Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 3 of 20

M-Drive: M-Drive 3 Installation, pages 15 to 24

Pages 15 to 24 of 148, from M-Drive

The original document is the PDF (4.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Fenner M-TRIM-2 and Contrex M-TRIM-2

Page 15 read from a scan by OCR; it may hold reading errors

INSTALLATION 3

INTRODUCTION

This chapter contains the information and procedures required to complete the initial installation and wiring for the M-Drive. All pages within this chapter must be read to ensure that the appropriate decisions are made prior to the final wiring of the M-Drive.

Note to Electricians installing the M-Drive:

- Class G branch circuit fuses rated 250V, 15 A shall be provided in the end application.

- Motor overload protection shall be provided in the end installation in accordance with the NEC.

The installation of this motor control must conform to area and local electrical codes. For information, refer to the National Electrical Code

(NEC) Article 430 published by the National Fire Protection Association, or the Canadian Electrical Code (CEC). Refer to local codes as applicable.

WARNING Hazardous voltages are present during certain installation

Procedures. Therefore, the M-Drive should only be installed by qualified electrical maintenance personnel.

This chapter is organized into 2 distinct sections: MOUNTING WIRING

The Mounting section provides drawings and instructions for mounting the M-Drive in an enclosure. The wiring section summarizes the wiring connections for the M-Drive.

Page 3-1

Page 16 read from a scan by OCR; it may hold reading errors

MOUNTING INTRODUCTION

The M-Drive is packaged in a 1/2 DIN Vertical instrument enclo- sure intended for door mounting in a NEMA enclosure. Figure 3-1 illustrates an installed M-Drive with dimensions.

Note: Prior to mounting the M-Drive in your enclosure, complete the Configuration Procedures outlined in Chapter 2. The configuration shunts and switches may be less accessible after the device is installed in the enclosure,

DOOR PANEL

* To rear of Connectors from Front Panel

Figure 3-1: M-Drive Dimensions Page 3-2

Page 17 read from a scan by OCR; it may hold reading errors

MOUNTING PROCEDURE

Mount the M-Drive into your enclosure according to the following procedure: 1. Ensure the mounting location meets the environmental conditions for the M-Drive:

Temperature: 0-55 degrees C (interior enclosure) Humidity: 0-90% non-condensing

Note: Allow adequate spacing between the M-Drive and other equipment to provide for proper heat convection. Placing the M-Drive too close to adjacent equipment could cause the interior ambient temperature to exceed 55 degrees C. Spacing requirements depend on air flow, enclosure construction and applied horsepower.

2. Determine the appropriate door or panel location and make the panel cutout per Figure 3-2 below. Allow adequate top and bottom room for mounting bracket.

3. Insert the M-Drive from the panel front up to the bezel or gasket. 4. Connect the two mounting brackets from the rear of the M-Drive on the top and bottom.

5. Drive the mounting bracket screws onto the rear of the door or panel until the M-Drive is securely mounted. PMounting i Bracket I

7a

Panel

7.25" + .03" Cutout 20" i Mounting I L Bracket, - 3.65" +..03", - >|

Figure 3-2: Panel Cutout Dimensions Page 3-3

Page 18 read from a scan by OCR; it may hold reading errors

WIRING INTRODUCTION

The wiring portion of this chapter is divided into five sections:

Required Inputs Required Outputs Elective Inputs

Elective Outputs

Serial Communications

UPoOh =

As the titles indicate, the decisions made during the Required sections are mandatory to obtain a properly installed M-Drive. The elective sections are completed at the discretion of the User.

The Serial Communications connections are discussed as a separate item in the fifth and final wiring section.

CAUTION

Where indicated, it is important to use shielded cable to minimize equipment malfunctions due to electrical noise. It is assumed throughout this manual that shields are terminated at the receiving end only.

Proper earth grounding of all electronic equipment is required for successful Operation. It is recommended that all shield and chassis ground connections be made to an earth ground to provide proper noise immunity and grounding protection.

AC power wiring (J2) should be kept physically separated from other wiring on the M-Trim. Failure to do so could result in coupled electrical noise and subsequent M-Trim malfunction.

Inductive coils from relay, contactors, solenoids, etc. on the same AC power line or in the same enclosure should be suppressed with an RC network across the coil. Best results occur with resistance (r) values of 50 ohms and capacitance (c) values of 0.1 microfarads.

lf excessive EMI noise exists on the AC power line, such as line notches or spikes, it may be required to install an AC line filter or isolation transformer to ensure proper operation.

Page 3-4

Page 19 read from a scan by OCR; it may hold reading errors

M-DRIVE WIRING DRAWING

Figure 3-3 below illustrates the control installation wiring for the M-Drive. It is divided into Required Inputs and Outputs, Elective Inputs and Outputs and Serial Communications.

n M-Drive j Motor Ey Fl+ 2 Ll, - _ - - - 5 1 Field 8 Neutral L2, - - - - __6 | 32 J2 [32 FR -yYy_] © Chassis Gnd 7 3 LA2 ~ Armature 2 +12V (5 mA Max) T 3 3 CO J3 ; o Oo [ rT] Drive Output ® & Feedback 6 1, m 7 ie) R=-Sto il & Pp 6EY + 3 RUN o - 13 id g F-STOP rote 14 15 me em, _ | mmm 1) Ext. Ref. rans 2 bn Freq. Inp. LI 3 rt, 8 + a a 4 9 Zero Speed 3 JOG oO 16 1 High Alarm © Ji | il Low Alarm ® Offset Freq. Ft 8 127] Dev Alarm l a Input 9 a 13 Dev Alarm 2 re) Sn 14 - 0 om Spare oe 4 pl Closed/ 5 n = } e » Open Loop 6 A ow J4 | 17 (Common) Analog =) ar J4 18 (Signal) Output rt Keypad 9 1 (Optional) wo Lockout $ 2 e 2 Primary/ 0 3 id g + Sec Mode io) lt eee & rf f famp oe u 1 < +12V b Disable 8 2 < + a Primary 2 a 9 it 3, = = 3 SetPt Sel lL J1 4, < + wg XD z Secondary 3, - 5 ~~ 8 SetPt Sel 40 18 5] 6 < COM (OPT) e } 1l rh 7 Ci] Local/ oo 12 vc Computer = 3 Rmt Scroll 13 UP t - 14 Rmt Scroll oo 15 id DN Analog (signal) a 16 Input (common) wai me (Optional) rT

Figure 3-3: M-Drive General Wiring Drawing Page 3-5

Page 20 read from a scan by OCR; it may hold reading errors

M-DRIVE CONNECTOR LOCATIONS

Figure 3-4 below illustrates the location and numbering of the wiring connectors as viewed from the rear of the M-Drive.

1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 J3 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 16 J1 1 2 3 4 5 6 1 7 2 8 3 J4 9 4 10 5 11 6 12 7 13 14 J2 15 16 17 18

Figure 3-4: Wiring Connector Locations

Page 3-6

Page 21 read from a scan by OCR; it may hold reading errors

1) REQUIRED INPUTS

INPUT POWER

The M-Drive operates on either 115 VAC or 230 VAC. The lowest 3 pin connections on J2 are allocated for the power connection.

Ll 5 NEUTRAL OR L2 6 CHASSIS GND 7

J2

Figure 3-5: Input Power

FEEDBACK INPUT Feedback Input is a pulse train input used by the M-Drive to ascertain motor speed. The specific Feedback Input connections to the M-Drive are identical whether the sensor is a Magnetic Pickup, Encoder, Hall Effect Quad Sensor or Proximity Sensor. The Feedback Input connections are illustrated below:

+12V *(OPT) . 1

SIGNAL a 5

COMMON . 6

SHIELD 7 vy J3

Figure 3-6: Feedback Input Connections

* Amplified or 3-wire sensors will contain their own source supply voltage or use the M-Drive + 12VDC if their current draw does not exceed 50 milliamps total.

Page 3-7

Page 22 read from a scan by OCR; it may hold reading errors

RUN

RUN is a momentary input which when closed allows the M-Drive to run normally. Asa momentary input, the RUN state is internally latched and need not be maintained by the operator device.

RUN

12

13

J3

Figure 3-7: Run Input

R-STOP R-STOP is a momentary input which when opened commands the M-Drive to ramp to zero speed at the specified deceleration rate. As a momentary input, the R-STOP state is internally latched and need not be maintained by the operator device.

R-STOP il

12

J3

Figure 3-8: R-Stop Input

Page 3-8

Page 23 read from a scan by OCR; it may hold reading errors

F-STOP

F-STOP is a momentary input which when opened commands the M-Drive to come to zero speed immediately, ignoring the specified deceleration rate. As a momentary input, the F-STOP state is internally latched and need not be maintained by the operator device.

F-STOP

14

0) Oo - 15

4

J3 Figure 3-9: F-Stop Input

Note: Both the R-STOP and F-STOP inputs must be closed prior to entering the RUN state. If only one of the Stop inputs is used, the other needs to be wire shorted for proper M-Drive operation.

2) REQUIRED OUTPUTS MOTOR CONNECTIONS

Connect the armature leads to J2 pins 3 and 4. Reversal of the armature leads reverses the direction of motor rotation.

Connect the field leads to J2 pins 1 and 2. Permanent magnet (PM) motors do not require field connections. Figure 3-10 below illustrates the motor connections.

1 [+ 1 |+ 2 [7 F2 6YYY\__FL] 2 F2 (YYY\FI1 OR

3 - 3 ~ - + A2, + Al A2 Al

4 + 4a +

| J2 4-W1RE J2 3-WIRE

Figure 3-10: Motor Connections

Page 3-9

Page 24 read from a scan by OCR; it may hold reading errors

3) ELECTIVE INPUTS

EXTERNAL REFERENCE FREQUENCY INPUT

The External Reference Frequency Input is a frequency input that acts as the lead signal when the M-Drive is in Follower Format. This signal is proportioned by the ratio setpoint to control the speed of the Follower M-Drive.

If this input is used, install per Figure 3-11.

+12V *(OPT) . I

SIGNAL . 2

COMMON . 3

SHIELD 4 y J3

Figure 3-11: External Reference Frequency Input

JOG

JOG is a maintained input which when closed drives the motor at the selected jog speed. As a maintained input, the jog state is only valid for the duration of the time the operator device is held closed.

JOG tt 15 16 iy J3

Figure 3-12: Jog Input

Page 3-10