CLOSED/OPEN LOOP

The Closed/Open loop input determines the basic manner in which the control algorithm operates. In the Closed Loop position, the control algorithm adjusts the Drive output to reduce the error (setpoint minus feedback) to zero. In the Open Loop position, the control algorithm adjusts the drive output in response to setpoint input only and ignores the feedback or error.

Normal operation of the M-Drive occurs in the Closed Loop position. The Open Loop position is used to calibrate the drive during the scaling operation or to monitor non-linearities in the system control loop.

CLOSED LOOP

5 ; aa OPEN LOOP J4

Figure 3-13: Closed/Open Loop Input

PRIMARY/SECONDARY MODE (MASTER/FOLLOWER)

The Primary/Secondary input selects the scaling format used by the control algorithm. The Primary and Secondary modes are user programmable (as described in Chapter 8), but are defaulted to Master and Follower, respectively, as shipped from the factory. A detailed discussion of the scaling modes can be found in the Programming chapters of this manual.

PRIMARY (MASTER)

Om 2

. ak

SECONDARY ( FOLLOWER) J4

Figure 3-14: Primary/Secondary Input

Page 3-11

Page 26 read from a scan by OCR; it may hold reading errors

_ SETPOINT SELECT PRIMARY SETPOINT SELECT (SETPOINT #1 OR SETPOINT #2)

The Primary Setpoint Select input selects the setpoint source when in the Primary scaling mode. In the open position, the setpoint is selected from the Control Parameter 1 entered by the operator. In the closed position, the setpoint is selected from the Control Parameter 2 entered by the operator. A more detailed discussion of the selectable setpoint feature is available in the Advanced Programming chapter of this manual.

CONTROL PARAMETER 1

~ 4

J4

Oo - CONTROL PARAMETER 2*

Figure 3-15: Primary Setpoint Select

SECONDARY SETPOINT SELECT (SETPOINT #3 OR SETPOINT #4)

The Secondary Setpoint Select input selects the setpoint source when in the secondary scaling mode. In the open position, the setpoint is selected from the Control Parameter 3 entered by the operator. In the closed position, the setpoint is selected from the Control Parameter 4 entered by the operator. A more detailed discussion of the selectable setpoint feature is available in the Advanced Programming chapter of this manual.

CONTROL PARAMETER 3

SN 16 il

Oo - CONTROL PARAMETER 4* id J4

Figure 3-16: Secondary Setpoint Select

Page 3-12

Page 27 read from a scan by OCR; it may hold reading errors

RAMP DISABLE

The Ramp Disable input is used to inhibit acceleration or deceleration. Acceleration ramp and deceleration ramp are locked in place until the Ramp Disable input is released.

The only exception to the Ramp Disable function is the F-Stop state. If an F-Stop is called for, the speed drive output is immediately reduced to zero, ignoring the Ramp Disable input.

ACTIVE

HOLD

74

Figure 3-17: Ramp Disable

KEYPAD LOCKOUT

The Keypad Lockout input is used to disable the front operator keypad from making setpoint and other parameter changes. The specific setpoints “locked out" during a

Keypad Lockout condition are determined by the Setpoint Mask value (CP-79). See Page -14 for information concerning Setpoint Mask.

All functions associated with monitoring or viewing of variables remain enabled during Keypad Lockout.

ENABLE SN 1 LOCKOUT J4

Figure 3-18: Keypad Lockout

Page 3-13

Page 28 read from a scan by OCR; it may hold reading errors

LOCAL/COMPUTER

The Local/Computer input is used to enable the serial communi- cations interface to change control variables or selected control commands. In either position, the serial communications is active to monitor variables, but only in the closed position can the serial communications change the control and command variables. More detail on the communications interface is available in Chapter 8 of this manual.

LOCAL NN, IT ry o. 12 COMPUTER

74

Figure 3-19: Local/Computer Input

REMOTE SCROLL UP

The Remote Scroll Up input increments the active setpoint (see Setpoint Select on Page -12 for setpoint selection information). This input increments the active setpoint whether or not the setpoint is displayed.

There are two methods to increment the active setpoint using Remote Scroll Up. Each closure of this input increments the active setpoint 1 Engineering Unit. In addition, the active setpoint increments 1 Engineering Unit every half second while this input is held closed.

NO EFFECT we 13 ° 14 3 REMOTE SCROLL UP 74

Figure 3-20: Remote Scroll Up

Page 3-14

Page 29 read from a scan by OCR; it may hold reading errors

REMOTE SCROLL DOWN

The Remote Scroll Down input decrements the active setpoint (see Setpoint Select on Page 3-12 for setpoint selection information). This input decrements the active setpoint whether or not the setpoint is displayed.

There are two methods to decrement the active setpoint using Remote Scroll Down. Each closure of this input decrements the active setpoint 1 Engineering Unit. In addition, the active setpoint decrements 1 Engineering Unit every half second while this input is held closed.

NO EFFECT

~ fd

° REMOTE SCROLL DOWN

J4

Figure 3-21: Remote Scroll Down

ANALOG INPUT (Requires Optional Analog I/O Board)

The Analog Input can be used to replace either one of the three frequency inputs or one of the four internal setpoint inputs. (For a detailed discussion concerning analog input uses, refer to Chapter 8 - Advanced Programming.) Figure 3-22 below illustrates the wiring for the analog input.

Note: The Analog Input can accept either a 0 to 10 VDC or 4 to 20 mA current source. Refer to Chapter 2 - Configuration, for the Analog Input configuration procedure.

SHIELD 19 |

J3 INPUT SIGNAL N 16 COMMON 17

4 Figure 3-22: Analog Input

Page 3-15

Page 30 read from a scan by OCR; it may hold reading errors

4) ELECTIVE OUTPUTS

CONTROL OUTPUTS

The M-Drive Control Outputs are all open-collector relay drivers (specs listed on Page viii). An external DC power supply is required to provide power to the relays. Free-wheeling diodes are incorporated and need not be added externally.

Figure 3-23 illustrates the wiring for the first three elective outputs. The remaining outputs follow the same pattern.

Diode Protect 8 + EXT. Zero Speed 9 (a1) be = POWER High Alarm 1d (R2) SUPPLY Low Alarm il (R3) (50V Max) Common 14 - J1

Figure 3-23: Elective Outputs

Page 3-16

Page 31 read from a scan by OCR; it may hold reading errors

ZERO SPEED (J1 Pin 9)

The Zero Speed output may be controlled either by the Ramped Reference, or by both the Ramped Reference and the Feedback. For additional information, refer to CP-74 on Page C-13.

HIGH ALARM (J1 Pin 10)

The High Alarm output is used to indicate when the speed, as identified by the Feedback Input, exceeds a level that is specified by the operator. The High Alarm output is high (inactive) when the feedback is below this level. Itis low (active) when the feedback is at or above this level. (See CP-13 on Page C-3.)

LOW ALARM (Ji Pin 11)

The Low Alarm output is used to indicate when the feedback is below a level that is specified by the operator. The Low Alarm output is high (inactive) when the feedback is above this level. It is low (active) when the feedback is at or below the specified level. (See CP-12 on Page C-3.)

RAMPED ERROR (ERROR ALARM 1) (J1 Pin 12)

The Ramped Error output is used to indicate when the speed error (Ramped Reference minus feedback) is at or outside a band specified by the operator. This output is high (inactive) when the error is within the specified band. It is low (active) when the error is at or exceeds the specified band. (See CP-14 on Page C-3.)

SCALED ERROR (ERROR ALARM 2) (J1 Pin 13)

The Scaled Error output operates the same as the Ramped Error, except the speed error is: (Scaled Reference minus feedback). (See CP-15 on Page C-3.)

Page 3-17

Page 32 read from a scan by OCR; it may hold reading errors

ANALOG OUTPUT (Requires Optional Analog I/O Board)

The Analog Output can be patched to any of the monitor variables or control parameters of the M-Drive. (For a detailed discussion concerning analog output uses, refer to Chapter 8 - Advanced Programming.) Figure 3-24 below illustrates the wiring for the analog output.

Note: The Analog Output can be configured for either a + 10 VDC or 4 to 20 mA level. Refer to Chapter 2 - Configuration, for the analog output configuration procedure.

7 SHIELD Jl 17 L COMMON i 18 | SIGNAL OUTPUT g4

Figure 3-24: Analog Output

Page 3-18

Page 33 read from a scan by OCR; it may hold reading errors

5) SERIAL COMMUNICATIONS

The Serial Communications interface on the M-Drive complies with EIA Standard RS-422 -A for balanced line transmissions. This interface is provided to permit remote computer variable programming, status or performance monitoring, and remote control. A detailed discussion of the Serial Communications capability is provided in Chapter 7 of this manual.

Figures 3-25 and 3-26 illustrate a multidrop installation of the Serial Communications link.

Contrex Micro-Module 100

RS232 to RS422

Converter 3200-1800 or equivalent a ¥

RXD TXD B +. + COM int

J1 M-Drive #1

@ 3 | -TXD |, - _ - _ - 21+TXD A J1 M-Drive #2

Figure 3-25: Serial Communications Connections

Page 3-19

Page 34 read from a scan by OCR; it may hold reading errors

A it may be necessary to terminate the communication line at the furthest receiving ends only. A 100 ohm, 1/2 Watt resistor is usually adequate for this purpose. For more information, refer to EIA Standard RS-422-A.

VEN Shield at one end of cable only.

M-Drive M-Drive M-Drive RS232 TO HOST RS422 CONVERTER M-Drive M~Drive M-Drive

Figure 3-27: Correct M-Drive Multidrop Installation

M-Drive M-Drive M- ve ee | HOST CONVERTER M-Drive M-Drive M-Drive

Figure 3-28 Incorrect Installation

Page 3-20