adjustable from approximately 4 to 15 amps. To limit the load current to the desired limit, follow the procedure below:
1. Place a DC plus AC RMS ammeter in series (or clamp on) with one of the motor armature lines (A1 or A2).
2. Turn the current limit potentiometer at the rear of the M-Drive fully clockwise. This potentiometer is located below the J1 connector.
3. With the M-Drive in the RUN state, gradually increase the load until the AC ammeter reaches the desired limit level.
4. Turn the current limit potentiometer counterclockwise until the M-Drive begins to current limit. This is exhibited by the following conditions: a) A slight reduction in motor RPM b) The front panel "Limit Alarm" LED illuminates C) CP-52 indicates a value of 7.
9. Increase the motor load gradually. The load current should not increase and the motor RPMs should decrease.
The rate at which the M-Drive reduces motor RPMs in response to added load in current limit is adjustable. This value is defaulted at the factory and should not require field adjustment. However, if a different value is desired, adjust CP-60 until the desired response is achieved.
Note: The current limit is not operable when the M-Drive is in Direct Scaling Mode
(CP-61 = 0). For additional information concerning Direct Scaling Mode, refer to Chapter 8 (Advanced Programming).
Page 4-1
Page 36
ANALOG INPUT (Requires Optional Analog I/O Board)
The analog input is factory calibrated for zero and span levels at 0-10 VDC. If it is necessary to field calibrate the analog input, follow these procedures:
Zero Adjust
1. 2.
Enter CP-85 by pressing: Code Select, 8, 5, and “Enter”
Place either zero volts (short) or 4 mA on the analog input depending on the analog input configuration (determined during Chapter 2 procedures).
Press the "." (decimal point) key. The display should now read between 0 and 20. This step zero adjusts the analog input.
Span Adjust
1. 2.
Enter CP-86 by pressing: Code Select, 8, 6, and "Enter".
Place either +10 VDC or 20 mA on the analog input depending on the analog input configuration (determined during Chapter 2 procedures).
Press the "." (decimal point) key. The display should now display a value from 3600 to 4000 for a 10 VDC input. This step span adjusts the analog input.
For a comprehensive discussion of the functional use of the analog input for replacing frequency inputs and setpoints, refer to Chapter 8, Advanced Programming.
Page 4-2
Page 37
ANALOG OUTPUT (Requires Optional Analog I/O Board)
Zero Adjust
The Analog Output is factory calibrated for zero and span levels at + 10 VDC. If it is necessary to field calibrate the analog output, follow these procedures:
1. Place a DC voltmeter or ammeter on J4 pins 17 and 18. (Use a DC voltmeter if the analog output is configured for + 10 VDC, or use an ammeter if the analog output is configured for 4 to 20 mA.)
2. Enter CP-82 by pressing: Code Select, 8, 2, and "Enter". 3. Enter new values for CP-82 until the output on the meter reads zero or 4 mA. (See NOTE below.) Enter values from 0 to 2048 (a value of 1024 is nominal).
Larger values will increase the analog output level. The analog output is now zero adjusted.
Note: Two methods are available for entering new values into the M-Drive: 1) Press the digit keys until the new number is displayed, then press "Enter". 2) Press the scroll keys until the new number is displayed.
Span Adjust 1. Enter CP-83 by pressing: Code Select, 8, 3, and Enter. 2. Enter new values for CP-83 until the meter reads 10 volts or 20 mA. Enter values from 2048 to 4096. Larger values will increase the analog output level. The analog Output is now span adjusted.
A comprehensive discussion of the functional use of the analog output is available in Chapter 8, Advanced Programming.
Page 4-3
Page 38
NOTES
Page 4-4